background image

 

NOVUS AUTOMATION

 

www.fieldlogger.net 

73/104

 

INPUT TYPE 

CONDITION OF INPUT SIGNAL 

INDICATION 

Current (mA): 

4 to 20 mA 

and 0 to 20 mA 

Within the range 

Value read from input 

Disconnected signal  

4 a 20 mA: Value of configured error 

0 to 20 mA: 0 mA 

Just above the upper limit 

Value read from input * 

A little below the lower limit 

4 to 20 mA: Value read from input * 

0 to 20 mA: it is not possible to 

decrease besides the inferior limit  

Far above the upper limit 

Value of configured error 

Far below the lower limit 

4 to 20 mA: Value of configured error 

0 to 20 mA: it is not possible to 

decrease besides the inferior limit  

 (*) Note: 

The indication of the analog channel is still a bit beyond the limits specified for the selected input type. However, in this condition, the 

accuracy is not guaranteed. 

Table 01 

- Measurement and indication of the 

FieldLogger

 input types

 

For each channel, you have to choose the digital filter to be used in this channel reading, with valid values between "0" 
(no filter) and "20" (maximum filter): the higher the value of the filter is, the lower are there fluctuations read in the input, 
but the slower is the channel response to changes in the input signal. 

There is also the feature of inserting up to 10 points for each channel in order to correct distortions in the reading of 
these channels at these points.  We call this feature "custom calibration," because it allows the user to adjust the 
indication at the desired points, resetting to zero the error on these points. Between the inserted points, the adjustment is 
done linearly, depending on the entered values. It is important to point out that the insertion of custom calibration points 
is optional, available only to those who want to adjust the indication with a local standard, because 

FieldLogger

 already 

comes fully calibrated from the factory. 

 

Whenever you change the input type, make sure that the custom calibration points of the previous input 
are deleted! 

For each channel, you must assign a unique name (tag), which will be used to reference the channel. You should also 
choose the type of input (sensor) that will be connected to that channel.  In addition, you can assign the unit for the 
measured value: when temperature sensors (Pt100, Pt1000 or thermocouples) are involved you must choose between 
Centigrade  (°C) and Fahrenheit degrees (°F);  when linear sensors (voltage or current) are involved, you can type the 
desired unit. 

In the case of linear input types, you should choose what the indication range of the channel is, in other words, what the 
channel must  indicate when the input is at its minimum value and what it should indicate when at its maximum value 
(minimum and maximum values considering the working range of the 

FieldLogger

 for the selected input type). Example: 

selecting  the  4-20 mA input type connected to a  0 to 2 bar pressure transmitter.  In this case, we must choose the 
minimum value in the configuration of the input "0.0" and the maximum value  "2.0".  All the available resolution and 
accuracy will be contained in the selected range. 

When using any equipment on analog inputs that are connected to the power network (for example: thermocouples or 
voltage simulator), it is recommended not to use the USB interface for communicating. In some cases, it was noticed the 
occurrence of noise and offsets in the readings due to the influence of the USB cable connection, probably due to ground 
loops. 

DIGITAL INPUTS/OUTPUTS 

FieldLogger

 has eight digital channels that can be individually configured as inputs or outputs. 

Channels configured as inputs, if enabled, may be logged in memory, used as alarm inputs and as operands of virtual 
channels. Channels configured as outputs are "open-drain" type and may be triggered by alarms or triggered via external 
Modbus commands. 

The digital inputs have two (floating point) values associated with their logic states during the equipment configuration. 
Depending on  the input’s current logic state ("0" is equivalent to a low voltage or a closed contact in the input;  "1" is 
equivalent to a high voltage or an open contact in the input), this corresponding value is used by the virtual channels, 
alarms and logs. 

The digital outputs configured to be controlled by the  alarms  cannot  be triggered by external Modbus commands. 
Likewise, the outputs configured to be controlled by external Modbus commands cannot be used by the alarms. 

The outputs controlled by external commands can be used, for example, as control outputs or alarm outputs of SCADA 
software or PLCs. 

 

The digital inputs/outputs terminals are not isolated from the analog inputs terminals! 

Do not use analog  and digital signals coming from the same voltage source; this will cause the 
equipment to malfunction. 

Содержание fieldlogger

Страница 1: ...ONFIGURATION 25 ETHERNET INTERFACE CONFIGURATION 26 ETHERNET INTERFACE CONFIGURATION TCP IP 27 ETHERNET INTERFACE CONFIGURATION FTP 28 ETHERNET INTERFACE CONFIGURATION SMTP 30 ETHERNET INTERFACE CONFI...

Страница 2: ...DEBUGGING 78 WEB PAGES HTTP 79 UNCHANGEABLE PAGES 79 CUSTOM PAGES 81 FILE TRANSFER FTP 84 NETWORK MANAGEMENT SNMP 84 CLOUD 85 PREREQUISITES 85 OPERATION 86 DEBUGGING 86 DATA LOGGING AND DOWNLOAD 86 AL...

Страница 3: ...n The analog input channels are configurable for reading voltage current thermocouples Pt100 and Pt1000 signals These inputs count on the precision of a 24 bit A D converter with high acquisition spee...

Страница 4: ...the installation on the rail you must pull out the two clamps located right below the connections of the channels taking care not to remove them as per Fig 01 Note If necessary the connector may be r...

Страница 5: ...NOVUS AUTOMATION www fieldlogger net 5 104 And finally push the two clamps until you hear a double click for the complete installation as per Fig 03 Fig 03 DIN rail installation...

Страница 6: ...NOVUS AUTOMATION www fieldlogger net 6 104 Dimensions Without HMI module Fig 04 Dimensions of the FieldLogger without HMI module Fig 05 Dimensions of FieldLogger side without HMI module...

Страница 7: ...NOVUS AUTOMATION www fieldlogger net 7 104 With HMI module Optional Fig 06 Dimensions of the FieldLogger with HMI module Fig 07 Dimensions of FieldLogger side with HMI module...

Страница 8: ...ll the lever at the right side of the FieldLogger up to the end When attaching it insert the cover left side first and press its right side gently After that press the lever back into the chassis Fig...

Страница 9: ...s document to draw the user s attention to important operational and safety information CAUTION or WARNING Read complete instructions prior to installation and operation of the unit CAUTION or WARNING...

Страница 10: ...must be wired near to the FieldLogger 2 A switch or circuit breaker placed near to the FieldLogger shall be used as the disconnecting device Fig 14 Lower side connections RECOMMENDATIONS FOR INSTALLAT...

Страница 11: ...When configured as outputs they can activate limited power loads please check the Specifications section Fig 18 Connection of a load RL to a digital output The digital inputs outputs terminals are not...

Страница 12: ...dc power supply available in the FieldLogger for powering transmitters in the field This auxiliary power supply is electrically isolated from the other FieldLogger terminals Below is the correct way t...

Страница 13: ...accordance with the figure at the left Please observe the correct connection polarity Cables used for connecting thermocouples must have the same thermoelectric characteristics of the used thermocoup...

Страница 14: ...the exportation for the most diverse data formats Ethernet Interface used for Ethernet 10 100 communication It is recommended to use a category 5 or better cable in a RJ45 connector The Ethernet conne...

Страница 15: ...d If it is OK try rebooting the machine by turning off its power supply and restarting it after 10 seconds If the LED continues to indicate an error there may be something wrong with your FieldLogger...

Страница 16: ...ed 1 During the boot you should press the F8 key to enter the Start up Configurations 2 Pressing the F7 key you can disable the Imposition of the Driver Signature 3 Windows 8 will now allow you to ins...

Страница 17: ...NOVUS AUTOMATION www fieldlogger net 17 104 3 Locate the FieldLogger probably with an icon with an exclamation mark next to it and double click on it 4 Click on the button Update Driver...

Страница 18: ...t 18 104 5 Ask to Browse my computer for driver software 6 Enter the path of the folder where the drivers are located the product CD or folder where you saved them when downloaded from the site 7 Wait...

Страница 19: ...indicate that it cannot verify the editor of this driver Confirm to install anyway 9 A message indicating successful installation will display 10 Returning to the Device Manager screen you can check...

Страница 20: ...Select Port Settings guide and click on Advanced In the COM Port Number select the serial port to be associated with FieldLogger Some serial ports can be checked while being used In Use Just select on...

Страница 21: ...its features will be detailed in the chapter FieldLogger Operation On the main screen you should choose the function that you want to run as it is shown below Configuration Allows you to change the Fi...

Страница 22: ...on saved to a file If the chosen option was to create a new configuration you must specify a file where this configuration will be saved Besides that from software version 1 40 on you must select whic...

Страница 23: ...he icon bar at the bottom of the window has icons for the following functions as they are described below Back It allows coming back to the previous configuration screen Save Saves the current configu...

Страница 24: ...nels and status of the FieldLogger o Overall configuration and reading HMI can be used to configure parameters its own and some of FieldLogger in addition to viewing the channels and status of the Fie...

Страница 25: ...ed at all It is recommended to disable the interface if it is not used When it is used as a slave you must configure your Modbus address the baud rate parity and number of stop bits When it is used as...

Страница 26: ...T INTERFACE CONFIGURATION The configuration of the Ethernet interface should be carried through on the next screen If it is desired not to use this interface it is recommended to disable it as shown i...

Страница 27: ...n of using fixed IP or DHCP and in the case of fixed IP to choose the parameters relating to it such as FieldLogger IP the subnet mask and default gateway Moreover we must choose whether or not to use...

Страница 28: ...ect to an FTP server to send data from its logging memory internal or SD card This can either be done once a day at a set time or many times a day from firmware version 1 50 on in a configurable time...

Страница 29: ...NOVUS AUTOMATION www fieldlogger net 29 104 Ethernet Interface FTP Configuration Example 2...

Страница 30: ...subject maximum of 32 characters and has a part of the message body that is user defined up to 64 characters and that is the same for all alarms or events The e mail of the sender maximum of 50 chara...

Страница 31: ...ured by clicking on the SNMP button SNMP in the FieldLogger is read only Thus you should set up the community for access maximum of 16 characters and connection port For using traps you must enable th...

Страница 32: ...ge with some data from the equipment This page has an auto refresh parameter indicating to the navigator software browser that the page should be reloaded with updated data from time to time For this...

Страница 33: ...tood as being targeted to a RS485 slave in the RS485 network reached through the gateway function On this case if this functionality is enabled the data packet will be forwarded to the RS485 bus When...

Страница 34: ...ore sending the configuration to the FieldLogger From firmware version 1 61 on it is also possible to write to FieldLogger digital outputs and to its alarm setpoints from NOVUS Cloud Writing to the di...

Страница 35: ...more filtered is the indication of the channel making the response more immune to noises on the input signal but also slower to respond to variations maximum filter value is 20 There is the option of...

Страница 36: ...NOVUS AUTOMATION www fieldlogger net 36 104 Analog Channels Configuration of a linear channel...

Страница 37: ...e standard value and write down the value indicated by the equipment 3 Afterwards insert the pairs of Custom Calibration points source value and indicted value and apply the configuration Analog Chann...

Страница 38: ...ayed when in 0 level low voltage level or contact closed at the input and another value to be indicated when in 1 level high voltage level or contact open at the input These values will be shown in th...

Страница 39: ...puts to be activated from NOVUS Cloud The state ON OFF is not held permanently which means it will lose its state after a reset Sending a new configuration will not change the state of the outputs as...

Страница 40: ...made on the next screen is only available when the RS485 interface has been configured as a Modbus master In the case of the RS485 interface having been configured as a slave or disabled the remote c...

Страница 41: ...o be configured This value is shown on the channel when there is a problem for example a communication error with the slave The number of decimal places of the channel value must be inserted in the De...

Страница 42: ...each channel if the communication fails in all attempts it will display the error value set up for the channel The maximum response time valid range 2 to 10 000 ms indicates how long after sending the...

Страница 43: ...en Constant Value there should be placed the numeric value of the channel Finally one should choose a unit optional maximum of 10 characters for the channel plus an error value and the number of decim...

Страница 44: ...resis shall not be used must be configured with 0 Each alarm can have one or more associated actions You should then choose what actions should be performed on the occurrence of an alarm or event diff...

Страница 45: ...NOVUS AUTOMATION www fieldlogger net 45 104 Alarms Configuration Digital outputs selection Alarms Configuration Logs control configuration...

Страница 46: ...NOVUS AUTOMATION www fieldlogger net 46 104 Alarms Configuration E mail receivers selection Alarms Configuration Enabling SNMP traps...

Страница 47: ...NOVUS AUTOMATION www fieldlogger net 47 104 Alarms Configuration Selection the internal variables Alarms Configuration Alarm added to the list...

Страница 48: ...esired log rate The channels can be selected for logging moving them from the left side column available channels to the right side column channels to be logged A maximum of 100 channels can be logged...

Страница 49: ...ading will be used for writing In any other case we must choose which interface to use for sending the configuration At the end of the transmission a message shall appear indicating the success or not...

Страница 50: ...eries of configuration parameters of the RS485 interface For the Ethernet interface the current status connected or not is indicated as well as the IP and MAC numbers Shows the current status of the c...

Страница 51: ...elect the channel to be displayed and its associated color on the chart When all desired channels are selected you must click on the Start button and the channel values will be read every 2 seconds ap...

Страница 52: ...time status of all configured alarms or events At the top there is an indication of how many alarms are enabled and how many are in a state of alarm In the list below the settings for each alarm are s...

Страница 53: ...ate a folder on their computer or their network where a logging database will be created This database may have data from one or more FieldLogger s and will be the destination of all data downloaded f...

Страница 54: ...m a SD card The card must have been used in FieldLogger as the logging memory target Recommended when the card has too much logging data because it is the fastest way of moving data to the computer Do...

Страница 55: ...CP or RS485 Modbus RTU and there are many FieldLogger s in the network Then the FieldLogger memory where logged data is internal flash or SD card must be chosen In case you selected to download data f...

Страница 56: ...will start and a progress bar will be displayed in order to indicate the download progress Once it is ready a new screen will be opened for data visualization export the same described in the Downloa...

Страница 57: ...he way data will be processed The available ways include viewing in table format viewing in chart format export data to a well known file type and creation of a report with the desired data In the nex...

Страница 58: ...MATION www fieldlogger net 58 104 In the next screen user must select which FieldLogger data would like to be viewed Selection is done by their serial number After that the desired time period must be...

Страница 59: ...aylight saving time By leaving it unchecked original timestamps will be shown This option does not change the downloaded data but only the way they are visualized Table format view This kind of view s...

Страница 60: ...in chart format Passing the mouse over the chart shows the instantaneous values of each viewed channel at the bottom part of the screen In order to view data in this format no more than 16 channels ca...

Страница 61: ...r net 61 104 Data export To export the selected data you must click on the Export button After a prior processing a window will appear where you must select the destination folder the file name and th...

Страница 62: ...u can choose the most appropriate file format RTF HTML XML PDF CSV SQL XLSX and DOCX For exporting in SuperView or FieldChart format there is a top limit of 16 channels For exporting in PDF or RTF for...

Страница 63: ...be filled like report author name company name and report title An image can also be selected to be presented in the report When clicking on the OK button data is processed a progress bar is showed at...

Страница 64: ...NOVUS AUTOMATION www fieldlogger net 64 104 At the end clicking on the OK button will generate and show the report This report can be printed or saved to a file for later access...

Страница 65: ...sons The proper procedure is to select the source folder of the logged data logging database In the available downloads field will be displayed all devices that have downloaded data available You must...

Страница 66: ...OVUS AUTOMATION www fieldlogger net 66 104 Then select which channels among those available are of interest Finally the chosen channels can be viewed in several ways Viewing logged data in table forma...

Страница 67: ...re is a button on the upper left corner that allows users to print the chart To export the selected data you must click on the Export button After a prior processing a window will appear where you mus...

Страница 68: ...more control over the fields and formats of the exportation The basic window with the format choice became different Whenever choosing the Other formats options a second window pops up allowing the ch...

Страница 69: ...is no last file the software will indicate the error and display the initial screen Download Logging Data It will open the screen where you can choose what type of download will be performed Open Dia...

Страница 70: ...Export parameters All parameters are separated by semicolons ACTION TYPE The following actions are allowed 1 to download and export data 2 to export data from the data base 3 to download data without...

Страница 71: ...d data from the last X days Example 11097831 3 For Action 3 we need the following additional parameters their order should be respected 1 Data source It can be 0 when downloading data from device inte...

Страница 72: ...of input signal has a valid range of measurement detailed in the Specifications section of this manual However the equipment usually can measure signals that exceed the limits of this range How far be...

Страница 73: ...olved you must choose between Centigrade C and Fahrenheit degrees F when linear sensors voltage or current are involved you can type the desired unit In the case of linear input types you should choos...

Страница 74: ...simply made available via another interface Ethernet for example Please see the Remote Channel section for details of how to implement a Modbus RTU network with FieldLogger in the master role From fi...

Страница 75: ...ts value by 10 restoring the original temperature value This virtual channel could then be used to replace the remote channel for logging alarms or simple indication VIRTUAL CHANNELS There are up to 1...

Страница 76: ...te 1 Available from firmware version 1 10 on 2 Note 2 Available from firmware version 1 20 on 3 Note 3 Available from firmware version 1 40 on When an error occurs on any channel for example disconnec...

Страница 77: ...USB flash drive all logging data found from the last four days that actually have some logged data Remarks Use a USB flash drive with enough space for all data that must be downloaded preferably an em...

Страница 78: ...smaller than that value a timeout must occur instead of an exception code 0Bh Gateway Target Device Failed to Respond in a missing slave situation SENDING E MAILS SMTP FieldLogger can be configured to...

Страница 79: ...s are available in the product CD which allows the external usage of this data increasing application flexibility a typical application is the generation of a customized HTML page with data read from...

Страница 80: ...et 80 104 The configuration and status information page has the current status of some parameters as well as serial number firmware version and other information from the equipment Fig 23 Configuratio...

Страница 81: ...rv folder in the SD card FieldLogger works in the 8 3 file name format so no file should have more than 8 characters plus the 3 of the extension Files with markers that should be replaced by FieldLogg...

Страница 82: ...Analog channel 8 diagnostics information value Bit 0 open sensor Bit 1 shorted Pt100 Pt1000 Bit 2 out of limits Bit 3 Pt100 Pt1000 open cable DIGITAL__001 T Digital channel 1 tag DIGITAL__001 V Digita...

Страница 83: ...ou Via Modbus Only INFO IN STOP__ Stop logging mode selected Full Memory Circular Memory Date Time ou Alarm INFO IN FDRVIN USB flash drive connection status Yes connected or No disconnected INFO IN SD...

Страница 84: ...haracters or 0Dh and 0Ah in hexadecimal Server To use FTP server on FieldLogger simply enable this feature in the Configurator application and set up a username and password In this way the user will...

Страница 85: ...the index of the occurred alarm o Type OCTET STRING o Value String indicating the occurred alarm in the format TAG CONDITION VALUE Example Channel_1 129 43 CLOUD From firmware version 1 60 the FieldL...

Страница 86: ...which must be inserted into the proper compartment behind the cover or HMI as shown in Fig 20 The internal memory capacity is up to 532 480 loggings while SD card logging capability will depend on its...

Страница 87: ...he date time set for loggings start has arrived loggings will start FieldLogger goes on logging until the arriving of the date and time set In the case of a power failure logging is interrupted return...

Страница 88: ...mestamps are used as time reference to identify the moment in which the channels were logged Periodic timestamps serve to ensure the integrity of the loggings in time even under power failure or fault...

Страница 89: ...red to activation by alarm in the Configuration software Loggings start when reaching the alarm condition starts loggings if they are not already logging Loggings stops when reaching the alarm conditi...

Страница 90: ...ll the configuration of the equipment as well as the reading of the data of the inputs are done via Modbus protocol In the document FieldLogger Modbus pdf in the product CD is found all the informatio...

Страница 91: ...cation between IHM and FieldLogger is done through RS485 using a baud rate of 115200 bps what puts a limit to the HMI operation distance is the power what means that the voltage drop in the power cabl...

Страница 92: ...ge indication of the download already done If downloading data from FieldLogger internal flash memory it shows the percentage of the whole memory already downloaded If downloading from the SD card it...

Страница 93: ...r the chart Pressing the ENTER key one more time will lead you back to the Chart screen The red color is reserved to inform that one or more channels have values over the configured high limit or unde...

Страница 94: ...stopped Logging Mode Logging mode information Start Indicates how logging is supposed to start Stop Indicates how logging is supposed to stop SD Free Memory Shows the available memory for logging in t...

Страница 95: ...munication baud rate Parity Communication parity HMI HMI configuration Backlight Timeout Time to turn the backlight off 0 always on Chart Chart screen configuration Color Background Background color b...

Страница 96: ...the software Before performing the update proceed with the data download and if desired also the reading of the equipment s configuration and saving it to a file Both the configuration and the logged...

Страница 97: ...emoved 6 If during the copy writing of the firmware of FieldLogger there is some kind of error this will be indicated by the status led that is to stop flashing periodically and repeatedly showing a p...

Страница 98: ...ve from the USB host of the FieldLogger FieldLogger should reset itself automatically and may be used normally now with the new updated firmware We recommend deleting from the USB flash drive the firm...

Страница 99: ...d times may not represent real values FieldLogger whenever detecting such a situation informs it by continuously flashing the Status led three times in a row check the Flags LEDs section Replace batte...

Страница 100: ...our screws located under the enclosure Remove the back cover taking care not to remove the circuit board After removing the back cover remove the battery Avoid touching the circuit board Insert the ne...

Страница 101: ...e N 130 to 1300 C 202 F to 2372 F 0 2 F R 1 C Thermocouple R 20 to 1768 C 68 F to 3214 4 F 0 2 F R 3 C Thermocouple S 20 to 1768 C 68 F to 3214 4 F 0 2 F R 3 C Thermocouple B 100 to 1820 C 212 F to 33...

Страница 102: ...he option of circular logging where after filling up the memory the oldest data will be overwritten by more recent data Allows data to be downloaded during logging IMPORTANT The effective logging rate...

Страница 103: ...NOVUS AUTOMATION www fieldlogger net 103 104 SMTP e mail Supported authentication mode AUTH LOGIN Certifications CE and UL...

Страница 104: ...AINTENANCE This product contains no serviceable parts inside Contact our local distributor in case you need authorized service For troubleshooting visit our FAQ at www novusautomation com LIMITED WARR...

Отзывы: