NOVUS AUTOMATION
www.fieldlogger.net
85/104
•
1.3.6.1.4.1.34590.1.15 = Presence of USB flash drive (0 = no USB flash drive; 1 = USB flash drive present).
[INTEGER]
•
1.3.6.1.4.1.34590.1.16 = Presence of HMI (0 = no HMI; 1 = HMI present). [INTEGER]
•
1.3.6.1.4.1.34590.1.17 = Total number of enabled channels. [INTEGER]
•
1.3.6.1.4.1.34590.1.18.X.Y
o
X = Sequential channel number, starting with analog channels and followed by the digital, remote and
virtual ones:
X = 1: First channel enabled.
X = 2: Second channel enabled.
etc.
o
Y = Channel information:
Y = 1: Channel tag. [OCTET STRING]
Y = 2: Channel read value. Wherever appropriate (virtual and analog channels, for example),
it will be multiplied by the number of decimal places configured by the user. [INTEGER]
Y = 3: Channel unit. [OCTET STRING]
Y = 4: Channel type indication (analog, digital, etc.), and the channel number related to this
type. Examples: ANALOG_001, DIGITAL_005, REMOTE_014, VIRTUAL_103. [OCTET
STRING]
Y = 5: Channel error indication (0 = channel ok; 1 = channel in error state). [INTEGER]
Y = 6: Indicates that the channel is enabled (value = 1) or disabled (value = 0) for logging.
[INTEGER]
Traps
Traps will be generated if enabled and if selected in the alarms in order to warn about their occurrence. The address and
port of destination are configurable.
They have the following fields:
•
Community: “
FieldLogger
”.
•
OID: .1.3.6.1.4.1.34590.1.100 (where
34590
is the "enterprise number" used and the
1
following is the branch of
FieldLogger
)
•
General number: 6 (indicating that the trap is “enterprise-specific").
•
Specific number: Index for the occurred alarm (zero - based).
•
Trap value
o
OID: .1.3.6.1.4.1.34590.1.100.XX, where XX is the index of the occurred alarm.
o
Type: OCTET STRING.
o
Value: String indicating the occurred alarm in the format: TAG + CON VALUE. Example
:
“Channel_1 > 129.43”
CLOUD
From firmware version 1.60, the
FieldLogger
allows
NOVUS Cloud
connection, providing you to access your data in the
cloud (Internet).
The use of cloud publishing service requires Internet connectivity!
NOVUS offer you a data storage service on the cloud named
NOVUS Cloud
. Check the Web site for more
information on this service. This is a paid and optional service.
PREREQUISITES
The following conditions are necessary for the
FieldLogger
can perform data logging in
NOVUS Cloud
:
1. Internet connection with rules that allow access to the
NOVUS Cloud
server (check firewalls and network
policies). You must enable the registration on
NOVUS Cloud
with the correct URL and the DNS service.
2. You are saving the data in the internal flash memory. Currently, you cannot publish the data stored on the SD
card in
NOVUS Cloud
.
3. The time between records must be greater or equal to 1 second, which is the shortest time interval recognized
by
NOVUS Cloud
. It does not matter if the record is in circular memory or full memory; however, we assume
that the record should be slower than the system's ability to send data (Field network). In laboratory
tests, we successfully sent 100 channels, recording and publishing data every 3 seconds. However, we
recommend the use of time in minutes for most applications.
4. You should previously enable the
NOVUS Cloud
service in the portal, and define a virtual "FieldLogger"
configured with the same serial number of the real unit device, before the first connection. Keep in mind that
activation expires in 24 hours. If the
FieldLogger
have made its first connection within this period will continue