- 6 - 

RNPP-302

 

  

                                                                                                                            

NOVATEK-ELECTRO

 

4.4. Indication 

In the absence of the alarm situations on the LED display of RNPP-302 it shown the value of acting voltage 

(RMS voltage) on the selected phase marked by phase indicator (please see 

Figure 1

). 

REL

” LED indicator shows the ON/OFF state of the output relays of RNPP-302. If “

REL

” LED lights that mean 

that the relay is turned ON. During the countdown of the autoreclosing time delay LED indicator REL will blink in 
case of the normal power parameters. Time countdown of the autoreclosing delay starts from the moment of the 
fault detection (not from the moment when the power parameters recovered to their corresponding rated values). 

 

In case the power interruptions in minimal voltage, maximal voltage, phase loss and phase imbalance the 

corresponding LED will light up to mark the phase where the interruption happened.  

If the wrong phase sequence was detected by RNPP-30

2

 all red LEDs will light up in turns. 

On all other alarm situations all red LEDs will light permanently. 
All codes of the alarm situation are shown on the LED display according to the 

Table 1

 

4.5. Signalization 

Signalization relay output turns ON/OFF simultaneously with the main output relay that operates with the 

power load. This allows to use signalization relay for the operation by the contactor also. So the main output 
relay could be used as a signalization relay with normally closed contacts (contacts are closed when there is 
no alarm situation). 

                                                          

Table 1 -  ALARM CODES        

Signalization codes shown on display  

А1 

Digital input Turn OFF remote control 

 

Minimal voltage  

 

Maximal voltage  

 

Phase imbalance  

 

The absence of voltage on the contactor output terminals or in case of not full 
phase switching of the contactor 

 

Wrong phase sequence 

 

Phase loss 

 

                       

          Table 2 - RNPP-302 OPEATION MODES     

 

Adjustable and measures 

parameters 

P

ar

amet

er

 

cod

es

 

Minimal 

va

lue

 

Ma

xim

al 

V

alue

 

F

ac

to

ry 

se

tt

ing

 

Description 

Basic parameters and SETTINGS 

Voltage measurement 
indication 



0 - Manual phase selection. It is displayed the 
voltage on the phase which is marked by Phase 
Indicator. 
1 - Automatic Phase Selection. Voltage measu-
rements on each phase are shown in turns every 
5 sec

 

Digital input signal to turn 
OFF the RNPP-302 relay 
remotely 



0 - not enabled 
1 - on closing of the digital input contact the 
RNPP-302 immediately turns OFF the power load 
2 - on opening of the digital input contact the 
RNPP-302 immediately turns OFF the power load  

Mode

 

of

 

RNPP-302 

operation 



0 - PHASE LOSS RELAY (minimal and maximal 
voltage are not controlled), RNPP-302 turns OFF 
the power load only if voltage disappear on 1 or 
2 phases; 
1 - MINIMAL VOLTAGE RELAY,  RNPP-302 turns 
OFF the power load if the voltage gets lower 

than preset 

 value; 

 

Содержание RNPP-302

Страница 1: ...for 2 hours before switching to the mains Do not use abrasives or organic compounds for cleaning spirit gasoline solvents etc NEVER ATTEMPT TO REMOVE AND REPAIR THE UNIT Some of the unit components m...

Страница 2: ...MS of the phase voltage or alternatively line voltage depending on mode of operation Voltage fault in mains power supply and the type of the interruption State of output relay contacts OPEN CLOSE NOTI...

Страница 3: ...phase to neutral voltage on each phase L1 L2 L3 if the parameter 0 or alternatively phase to phase voltage L1 L2 L2 L3 L3 L1 if parameter 1 Phase Indicator indicator of the currently measured phase L...

Страница 4: ...esting of the RNPP 302 4 2 2 Minimal voltage monitoring mode 1 If the RNPP 302 was initially in turned OFF state then in case the correct voltage is applied to the device it will automatically turn ON...

Страница 5: ...load after the time and turn OFF the signalization RNPP 302 performs the control over following parameters 1 Phase imbalance If the parameter 1 the RNPP 302 performs the control over phase imbalance...

Страница 6: ...ignalization relay for the operation by the contactor also So the main output relay could be used as a signalization relay with normally closed contacts contacts are closed when there is no alarm situ...

Страница 7: ...manual stop start function is required Voltage setting Voltage measurement 0 3 0 0 phase voltage phase to neutral 220V 1 phase voltage phase to neutral 230V 2 phase voltage phase to neutral 240V 3 lin...

Страница 8: ...iance with the operating manual by the user within the warranty period RNPP 302 is not subject to the warranty service in the following cases expiry of the warranty period availability of mechanical d...

Страница 9: ...220 240 LYQ20DC12 6031007G 6131406HQ 6 1393099 3 6 1393099 8 6 1393122 4 6 1393123 2 6 1393767 1 6 1393843 7 6 1415012 1 6 1419102 2 6 1423698 4 6 1608051 6 6 1608067 0 6 1616170 6 6 1616248 2 6 16162...

Отзывы: