- 7 -
NOVATEK-ELECTRO
RNPP
-302
Adjustable and measures
parameters
P
ar
amet
er
cod
es
Minimal
va
lue
Ma
xim
al
V
alue
F
ac
to
ry
se
tt
ing
Description
2 - MAXIMAL VOLTAGE RELAY, RNPP-302turns
OFF the power load if the voltage gets higher
than preset
value;
3 - MINIMAL/MAXIMAL VOLTAGE RELAY,
RNPP-302 turns OFF the power load if the
voltage gets lower than
value or higher
than
value
Method to set Voltage
deviation
0
1
0
0 - voltage values are set up in absolute values
1 - voltage values are set up in % of rated power
parameters
Phase imbalance control
0
1
1
0 - not enabled
1 - enabled
Phase sequence control
0
1
1
0 - not enabled
1 - enabled
Control of the voltage
presence on the output
contacts of the contactor
0
2
0
0 - not enabled
1 - enabled
2 - enabled, and full-phase TURN OFF or TURN
ON of the contactor is allowed (for example for
the cases where manual stop/start function is
required)
Voltage setting
Voltage measurement
0
3
0
0 - phase voltage (phase-to-neutral) 220V
1 - phase voltage (phase-to-neutral) 230V
2 - phase voltage (phase-to-neutral) 240V
3 - line voltage (phase-to-phase) 380V
4 - line voltage (phase-to-phase) 400V
5 - line voltage (phase-to-phase) 415V
Minimal voltage setting,
V:
In % values
85
147
-60
230
398
+10
180
311
-30
If
=0 and
=0,
=1,
=2;
If
=0 and
=3,
=4,
=5;
If
=1 and any values of
parameter.
Maximal voltage setting,
V:
In % values
235
407
-10
295
510
+20
245
424
10
If
=0 and
=0,
=1,
=2;
If
=0 and
=3,
=4,
=5;
If
=1 and any values of
parameter.
Phase imbalance, V:
In % values
10
17
5
80
138
35
15
25
5
If
=0,
=1,
=2;
If
=0 and
=3,
=4,
=5;
If
=1 and any values of
parameter.
Time setting
Autoreclosing time delay,
sec
0,5
600
10
Time delay to TURN OFF
the power load in case of
minimal voltage
interruption detected, sec
0,1
30
10
Time delay to TURN OFF
the power load in case of
maximal voltage
interruption detected, sec
0,1
30
1
Time delay to TURN OFF
the power load in case
the phase imbalance is
detected, s
0,1
30
3,0