NOVATEK-ELECTRO

                                                                                                    

 RNPP

-302

 

  

                                                                                                                      

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Figure 1

. Front panel, controls and size dimensions of the 

RNPP-302 

 

Red LED  “

L1

” – lights up in case of the alarm on phase L1 

Red LED  “

L2

” –  lights up in case of the alarm on phase L2 

Red LED  “

L3

” – lights up in case of the alarm on phase L3 

Green LED  “

REL

” – lights up when the output relay is closed 

SET

” button – to set the parameter value 

WR

” – to write and save the parameter 

“  and  ” Buttons  - to scroll and adjust the parameters value in menues 
 

Notes:

    button hereinafter in text 

– “

UP

”,    button – “

DOWN

” 

 
 

2. START UP PROCEDURE 

 

Connect the contactor  (magnetic starter) to the 

RNPP-302

 and make all other necessary connections as 

shown on 

Figure 2

 

 

 Connect mains power supply to the input terminals of RNPP-302 

 

Turn ON the power and adjust all required settings according to 

Table 2

 

 

 

NOTE

. All wiring connections must be performed on the dead device. 

 

3. RNPP-302 SETTINGS AND CONTROLS 

3.1. 

At the initial state on the front panel the following information is shown:

 

- depending the operation mode phase-to-neutral voltage on each phase (L1, L2, L3) if the parameter

 



= 0  or alternatively phase-to-phase voltage (L1-L2; L2-L3; L3-L1) if parameter 



=1; 

-  Phase Indicator (indicator of the currently measured phase (L1, L2 or L3)); 
- Operational state of the output relay (Open/Closed) 
To  select  the  phase  manually

 

(



=0)  use 

DOWN

  and 

UP

  buttons,  alternatively  if  parameter 



=1  the 

measurement values on phases are displayed in turns automatically every 5 seconds

 

 

3.2.

 To view and change the parameters it is necessary press 

SET

 button and all phase indicators will light 

up. To scroll between the parameters use 

DOWN

 and 

UP

 buttons. To enter the parameter and chance value 

press 

SET

 button. Then using 

DOWN

 and 

UP

 buttons set the desired values. To save the parameter and exit 

the current menu press 

WR

 button. To exit the menu without saving press 

SET

 button. If none of the buttons 

are pressed within 15 seconds the RNPP-302 returns to initial state. 

 

3.3. 

To restore default factory settings quickly it is necessary to press simultaneously 

SET

DOWN

 and 

UP

 

buttons and energize the RNPP-302 while keeping these buttons pressed. Then the display should indicate 



”. Then Turn OFF the device. Factory settings are restored. 

 

Содержание RNPP-302

Страница 1: ...for 2 hours before switching to the mains Do not use abrasives or organic compounds for cleaning spirit gasoline solvents etc NEVER ATTEMPT TO REMOVE AND REPAIR THE UNIT Some of the unit components m...

Страница 2: ...MS of the phase voltage or alternatively line voltage depending on mode of operation Voltage fault in mains power supply and the type of the interruption State of output relay contacts OPEN CLOSE NOTI...

Страница 3: ...phase to neutral voltage on each phase L1 L2 L3 if the parameter 0 or alternatively phase to phase voltage L1 L2 L2 L3 L3 L1 if parameter 1 Phase Indicator indicator of the currently measured phase L...

Страница 4: ...esting of the RNPP 302 4 2 2 Minimal voltage monitoring mode 1 If the RNPP 302 was initially in turned OFF state then in case the correct voltage is applied to the device it will automatically turn ON...

Страница 5: ...load after the time and turn OFF the signalization RNPP 302 performs the control over following parameters 1 Phase imbalance If the parameter 1 the RNPP 302 performs the control over phase imbalance...

Страница 6: ...ignalization relay for the operation by the contactor also So the main output relay could be used as a signalization relay with normally closed contacts contacts are closed when there is no alarm situ...

Страница 7: ...manual stop start function is required Voltage setting Voltage measurement 0 3 0 0 phase voltage phase to neutral 220V 1 phase voltage phase to neutral 230V 2 phase voltage phase to neutral 240V 3 lin...

Страница 8: ...iance with the operating manual by the user within the warranty period RNPP 302 is not subject to the warranty service in the following cases expiry of the warranty period availability of mechanical d...

Страница 9: ...220 240 LYQ20DC12 6031007G 6131406HQ 6 1393099 3 6 1393099 8 6 1393122 4 6 1393123 2 6 1393767 1 6 1393843 7 6 1415012 1 6 1419102 2 6 1423698 4 6 1608051 6 6 1608067 0 6 1616170 6 6 1616248 2 6 16162...

Отзывы: