background image

- 5 - 

NOVATEK-ELECTRO

                                                                                                    

 RNPP

-302

 

  

                                                                                                                      

 

curtain  time  defined  by  user  (parameter 

–  then  the  RNPP-302  will  turn  OFF  the  power  load: 

terminals 23, 24 will open while 22, 24 and 20, 21 will close. 

After the recovery of the voltage parameters 

– when controlled voltage becomes 5-6 V lower than maximal 

tripping threshold (voltage hysteresis is 5-6 V) the relay will automatically turn ON the power load with delay 
time defined by

 



 

parameter. 

 

4.2.4. Over/Under voltage monitoring (min/max) mode 

(



 

=3) 

If the RNPP-302 was initially in turned OFF state then in case the correct voltage is applied to the device it 

will  automatically  turn  ON  within  the  delay  time  defined  by

 



 

parameter:  the  “

REL

”  LED  will  light  up  and 

terminals 23, 24 will open while 22, 24 and 20, 21 will close. 

If the input voltage get lower than the minimal tripping threshold (parameter 

) within the curtain time 

defined  by  user  (parameter 

– then the RNPP-302 will turn OFF the power load: terminals 23, 24 will 

close while 22, 24 and 20, 21 will open. 

If the voltage decrease is more than 80 V regardless of the preset voltage tripping threshold the RNPP-302 

will cut OFF the power load within 0,1 second (accelerated turn OFF). 

After the recovery of the voltage parameters 

– when controlled voltage becomes 5-6 V higher than minimal 

tripping threshold (voltage hysteresis is 5-6 V) the relay will automatically turn ON the power load with delay 
time defined by 



 

parameter. 

If  the  increase  in  input  voltage  is  more  than the maximal  tripping  threshold  (parameter 

)  within  the 

curtain time defined by user (parameter 

– then the RNPP-302 will turn OFF the power load: terminals 

23,  24  will  close  while  22,  24  and  20,  21  will  open.  After  the  recovery  of  the  voltage  parameters 

–  when 

controlled voltage becomes 5-6 V lower than maximal tripping threshold (voltage hysteresis is 5-6 V) the relay 
will automatically turn ON the power load with delay time defined by 



 

parameter. 

 

4.3. Control of the additional voltage parameters  

In all above stated modes of operation the RNPP-302 performs permanent control over additional voltage 

parameters  and  in  case  of  deviation  from  the  preset  values  it  turns  OFF  the  power  load  and  turns  ON  the 
alarm signalization. On the recovery of voltage level and cancel of the alarm situation RNPP-302 will turn ON 
the power load after the 



 

time and turn OFF the signalization. 

RNPP-302 performs the control over following parameters: 

1) Phase imbalance. If the parameter 

=1 the RNPP-302 performs the control over phase imbalance 

and the tripping threshold for the phase imbalance is defined by parameter 

 

2)  Wrong  phase  sequence  and  phase  combination.  If  the  parameter 

=1  RNPP-302  monitors  the 

correct phase sequence and the absence of the phase combination. 

 

3) Feedback control of the voltage presence on the contactor (magnetic starter) terminals. If the contactor 

has burned or stuck contacts 

– RNPP-302 will cut the output relay and turn ON the alarm signalization. This 

function  is  of  a  great  importance  as  the  equipment  could  be  damaged  due  to  bad  or  damaged  contactor 
whereas all input voltage parameters are fine and correct.  

If the parameter 

=1 the RNPP-302 detects the presence of the voltage on the output terminals of the 

contactor and in case the stuck contacts it turns OFF the power load and turns ON the alarm signalization. 

If the parameter 

=2 the RNPP-302

 

checks the voltage presence on the output contactor contacts and 

allows all contacts to be opened (full-phase disconnection is permitted). The alarm situation is detected only in 
case one or two contacts of the contactor are opened. So it may be the situation when only one or two phases 
will come to the equipment because of a damaged or not properly working contactor and this may result to the 
damage of the equipment or installation. This function is essential when the equipment or power load need to 
be switched ON/OFF using the remote control switch or additional technological contact. 

 

To restart the operation of the RNPP-302 again after the detection of wrong phase sequence or the 

absence of voltage on the contactor output terminals it will be necessary to eliminate the reason of the

 

power interruption, then reconnect the RNPP-302 and then turn ON the power supply. 

 

4) Control of the external signals coming to the digital input. It is defined by parameters

 



=1 (



=2).

 

RNPP-302 has the digital input that may be used to detect the external alarm situation (for example the signal 
from thermostat built into the AC motor coil). On getting the signal the RNPP-302 immediately disconnect the 
power load and displa

ys the “

A1

” alarm code. When the alarm situation is eliminated (there is no signal from 

the  external  source)  the  RNPP-302  will  automatically  turn  on  the  power  load  with  the  delay  time  defined  by

 



 

parameter. 

Содержание RNPP-302

Страница 1: ...for 2 hours before switching to the mains Do not use abrasives or organic compounds for cleaning spirit gasoline solvents etc NEVER ATTEMPT TO REMOVE AND REPAIR THE UNIT Some of the unit components m...

Страница 2: ...MS of the phase voltage or alternatively line voltage depending on mode of operation Voltage fault in mains power supply and the type of the interruption State of output relay contacts OPEN CLOSE NOTI...

Страница 3: ...phase to neutral voltage on each phase L1 L2 L3 if the parameter 0 or alternatively phase to phase voltage L1 L2 L2 L3 L3 L1 if parameter 1 Phase Indicator indicator of the currently measured phase L...

Страница 4: ...esting of the RNPP 302 4 2 2 Minimal voltage monitoring mode 1 If the RNPP 302 was initially in turned OFF state then in case the correct voltage is applied to the device it will automatically turn ON...

Страница 5: ...load after the time and turn OFF the signalization RNPP 302 performs the control over following parameters 1 Phase imbalance If the parameter 1 the RNPP 302 performs the control over phase imbalance...

Страница 6: ...ignalization relay for the operation by the contactor also So the main output relay could be used as a signalization relay with normally closed contacts contacts are closed when there is no alarm situ...

Страница 7: ...manual stop start function is required Voltage setting Voltage measurement 0 3 0 0 phase voltage phase to neutral 220V 1 phase voltage phase to neutral 230V 2 phase voltage phase to neutral 240V 3 lin...

Страница 8: ...iance with the operating manual by the user within the warranty period RNPP 302 is not subject to the warranty service in the following cases expiry of the warranty period availability of mechanical d...

Страница 9: ...220 240 LYQ20DC12 6031007G 6131406HQ 6 1393099 3 6 1393099 8 6 1393122 4 6 1393123 2 6 1393767 1 6 1393843 7 6 1415012 1 6 1419102 2 6 1423698 4 6 1608051 6 6 1608067 0 6 1616170 6 6 1616248 2 6 16162...

Отзывы: