- 7 - 

NOVATEK-ELECTRO 

                                                                                                                          

REV-114

 

 

Table 3 

(Continued)

 

 

Mode number and 

name 

Description 

10 

 

On/off delay with 

external start 

After energizing, the indicator 

ON

 (Fig.1it.10) is on 

and the product goes into standby mode, in this 
case the load relay contacts 

and

 NO 

are open, 

and the indicator 

 (Fig.1 it.9) is off. When 

control signal 

S

 occurs, there is the set time delay 

. During the delay time the indicator 

 

periodically flashes. 
At the end of the delay time the load relay 
contacts are closed, the indicator 

 is on and 

the pro-duct goes into standby mode. When there 
is no the control signal 

S

, there is the set time 

delay 

. During the delay time the indicator 

 periodically is off. 

At the end of the delay time the load relay contacts are open, the indicator 

 is off and the 

product goes into standby mode. 

In case of repeated occurrence of the control signal 

S

, the algorithm fulfillment is repeated.  

11 

 

Pitch of the load 

relay 

After energizing, the indicator 

ON

 (Fig.1 it.10) is on 

and the product goes into standby mode, in this 
case the load relay contacts 

and

 NO 

are open, 

and the indicator 

 (Fig.1 it.9) is off. 

When control signal 

occurs, the load relay 

contacts and the indicator 

 change its state to 

the opposite, then the product

 

goes into standby 

mode. 
When there is no the control signal 

S

, the product 

continues to be in standby mode. 
In case of repeated occurrence of the control signal 

S

, the algorithm fulfillment is repeated. 

12 

 

Periodic with external 

start and on-delay 

After energizing, the indicator 

ON

 (Fig.1 it.10) is 

on and the product goes into standby mode, in 
this case the load relay contacts 

and

 NO

 are 

open, and the indicator 

 (Fig.1 it.9) is off. 

When control signal

 S

 occurs, there is the set time 

delay 

. During the delay time the indicator 

 (Fig.1 it.9) periodically flashes. 

At the end of the delay time the load relay 
contacts 

and 

NO

 are closed for set time 

 

and the indicator 

 is on. During the delay 

time the indicator 

 periodically is off. 

At the end of the delay time the load relay contacts are open, and the product starts the 
algorithm fulfillment from the beginning. 
When there is no the control signal 

S

, the algorithm fulfillment is stopped, the load relay 

contacts 

and

 NO

 are open and the product goes into the standby mode. 

13 

 

Periodic with external 

start and time delay 

when energizing 

After energizing, the indicator 

ON

 (Fig.1 it. 10) is 

on and the product goes into the standby mode, 
in this case the load relay contacts 

and

 NO

 are 

open, and the indicator 

 (Fig.1 it.9) is off. 

When control signal 

S

, the load relay contacts 

and

 NO

 are closed for set time

. During the 

delay time the indicator 

 (Fig.1 it.9) 

periodically is off. At the end of the delay time the 
load relay contacts 

and

 NO

 are open for set 

time 

 

and the indi-cator 

 

is off. During 

the delay time the indica-tor 

 periodically flashes. 

At the end of the delay time the product starts the algorithm fulfillment from the beginning. 
When there is no the control signal 

S

, the algorithm fulfillment is stopped, the load relay 

contacts 

and

 NO

 are open and the product goes into the standby mode. 

 
 
 

Содержание REV-114

Страница 1: ...m of development and production production complies with the requirements of ISO 9001 2015 Dear Customer Company thanks you for purchasing our products You will be able to use properly the product aft...

Страница 2: ...OF THE CASE IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE PRODUCT During operation and maintenance the regulatory document requirements must be met namely Regulations...

Страница 3: ...e delay relay REV 114 is the microprocessor based device intended to control the load with independent time delay It provides the certain sequence of the load operation according to the mode specified...

Страница 4: ...17 Adjustment range of time from 0 1 s to 10 days Timing adjustment Buttons on the front panel Digit display of remaining time available Service of the product Switchgear and control gear Rated opera...

Страница 5: ...ed for set time and the indicator is on During the delay time the indicator periodically is off At the end of the delay time the load relay contacts are open and the product starts fulfillment of algo...

Страница 6: ...he indicator is off and the product goes into standby mode In case of repeated occurrence of the control signal S the algorithm fulfillment is repeated 8 Pulse I with external start After energizing t...

Страница 7: ...ith external start and on delay After energizing the indicator ON Fig 1 it 10 is on and the product goes into standby mode in this case the load relay contacts C and NO are open and the indicator Fig...

Страница 8: ...ts C and NO remain open and the indicator is off The product goes into the standby mode until power off 3 INTENDED USE 3 1 Preparation for operation Unpack the product we recommend to keep the origina...

Страница 9: ...nd wire can burn If you increase the tightening torque it is possible to have thread failure of the terminal block screws or the compression of the connected wire Error when performing the installatio...

Страница 10: ...is case the display will flash the current value of the selected time unit Using the buttons or set the required value Press the buttons one time to save the set value and return to the previous menu...

Страница 11: ...t should be packed in the original or other packing excluding mechanical damage You are kindly requested in case of return of the product and transfer it to the warranty post warranty service in the f...

Страница 12: ...12 REV 114 NOVATEK ELECTRO...

Отзывы: