- 8 - 

REV-114

                                                                                                                            

NOVATEK-ELECTRO

 

 

Table 3 

(Continued)

 

Mode number and 

name 

Description 

14 

 

Pulse generator with 

external start 

After energizing, the indicator ON (Fig.1 it.10) is 
on and the product goes into the standby mode, 
in this case the load relay contacts C and NO 
are open, and the indicator 

 (Fig.1 it.9) is 

off. When control signal S occurs, there is the set 
time delay 

. During the delay time the 

indicator 

 (Fig.1 it.9) periodically flashes. At 

the end of the delay time the load relay contacts 

C and NO are closed for the set time 

 and 

the indicator 

 is on. During the delay time 

the indicator 

 periodically is off. At the end of the delay time the load relay contacts are 

open, and the product goes into the standby mode. 

15 

 

Start-stop

 

After energizing, the indicator 

ON

 (Fig.1 it.10) is 

on and the product goes into the standby mode, 
in this case the load relay contacts 

and

 NO

 are 

open,and the indicator 

 (Fig.1 it.9) is off. 

When control signal S occurs, there is the set time 
delay 

. During the delay time the indicator 

 (Fig.1 it.9) periodically flashes. At the end of 

the delay time the load relay contacts 

and

 NO

 

are closed, the indi-cator 

 is on. In case of 

repeated occurrence of the control signal S, there 
is the set time delay 

 During the delay time the indicator 

 (Fig.1 it.9) periodically is off. 

At the end of the delay time the load relay contacts C and NO are open, the indicator 

 is 

off and the product goes into the standby mode.

 

16 

Always ON 

After energizing, the indicator 

ON

 (Fig.1 it.10) is on, the load relay contacts 

and

 NO

 are 

closed, the indicator 

 is on and the product goes into the standby mode until power-off. 

17 

Always OFF 

After energizing, the indicator 

ON

 (Fig.1 it.10) is on, the load relay contacts 

and

 NO

 remain 

open, and the indicator 

 is off. The product goes into the standby mode until power-off. 

 

3. INTENDED USE 
3.1. Preparation for operation 

 Unpack  the  product  (we  recommend  to  keep  the  original  packing  for  the  entire  warranty  period  of  the  product 

operation); 

 Check the product for damage after transportation; in case of such damages detection, contact the supplier or 

manufacturer; 

 Carefully  study  the  Operation  Manual  (

pay  special  attention  to  the  connection  diagram  to  power  the 

product

); 

 If the temperature of the product after transportation or storage differs from the temperature of the environment 

at  which  it  is  supposed  to  be  operated,  then  before  connecting  to  the  mains  hold  the  product  under  operating 
conditions within two hours (because there is possible moisture condensation on the elements of the product); 

 If  you  have  any  questions  regarding  the  installation  of  the  product,  please  contact  the  manufacturer  by 

telephone number indicated at the end of this Operation Manual

 

3.2. Product connection 

Connect the product in accordance with the diagram given in Fig.2.

 

 

ATTENTION! 
THE  PRODUCT  IS  NOT  DESIGNED  FOR  LOAD

 

COMMUTATION  IN  CASE  OF  SHORT  CIRCUITS. 

THEREFORE, THE LOAD POWER SUPPLY CIRCUIT SHOULD BE EQUIPPED WITH THE CIRCUIT BREAKER 
FOR CURRENT OF 6 A MAXIMUM.

 

ALL CONNECTIONS MUST BE PERFORMED WHEN THE PRODUCT IS DE-ENERGIZED. 

 

To  improve  performance  of  the  product  it  is  recommended  to  install  the  fuse  or  the  analogue  in  the 

power supply circuit of REV-114 for 1 A current. 

To  ensure  the  reliability  of  electrical  connections  you  should  use  flexible  (stranded)  wires  with  insulation  for 

voltage  of  no  less  than  450 V,  the  ends  of  which  it  is  necessary  to  be  striped  of  insulation  for  5±0.5 mm  and 
tightened  with  bootlaces.  Recommended  cable  cross  section  is  no  less  than  1.0 mm

2

.  Wires  fastening  should 

exclude mechanical damage, twisting and abrasion of the wire insulation.  

Содержание REV-114

Страница 1: ...m of development and production production complies with the requirements of ISO 9001 2015 Dear Customer Company thanks you for purchasing our products You will be able to use properly the product aft...

Страница 2: ...OF THE CASE IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE PRODUCT During operation and maintenance the regulatory document requirements must be met namely Regulations...

Страница 3: ...e delay relay REV 114 is the microprocessor based device intended to control the load with independent time delay It provides the certain sequence of the load operation according to the mode specified...

Страница 4: ...17 Adjustment range of time from 0 1 s to 10 days Timing adjustment Buttons on the front panel Digit display of remaining time available Service of the product Switchgear and control gear Rated opera...

Страница 5: ...ed for set time and the indicator is on During the delay time the indicator periodically is off At the end of the delay time the load relay contacts are open and the product starts fulfillment of algo...

Страница 6: ...he indicator is off and the product goes into standby mode In case of repeated occurrence of the control signal S the algorithm fulfillment is repeated 8 Pulse I with external start After energizing t...

Страница 7: ...ith external start and on delay After energizing the indicator ON Fig 1 it 10 is on and the product goes into standby mode in this case the load relay contacts C and NO are open and the indicator Fig...

Страница 8: ...ts C and NO remain open and the indicator is off The product goes into the standby mode until power off 3 INTENDED USE 3 1 Preparation for operation Unpack the product we recommend to keep the origina...

Страница 9: ...nd wire can burn If you increase the tightening torque it is possible to have thread failure of the terminal block screws or the compression of the connected wire Error when performing the installatio...

Страница 10: ...is case the display will flash the current value of the selected time unit Using the buttons or set the required value Press the buttons one time to save the set value and return to the previous menu...

Страница 11: ...t should be packed in the original or other packing excluding mechanical damage You are kindly requested in case of return of the product and transfer it to the warranty post warranty service in the f...