Mode number and
name
Description
14
Pulse generator with
external start
After energizing, the indicator ON (Fig.1 it.10) is
on and the product goes into the standby mode,
in this case the load relay contacts C and NO
are open, and the indicator
(Fig.1 it.9) is
off. When control signal S occurs, there is the set
time delay
. During the delay time the
indicator
(Fig.1 it.9) periodically flashes. At
the end of the delay time the load relay contacts
C and NO are closed for the set time
and
the indicator
is on. During the delay time
the indicator
periodically is off. At the end of the delay time the load relay contacts are
open, and the product goes into the standby mode.
15
Start-stop
After energizing, the indicator
ON
(Fig.1 it.10) is
on and the product goes into the standby mode,
in this case the load relay contacts
C
and
NO
are
open,and the indicator
(Fig.1 it.9) is off.
When control signal S occurs, there is the set time
delay
. During the delay time the indicator
(Fig.1 it.9) periodically flashes. At the end of
the delay time the load relay contacts
C
and
NO
are closed, the indi-cator
is on. In case of
repeated occurrence of the control signal S, there
is the set time delay
.
During the delay time the indicator
(Fig.1 it.9) periodically is off.
At the end of the delay time the load relay contacts C and NO are open, the indicator
is
off and the product goes into the standby mode.
16
Always ON
After energizing, the indicator
ON
(Fig.1 it.10) is on, the load relay contacts
C
and
NO
are
closed, the indicator
is on and the product goes into the standby mode until power-off.
17
Always OFF
After energizing, the indicator
ON
(Fig.1 it.10) is on, the load relay contacts
C
and
NO
remain
open, and the indicator
is off. The product goes into the standby mode until power-off.
3. INTENDED USE
3.1. Preparation for operation
•
Unpack the product (we recommend to keep the original packing for the entire warranty period of the product
operation);
•
Check the product for damage after transportation; in case of such damages detection, contact the supplier or
manufacturer;
•
Carefully study the Operation Manual (
pay special attention to the connection diagram to power the
product
);
•
If the temperature of the product after transportation or storage differs from the temperature of the environment
at which it is supposed to be operated, then before connecting to the mains hold the product under operating
conditions within two hours (because there is possible moisture condensation on the elements of the product);
•
If you have any questions regarding the installation of the product, please contact the manufacturer by
telephone number indicated at the end of this Operation Manual
.
3.2. Product connection
Connect the product in accordance with the diagram given in Fig.2.
ATTENTION!
THE PRODUCT IS NOT DESIGNED FOR LOAD
COMMUTATION IN CASE OF SHORT CIRCUITS.
THEREFORE, THE LOAD POWER SUPPLY CIRCUIT SHOULD BE EQUIPPED WITH THE CIRCUIT BREAKER
FOR CURRENT OF 6 A MAXIMUM.
ALL CONNECTIONS MUST BE PERFORMED WHEN THE PRODUCT IS DE-ENERGIZED.
To improve performance of the product it is recommended to install the fuse or the analogue in the
power supply circuit of REV-114 for 1 A current.
To ensure the reliability of electrical connections you should use flexible (stranded) wires with insulation for
voltage of no less than 450 V, the ends of which it is necessary to be striped of insulation for 5±0.5 mm and
tightened with bootlaces. Recommended cable cross section is no less than 1.0 mm
2
. Wires fastening should
exclude mechanical damage, twisting and abrasion of the wire insulation.