REV-114

                                                                                                                            

NOVATEK-ELECTRO

 

Fig.1 

– 

Controls, overall and mounting dimensions of REV

–114 

1.3. Operation conditions 

The product is designed for operation in the following conditions: 

 Ambient temperature: from minus 30 to +55°C; 

 Atmospheric pressure: from 84 to 106.7 kPa; 

 Relative air humidity 

(at temperature of +25°C): 30 … 80 %. 

ATTENTION! The product is not intended for operation in the following conditions: 

 Significant vibration and shocks; 

 High humidity; 

 Aggressive  environment  with  content  in  the  air  of  acids,  alkalis,  etc.,  as  well  as  severe  contaminations 

(grease, oil, dust, etc.). 
 

2. SPECIFICATIONS 
2.1. Basic Specifications 

Basic specifications of REV

–114 are given in Table 1. 

Specifications of the load relay contacts are given in Table 2. 

 

Table 1 

– 

Basic Specifications 

 

Description 

Value 

Operating supply voltage, V: 

230 / 240 

Frequency of supply mains, Hz 

45 

– 62 

Voltage at which service capability is maintained, V 

185 

– 280 

Permissible harmonic configuration 

(unsinusoidality)

 of power supply voltage 

 EN 50160 

Readiness time when energizing, s, no more than 

0.4 

Accuracy of time setting holding, %, no less than 

0.5 

Number of operation algorithms 

17 

Adjustment range of time 

from 0.1 s to 10 days 

Timing adjustment 

Buttons on the front panel 

Digit display of remaining time 

available 

Service of the product 

Switchgear and control gear 

Rated operating condition 

Continuous  

Type and quantity of contacts (switching) 

Climatic design version 

NC 3.1 

Protection rating of case 

ІР40 

Protection rating of terminal box 

ІР20 

Commutation lifetime of output contacts if cos

=1: 

                                        - under load of 6 

А, time, no less than 

                                        - under load of 1 

А, time, no less than 

 

100 000 

1 000 000 

Power consumption (under load), W, no more than 

0.5 

Permissible contamination level 

II 

Overvoltage category 

II 

Electric shock protection class 

II 

Rated insulation voltage, V 

450 

Rated impulse withstand voltage, kV 

2.5 

Wire cross-section for connection to terminals, mm² 

0.5 

– 2 

Tightening torque of terminal screws, N*m 

0.4 

Weight, kg, not more 

0.150 

Overall dimensions, H x D x L, mm 

90 x 18 x 65 

Product installation (mounting) is on standard 35mm DIN rail 
The product remains functional at any position in space 
Case material is self-extinguishing plastic 

 
 

Table 2 

– 

Specifications of output contacts of the load relay  

 

сos 

 

Max. current at 

U~250 V

, А 

Max. switching 

power, VA 

Max. permissible 

continuous AC voltage, V 

Max. current at 

U

DC

=28 V, A 

1500 

250 

 

2.2. Product operation modes 

The product operation modes are given in Table 3. 

 
 

Содержание REV-114

Страница 1: ...m of development and production production complies with the requirements of ISO 9001 2015 Dear Customer Company thanks you for purchasing our products You will be able to use properly the product aft...

Страница 2: ...OF THE CASE IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE PRODUCT During operation and maintenance the regulatory document requirements must be met namely Regulations...

Страница 3: ...e delay relay REV 114 is the microprocessor based device intended to control the load with independent time delay It provides the certain sequence of the load operation according to the mode specified...

Страница 4: ...17 Adjustment range of time from 0 1 s to 10 days Timing adjustment Buttons on the front panel Digit display of remaining time available Service of the product Switchgear and control gear Rated opera...

Страница 5: ...ed for set time and the indicator is on During the delay time the indicator periodically is off At the end of the delay time the load relay contacts are open and the product starts fulfillment of algo...

Страница 6: ...he indicator is off and the product goes into standby mode In case of repeated occurrence of the control signal S the algorithm fulfillment is repeated 8 Pulse I with external start After energizing t...

Страница 7: ...ith external start and on delay After energizing the indicator ON Fig 1 it 10 is on and the product goes into standby mode in this case the load relay contacts C and NO are open and the indicator Fig...

Страница 8: ...ts C and NO remain open and the indicator is off The product goes into the standby mode until power off 3 INTENDED USE 3 1 Preparation for operation Unpack the product we recommend to keep the origina...

Страница 9: ...nd wire can burn If you increase the tightening torque it is possible to have thread failure of the terminal block screws or the compression of the connected wire Error when performing the installatio...

Страница 10: ...is case the display will flash the current value of the selected time unit Using the buttons or set the required value Press the buttons one time to save the set value and return to the previous menu...

Страница 11: ...t should be packed in the original or other packing excluding mechanical damage You are kindly requested in case of return of the product and transfer it to the warranty post warranty service in the f...

Страница 12: ...12 REV 114 NOVATEK ELECTRO...

Отзывы: