APPENDIX - A -
Control Panel Operation in DAY Mode (Day/Night LED= ON)
Control Panel Operation in NIGHT Mode (Day/Night Led = OFF)
CFP-600-Prog-5.VP
Installation and Operating Manual
Page 19
Doc. M-131.1-CFP600-ENG
Rev. B.1
NOTIFIER ITALIA
ZONE ALARM
PREALARM LED= FLASHING
DISPLAY= 01 : ZXX PREAL
PREALARM RELAY= ON
BUZZER= STEADY SOUND
PREALARM LED= OFF
PREALARM RELAY= OFF
ALARM LED= FLASHING
ALARM RELAY= ON
SOUNDER RELAY= ON
SIGNAL SILENCE LED= OFF
BUZZER= STEADY SOUND
DISPLAY= 01: ZXX AL
SIGNAL SILENCE
EXPIRED PREALARM TIME
SIGNAL SILENCE
ALARM LED= ON
SIGNAL SILENCE LED= ON
ALARM RELAY= OFF
SOUNDER RELAY= OFF
BUZZER= SILENT
DISPLAY= 01: ZXX AL
RECOGNITION TIME EXPIRED
RESET
YES
ZONE ALARM
ALARM LED= FLASHING
ALARM RELAY= ON
SOUNDER RELAY= ON
BUZZER= STEADY SOUND
DISPLAY= 01: ZXX AL
CONTROL TIMINGS EXPIRED
SIGNAL SILENCE
PREALARM LED= ON
PREALARM RELAY= OFF
SIGNAL SILENCE LED= ON
BUZZER= INTERMITTENT SOUND
DISPLAY= 01 : ZXX PREAL
YES
ALARM LED= ON
ALARM RELAY= OFF
SOUNDER RELAY= OFF
BUZZER= SILENT
DISPLAY= 01: ZXX AL
SIGNAL SILENCE LED
= ON
YES
NO
Manual Evacuation?
YES
NO
NOTE:ZONE ALARM
Single threshold Zone:
First Alarm= Zone in Alarm status
Double threshold Zone:
First Alarm= Zone in Prealarm status
Second Alarm= Zone in Alarm status
NO
ALL SIGNALS
=
OFF
YES
NOTE:ZONE ALARM
Single threshold Zone:
First Alarm= Zone in Alarm status
Double threshold Zone:
First Alarm= Zone in Prealarm status
Second Alarm= Zone in Alarm status