CHANGE ZONES - INCLUDE/EXCLUDE STATUS
An EXCLUDED Zone does not signal neither Alarms nor Troubles.
Use CURSOR KEYS to enter the zone number on which operate.
By pressing ENTER key, on the display appears the status of the zone
selected.
Press ENTER to modify the zone status.
If you do not want to change the zone status, press ESC.
»
NOTE: A)
PROGRAMMING THE CBE EQUATIONS
This function allows to map a set of events to each LOGIC ZONE (from the 13th one to the 20th), to activate it.
The admitted events are:
•
Alarm or Prealarm for initiating circuits (from 1 to 12);
•
Activated, for logic zones (from 13 to 20)
Maximum 4 events mapped to a logic zone can be programmed.
Each event is connected to the other by two types of conditions:
•
OR= it means either...or
•
AND= it means both...and
Example:
Follow this procedure to performe the programming:
›
Phase A)
•
Enter the zone number for which you wish to program the equation (13 to 20)
•
Now, enter 2 data: a zone its status (Alarm or Prealarm).
•
It is possible entering an operator of AND or OR with other zones and to continue the equation.
Page 10
Installation and Operating Manual
CFP-600-Prog-3.VP
NOTIFIER ITALIA
Rev. B.1
Doc. M-131.1-CFP600-ENG
INC./EXC.ZONES |A08
Z. __
|G08
|D00
|E00
INC./EXC. ZONES|A08
Z. 01 NORMAL
|G08
|D00
Modify
Exit |E00
Zone Status
Detector Alarms
Detector Troubles
Enabled
YES
YES
Disabled
NO
YES
Excluded
NO
NO
B) if a zone is EXCLUDED, any operation on it, is
inhibited (See config. Menu - Lev. 4 about
Exclusion function)
DESCRIPTION
CHARACTERS TO BE PROGRAMMED
Result
Zone nr. 20 active if...
Z. 20
Event nr. 1
Zone nr. 1 in Alarm status
01 A
Condition
or
+
Event nr. 2
Zone nr. 2 in Pre-Alarm status
02 P
EQUATION
CONFIGURATION
EQUATION for Z. _
EQUATION for Z.2_
EQUATION for Z. 20