CHANGE ZONE PARAMETERS
This section allows to program the following functions, for each zone.
•
2 THRESHOLDS for each ZONE (this programming allows to detect an alarm coming from 2 different detectors of
the same zone, and use only 1 zone for exstinguishing purposes)
•
ZONE ALWAYS IN NIGHT MODE (for fire alarm push buttons)
•
RESET RELAY (this programming enables the resettable voltage output to be activated or not when the zone is in
Walk Test Mode or the zone verification time is enabled).
Press ENTER to start the programming
Use CURSOR keys and ENTER key to select the zone
Press ENTER to have access to the Modify menu
Press ENTER to modify
CHANGE VERIFICATION TIMES
This section allows to program the alarm verification time for the single zones.
Press ENTER
Use CURSOR Keys to select the zone number on which you wish
to modify the verification time, then press ENTER to confirm the
zone number.
Press twice ENTER key.
Use CURSOR Keys and ENTER to set the verification time.
It is possible to program a 999-second maximum time.
Page 12
Installation and Operating Manual
CFP-600-Prog-3.VP
NOTIFIER ITALIA
Rev. B.1
Doc. M-131.1-CFP600-ENG