CHANGE ZONE DESCRIPTION
This function allows to program a label (16 characters max), for each zone.
Press ENTER to have access to the function.
Use CURSOR keys to enter the zone number, then press ENTER
to confirm.
Use CURSOR keys to enter the letters, then press
ENTER after pressing each character.
CHANGE SYSTEM TIME DELAY
This section shows the programmings of several time delays, supplied by the control panel.
Select the function from the menu by using CURSOR keys, and press ENTER.
The programming is carried out as the previous one, except that it is possible to enetr different figures according to the
time you are programming.
To enter the figures use CURSOR keys and press ENTER key to confirm.
Maximum Time in Day Mode
By pressing ENTER key the following display appears
Enter the hours by using the CURSOR keys
To accomplish the programming press ENTER key
»
NOTE: The programming time cannot exceed 18 hours.
Page 14
Installation and Operating Manual
CFP-600-Prog-3.VP
NOTIFIER ITALIA
Rev. B.1
Doc. M-131.1-CFP600-ENG
ZONE DESCRIPT. | A00
CONFIGURATION | G00
| D00
| E00
ZONE DESCRIPT. | A00
Z. __
| G00
| D00
| E00
ZONE DESCRIPT. | A00
Z. 02
| G00
| D00
FIRST LOOR
| E00
DEFAULT
MIN
MAX
5 seconds
5 seconds
60 seconds
10 seconds
10 seconds
60 seconds
2 minutes
0 minutes
60 minutes
30 seconds
001 second
120 seconds
30 seconds
001 second
120 seconds
30 seconds
001 second
120 seconds
60 minutes
10 minutes
60 minutes
•
Reset time
•
Waiting Time after an alarm in Walk Test
•
Maximum Time in Day Mode
•
Minimum Time for Mains Trouble signal
•
Prealarm control Stand-by Time
•
Alarm control Stand-by Time
•
Sounder control Stand-by Time
•
Memory Verification Time
MAX SYSTEM TIME | A00
IN DAY MODE
| G00
1 h
| D00
| E00
MAX SYSTEM TIME | A00
IN DAY MODE
| G00
1 h
__
| D00
| E00