D6001DE-L Double Unit Series (Double Egress)
Power Operator
Controller Interface Description
Screen 1
Adjustments
Default
Description
Mount:
Push or Pull
Push
Side of opening operator is mounted on
Hold Open:
0 - 30 sec in 1 sec increments
4s
Amount of time door will stay in full open position after an activation
Open Delay
(previously Start
Delay):
0 - 10 sec in 1 sec increments
0s
Time before operator begins to open door . Allows accessories time to function and not hinder
opening of door
Latch Rtrct:
OFF, 3 - 45 sec in 5 sec increments
OFF
Amount of time power is supplied to a latch retraction device
Home:
see Setting Open Position
-
Used to set Home position and Fully Open position of door
Vestibule:
OFF, 5 - 30 sec in 5 sec increments
OFF
Amount of delay for opening 2nd vestibule door
Push:
OFF or PushNGo
OFF
Turn on or off Push N Go feature . If On, a slight push or pull of the door starts automatic
opening .
Open Speed:
0 - 100% in 1% increments
120
How fast door opens to full open position
Close Speed:
0 - 100% in 1% increments
80
How fast motor returns to home position . As Latch and Sweep on closer are adjusted,
adjustments may be needed for Close Speed to assure closer is not trying to backdrive motor .
Errors:
not adjustable
-
Error code seen by controller . See Page 17 for Controller Error Codes .
Screen 2
Adjustments
Default
Description
Door Feedback:
not adjustable
-
General feedback . Includes Door State, Door Position, Motor Position, Open Limit, Close Limit
Drive Feedback:
not adjustable
-
General feedback . Includes Bus Voltage, Bus Current, Frequency
Usage:
not adjustable
-
General feedback . Includes Open Time, Close Time, Days, Cycles, Firmware Rev
Single:
Single Door, Dble:Follow,
Dble:Master, Dble:Mast Coord
Single
Set on Single for a single, stand alone door. Dble:Follow for Follower door on pair of doors.
Dble:Master for Master door on a pair of doors. Dble:Mast Coor for Master door on a pair of
doors when door coordination is needed .
MastStopOffset:
0-500
180
Adjustable point where Master Coord door will stop and wait for Follower door to fully close
so Follower does not contact astragal attached to Master Coord door
Follow Delay:
0-5 sec in 1 sec increment
0s
Amount of delay for Follower door after Master door has started to open
PDET Option:
On, Off
Off
On or Off for 585 Presence Detector
DT:
Standard,
SS1:Stall,
SS1:Return Open,
SS1:Stall /Open
Stnd
Standard is Door Toggle. SS1:Stall - when sensor detects an obstruction in opening as door is
closing, door will stall until obstruction is removed. SS1:Return Open – when sensor detects
an obstruction in opening as door is closing, door will stop and return to full open position
until obstruction is removed. SS1:Stall/Open – when sensor detects an obstruction in opening
as door is closing, door will stall until obstruction is removed and door will return to full open
position .
A2:
Standard,
SS2:Stall,
SS2:Return Home,
SS2:Stall /Home
Stnd
Standard is Activation mode - just like A1 activation. SS2:Stall – when sensor detects an
obstruction in opening as door is opening, door will stop until obstruction is removed .
SS2:Return Home – when sensor detects an obstruction in opening as door is opening, door
will stop and return to full closed position until obstruction is removed. SS2:Stall/Home
– when sensor detects an obstruction in opening as door is opening, door will stop until
obstruction is removed and door will return to full closed position .
Rly2:
Alarm, Activation, On Opened, On
Closed
Alarm
How Relay 2 is used: Alarm - used with above Alarm Delay; Activation - acts as an additional
NO/NC contact; On Opened - relay trips (closed contacts) when door is in opened position;
On Closed - relay trips (closed contacts) when door reaches fully closed position .
Alarm Delay:
OFF, 30 sec, 60 sec
OFF
Used only for alarm accessories
Slow Speed:
0 - 100% in 1% increments
55
Speed up or slow down door during last few degrees of opening
Hold Speed:
0 - 100% in 1% increments
55
Increase or decrease hold open force (when in “ON” position only, not “H/O”) to compensate
for spring force, wind conditions, etc .
Obst Delay:
0 - 5 sec in 1 sec increments
3s
Obstruction Delay: amount of time operator will push against an obstruction before closing if
during an opening cycle or reopening and trying to close again if during a clocking cycle .