background image

7

Unconditioned Spaces

All ductwork passing through unconditioned space must be 

properly insulated to prevent condensation and minimize 

duct losses. Use insulation with an outer vapor barrier. 

Refer to local codes for insulation material requirements.

Acoustical Ductwork

Certain installations may require acoustical lining inside 

the supply ductwork. Acoustical insulation must be in 

accordance with the current revision of the Sheet Metal 

and Air Conditioning Contractors National Association 

(SMACNA) application standard for duct liners. Duct lining 

must be U.L. classified batts or blankets with a fire hazard 

classification of FHC-25/50 or less.

Fiber ductwork may be used in place of internal duct liners 

if the fiber ductwork is in accordance with the current 

revision of the SMACNA construction standard on fibrous 

glass ducts.

Fibrous ductwork and internal acoustical lining must be 

NFPA Class 1 air ducts when tested per U.L. Standard 

181 for Class 1 ducts.

Downflow to Horizontal Conversion

The unit is shipped ready for downflow duct connections. If 

horizontal ducts are required, the unit must be converted 

according to the directions in the conversion kit for both 

the supply and return ducts.

ELECTRICAL WIRING

 WARNING:

To avoid the risk of electrical shock, personal 
injury, or death, disconnect all electrical power 
to the unit before performing any maintenance 
or service. The unit may have more than one 
electrical power supply.

•  Electrical  connections  must  be  in  compliance  with 

all applicable local codes and ordinances, and with 

the current revision of the National Electric Code  

(ANSI/NFPA 70).

•  For Canadian installations the electrical connections 

and grounding shall comply with the current Canadian 

Electrical Code (CSA C22.1 and/or local codes).

Pre-Electrical Checklist

  Verify that the voltage, frequency, and phase of the 

supply source match the specifications on the unit 

rating plate.

  Verify that the service provided by the utility is sufficient 

to handle the additional load imposed by this equipment. 

See Tables 2a-2b (page 19), Table 3 (page 20) or the 

unit wiring label for proper high and low voltage wiring.

  Verify factory wiring is in accordance with the unit wiring 

diagram. Inspect for loose connections.

  For 3 phase units always check the phase balance.

Line Voltage

It is recommended that the line voltage to the unit be 

supplied from a dedicated branch circuit containing the 

correct fuse or circuit breaker for the unit.

IMPORTANT NOTE:

 

An electrical disconnect must 

be installed readily accessible from and located 

within sight of the unit. (See unit data label for proper 

incoming field wiring). Any other wiring methods must 

be acceptable to authority having jurisdiction.

The power supply for the unit must be in accordance with 

the unit wiring diagram, and the unit rating plate. Connect 

the line-voltage leads to the corresponding terminals on 

the terminal block inside the Element access compartment. 

Refer to physical data drawings for compartment location. 

Use only copper wire for the line voltage power supply 

to this unit. Use proper code agency listed conduit and 

connector for connecting the supply wires.

All P6SP model units are shipped factory ready for Single 

Circuit Electrical Supply connections. See Table 2 or unit 

rating label for proper high voltage wiring requirements.

For Dual Electrical Supply connections see unit rating 

plate or heater kit installation instructions for proper high 

voltage wiring requirements. Use NORDYNE 3-Pole Dual 

Circuit Adaptor (P/N-917468 ) for converting to dual supply 

connections.

 CAUTION:

Label all wires prior to disconnection when 
servicing controls. Wiring errors can cause 

improper  and  dangerous  operation.  Verify 

proper operation after servicing.

Units are shipped from the factory wired for 230 or 460 volt 

operation. On 208-230V units being placed into 208 volt 

operation, remove the lead from the transformer terminal 

marked 240V and connect it to the terminal marked 208V. 

Overcurrent protection must be provided at the branch 

circuit distribution panel and sized as shown on the unit 

rating label and according to the National Electric Code 

and applicable local codes. 

NOTE: 

See the unit rating plate 

for maximum circuit ampacity and maximum overcurrent 

protection limits.

NOTE: 

1-3/8” conduit openings are supplied for high 

voltage field wiring entrance. If smaller openings are 

required use suitable (field supplied) reducers to meet 

specific conduit size requirements.

Unbalanced 3-Phase Supply Voltage

Voltage unbalance occurs when the voltages of all phases 

of a 3-phase power supply are no longer equal. This 

unbalance reduces motor efficiency and performance. 

Some underlying causes of voltage unbalance may include: 

Lack of symmetry in transmission lines, large single-phase 

loads, and unbalanced or overloaded transformers. A 

motor should never be operated when a phase imbalance 

in supply is greater than 2%.

 

Perform the following steps 

to determine the percentage of voltage imbalance:

Содержание P6SP

Страница 1: ...deciding factor when installing this product and using common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper...

Страница 2: ...a Multi Supply 20 Figure 13 Wiring Diag 072 090 120 Series 21 Figure 14 Ladder Diag 072 090 120 Series 22 Blower Performance Tables 23 Table 4 P6SP Alt Accessory Blower Drives 23 Table 5 P6SP 072 C D...

Страница 3: ...place combustible materials including gasoline and any other flammable vapors and liquids in the vicinity of the unit WARNING PROPOSITION 65 WARNING This product contains fiberglass wool a product kno...

Страница 4: ...of gravity Refer to Physical Data info pages 13 18 for center of gravity locations All panels must be securely in place during rigging and hoisting Roof Curb Condensate Drain 3 Min Figure 2 Condensate...

Страница 5: ...or downflow applications never drill or punch holes in unit base Leakage may occur if unit bottom pan is punctured If any brand other than a NORDYNE Roof Curb is to be used the frame support must be c...

Страница 6: ...talled in accordance with all applicablelocalcodesandthestandardsoftheNational Fire Protection Association Standard for Installation of Air Conditioning Systems NFPA 90A Design the ductwork according...

Страница 7: ...ircuit containing the correct fuse or circuit breaker for the unit IMPORTANT NOTE An electrical disconnect must be installed readily accessible from and located within sight of the unit See unit data...

Страница 8: ...ide of the control access panel and in Figures 13 16 pages 21 22 4 Secure the subbase or thermostat to the wall using screws provided with the thermostat 5 Install the correct thermostat housing to su...

Страница 9: ...sor crankcase Failure to comply may result in damage and could cause premature failure of the system This warning should be followed at initial start up and any time the powerhasbeenremovedfor12hourso...

Страница 10: ...ower mode 1 On a call for fan operation the thermostat applies 24 Vac directly to the blower contactor 2 The circulating blower is energized immediately Heating mode 1 On a call for heat the thermosta...

Страница 11: ...mpartment The blower compartment should be cleaned monthly during the heating and cooling seasons to remove any dirt and lint that may have accumulated in the compartment or on the blower and motor Bu...

Страница 12: ...eed for Removal with Curb Knockout for Bottom Power Entry Control Wiring Entry Power Wiring Entry 115v G F C I Convenience Outlet Factory or Field installed option Wiring supplied in field Condenser C...

Страница 13: ...31 8 30 1 2 775 16 1 2 419 30 1 2 775 16 1 2 419 A Corner D Corner C Corner A Corner B B 30 762 16 1 2 419 30 762 16 1 2 419 7 178 7 1 4 184 Filter Access Horizontal Duct connections for optional acc...

Страница 14: ...t mounting location Rating Label 15 3 8 390 AIR AIR Optional Economizer Hoods bottom pan top View Figure 10 P6SP 072 Series Continued physical data continued Dimensions shown in inches mm 5 3 4 146 16...

Страница 15: ...Access Optional Hail Guard Hood front View 43 1 2 1403 30 762 4 102 4 102 7 1 4 184 16 1 2 419 7 178 30 762 16 1 2 419 Filter Access Horz Return Air Opening Condenser Coil Horizontal Discharge Air Ope...

Страница 16: ...n top View 5 3 4 146 16 1 2 419 30 1 2 775 Discharge Air Opening 7 178 7 178 Return Air Opening 16 1 2 419 30 1 2 775 Power Entry 8 3 4 222 62 1575 101 1 4 2572 condenser end Airflow Airflow Compresso...

Страница 17: ...te Drain Field Wiring Electric Element Access 2 51 4 102 Recommended Unit Disconnect Location 16 1 2 30 762 419 16 1 2 7 1 4 4 102 30 762 184 419 178 7 419 16 1 2 Filter Access Coil Condenser Heat Exc...

Страница 18: ...pping Weight Center of Gravity Inches mm Corner Weights Unit Height A B C D Horizontal Duct Applications Vertical Duct Applications Lbs Kg Lbs Kg A B Lbs Kg Lbs Kg Lbs Kg Lbs Kg P6SP 072 C D 845 384 9...

Страница 19: ...090Ca 208 230 V Factory Std 2 ea 13 1 83 1 2 3 1 5 4 4 4 2 35 2 39 39 50 50 090Da 460 V 2 ea 6 1 41 1 2 2 1 16 7 19 20 120Ca 208 230 V Factory Std 2 ea 16 0 110 2 3 1 5 4 4 4 2 41 0 45 45 60 60 120Da...

Страница 20: ...81 92 97 110 60 60 60 60 90 100 100 110 120Da 460 V 22 30 46 55 25 30 50 60 Medium High Static Drive Electrical Data 072C 208 230 V 920609 32 33 51 58 81 92 n a 50 45 60 60 90 100 n a 072D 460 V 9205...

Страница 21: ...2 L3 T1 T2 T3 BLWR CON COM 5 5 S2 CCH S2 FS S2 LP S2 HP YE BR BR BR BR L1 L2 L3 T1 T2 T3 L1 L2 L3 T1 T2 T3 COMP 2 T2 T3 T1 BK BK BK BK BR BR S2 COMP CON S1 COMP CON L3 L1 L1 L2 L2 L3 L3 ECONOMIZER PLU...

Страница 22: ...2 L3 GND 24V Common 24V Hot Compressor 1 T2 T3 T1 CC2 Compressor 2 T2 T1 T3 CC1 Aux Switch N C CC2 Aux Switch N C CC1 CCH1 CCH2 IBC OFC Y1 Factory Jumper CC2 CC1 LVT C 24V COM IBC Aux Switch N O Field...

Страница 23: ...listed below for the high static drive kits The factory standard drive installed in these units has been set to deliver 400 Cfm ton at an External Static Pressure ESP of 0 25 0 30 in Wg Tables 5 10 sh...

Страница 24: ...8 2322 2181 2040 1870 RPM 897 876 855 831 807 780 kW 0 96 0 88 0 80 0 71 0 62 0 54 0 6 CFM 2395 2255 2115 1960 1805 RPM 901 880 858 834 809 kW 0 87 0 79 0 71 0 63 0 55 0 7 CFM 2509 2362 2214 2042 1870...

Страница 25: ...1 1904 RPM 836 812 788 760 731 kW 0 88 0 77 0 67 0 60 0 54 0 6 CFM 2687 2518 2349 2177 2005 RPM 885 862 838 815 791 kW 0 98 0 88 0 79 0 69 0 59 0 7 CFM 2460 2276 2092 RPM 889 865 841 kW 0 90 0 80 0 70...

Страница 26: ...9 3239 3115 2991 2846 2700 2549 2398 2257 RPM 990 972 950 928 904 881 857 833 813 kW 1 52 1 41 1 30 1 20 1 09 0 99 0 89 0 80 0 72 0 7 CFM 3294 3184 3074 2942 2810 2652 2493 2316 RPM 1011 993 975 953 9...

Страница 27: ...2 2919 2776 2616 2455 2282 RPM 986 966 947 928 904 879 856 833 809 kW 1 57 1 46 1 34 1 23 1 12 1 01 0 92 0 83 0 74 0 7 CFM 3360 3251 3142 3012 2881 2722 2563 2388 2212 RPM 1010 990 971 951 931 907 882...

Страница 28: ...9 712 695 678 659 639 623 kW 1 51 1 39 1 27 1 17 1 08 0 99 0 91 0 81 0 5 CFM 3998 3871 3706 3540 3368 3196 3017 RPM 761 747 731 714 697 680 661 kW 1 51 1 42 1 30 1 18 1 09 0 99 0 90 0 6 CFM 4016 3903...

Страница 29: ...1 RPM 743 727 711 694 676 658 640 623 kW 1 52 1 41 1 30 1 19 1 09 0 99 0 89 0 81 0 5 CFM 3969 3816 3662 3490 3318 3127 RPM 746 729 712 695 677 660 kW 1 44 1 32 1 20 1 10 0 99 0 89 0 6 CFM 3851 3719 35...

Страница 30: ...over the range of operation Always reference the charts to determine the ideal amount of sub cooling for a given liquid pressure Units charged to other values will not perform at the rated unit effic...

Страница 31: ...ication Notes for use Add refrigerant when below curve Remove refrigerant when above curve 180 205 230 255 280 305 330 355 380 405 430 455 480 505 530 555 580 50 55 60 65 70 75 80 85 90 95 100 105 110...

Страница 32: ...______ F Temperature Rise ___________ F INSTALLATION ADDRESS CITY_________________________ STATE_________________ UNIT MODEL _________________________________________ UNIT SERIAL _____________________...

Отзывы: