24
P6SP-072(C/D)
Factory Standard: 1Hp Down-flow Performance Chart
‡ Indicates Factory Sheave Setting
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Turn
Open
1
Turn
Open
1.5
Turns
Open
2.0
Turns
Open
2.5
Turns
Open
3.0
Turns
Open
3.5
Turns
Open
4.0
Turns
Open
4.5
Turns
Open
5.0
Turns
Open ‡
5.5
Turns
Open
6.0
Turns
Open
0.2
CFM
2656
2539
2422
RPM
797
771
744
kW
0.81
0.73
0.66
0.3
CFM
2751
2617
2483
2334
2185
RPM
850
826
801
774
747
kW
0.94
0.85
0.76
0.67
0.58
0.4
CFM
2680
2559
2405
2251
2098
1945
RPM
874
852
829
805
778
750
kW
0.95
0.86
0.76
0.66
0.59
0.52
0.5
CFM
2593
2458
2322
2181
2040
1870
RPM
897
876
855
831
807
780
kW
0.96
0.88
0.80
0.71
0.62
0.54
0.6
CFM
2395
2255
2115
1960
1805
RPM
901
880
858
834
809
kW
0.87
0.79
0.71
0.63
0.55
0.7
CFM
2509
2362
2214
2042
1870
RPM
956
930
904
883
861
kW
1.01
0.91
0.81
0.72
0.63
0.8
CFM
2403
2318
2158
1998
RPM
981
959
933
907
kW
1.00
0.92
0.82
0.72
0.9
CFM
2230
2112
1960
1807
RPM
984
962
936
910
kW
0.94
0.83
0.75
0.68
1.0
CFM
RPM
kW
Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil
When used with H5HK Heater kits, not all operational points shown may be available for use. Refer to the H5HK Installation Instruc-
tions to determine the minimum airflow requirements of the applicable heater assembly.
Deduct 250 Cfm for electric heater kits
Table 5. Blower Performance for P6SP-072(C,D) Series
(6 Ton Downflow Models Only)