28
P6SP-120(C/D)a & Q6SP-120(C/D)a
Factory Standard: 1.5Hp Down-flow Performance Chart
‡ Indicates Factory Sheave Setting
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Turn
Open
1
Turn
Open
1.5
Turns
Open
2
Turns
Open
2.5
Turns
Open ‡
3
Turns
Open
3.5
Turns
Open
4
Turns
Open
4.5
Turns
Open
5
Turns
Open
5.5
Turns
Open
6
Turns
Open
0.1
CFM
4468
4349
4230
4086
3942
3804
3665
RPM
706
689
672
653
633
616
599
kW
1.54
1.43
1.32
1.23
1.14
1.04
0.93
0.2
CFM
4412
4244
4124
4003
3847
3690
3546
3402
RPM
725
708
691
674
655
635
618
601
kW
1.58
1.44
1.34
1.24
1.15
1.06
0.96
0.86
0.3
CFM
4192
4042
3888
3733
3589
3445
3287
3129
RPM
727
710
693
676
657
637
620
603
kW
1.49
1.36
1.26
1.15
1.07
0.99
0.89
0.78
0.4
CFM
4106
3951
3796
3631
3466
3316
3165
2993
RPM
745
729
712
695
678
659
639
623
kW
1.51
1.39
1.27
1.17
1.08
0.99
0.91
0.81
0.5
CFM
3998
3871
3706
3540
3368
3196
3017
RPM
761
747
731
714
697
680
661
kW
1.51
1.42
1.30
1.18
1.09
0.99
0.90
0.6
CFM
4016
3903
3760
3616
3428
3240
3052
RPM
791
777
763
749
733
716
700
kW
1.59
1.49
1.41
1.32
1.20
1.09
0.98
0.7
CFM
3903
3801
3693
3512
3330
3118
RPM
806
793
779
766
752
736
kW
1.59
1.48
1.39
1.31
1.23
1.10
0.8
CFM
3654
3542
3406
3214
3022
RPM
808
795
781
768
754
kW
1.49
1.38
1.27
1.19
1.11
0.9
CFM
3356
3232
3074
RPM
810
797
783
kW
1.36
1.26
1.15
1.0
CFM
3013
RPM
812
kW
1.21
Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil
When utilized with H5HK Heater kits, not all operational points shown may be available for use. Refer to the H5HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.
Deduct 250 Cfm for electric heater kits
Table 9. Blower Performance for P6SP-120(C,D)a & Q6SP-120(C,D)a Series
(10 Ton Downflow Models Only)