31
P6SP CHARGING CHARTS (CONTINUED)
180
205
230
255
280
305
330
355
380
405
430
455
480
505
530
555
580
50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135
Li
qui
d
Pr
es
sur
e
(ps
ig)
Liquid Temperature (F)
Charging Chart - Cooling Operation - 7.5T P6 Packaged Units
* See Application Notes for use
Add refrigerant when below curve
Remove refrigerant when above curve
180
205
230
255
280
305
330
355
380
405
430
455
480
505
530
555
580
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
Liq P
(ps
ig)
Liq T (F)
Charging Chart - Cooling Operation - 10T P6 Units
*
See Application Notes for use
Remove refrigerant when above curve
Add refrigerant when below curve
Figure 16. Charging Chart for - 7.5 Ton Units
Figure 17. Charging Chart for - 10 Ton Units