6

3” min

Figure 7. Concrete Pad Installations

Roof 
Curb

Figure 6. Roof Curb Installations

CIRCULATING AIR SUPPLY

 WARNING:

Do not allow combustion products to enter the 
return air ductwork or the circulating air supply. 
Failure to prevent the circulation of combustion 
products into the occupied space can create 
potentially hazardous conditions including 
carbon monoxide poisoning that could result 
in personal injury or death.
All return ductwork must be secured to the 
unit with sheet metal screws. All joints must be 
taped and adequately sealed. When return air 
is provided through the bottom of the unit, the 
joint between the unit and the return air plenum 
must be air tight.
The roof curb or framing must provide sound 
physical support of the unit with no gaps, 
cracks, or sagging between the unit and the 
curb or frame.
Return air and circulating air ductwork must 
not be connected to any other heat producing 
device such as a fireplace insert, stove, etc. This 
may result in fire, explosion, property damage, 
personal injury, or death from carbon monoxide 
poisoning.

•  This unit is designed only for use with a supply and 

return duct. Any exterior ducts, joints, or openings in 

the building roof or walls must be weatherized with 

conventional flashing and sealing compounds.

•  Air  ducts  should  be  installed  in  accordance  with  all 

applicable local codes and the standards of the National 

Fire Protection Association “Standard for Installation 

of Air Conditioning Systems” (NFPA 90A).

•  Design the ductwork according to methods described 

by the Air Conditioning Contractors of America (ACCA) 

Manual Q.

•  It is recommended that the outlet duct be equipped 

with a removable access panel. This opening should 

be accessible when the unit is installed in service and 

shall be of a size such that the smoke or reflected light 

may be observed inside the casing to indicate the 

presence of leaks in the heat exchanger. The cover for 

the opening shall be attached in such a manner as to 

prevent leaks.

•  If outside air is used as return air for ventilation or to 

improve indoor air quality, the system must be designed 

so that the return air to the unit is not less than 50° F 

(10° C) during heating operation. If a combination of 

indoor and outdoor air is used, the ducts and damper 

system must be designed so that the return air supply 

to the unit is equal to the return air supply under normal, 

indoor return air applications.

must be square and level to ensure proper condensate 

drainage. Unit clearances must be in accordance with 

those shown in Figure 1 (page 4).

Unconditioned Spaces

All ductwork passing through unconditioned spaces 

must be properly insulated to minimize duct losses and 

prevent condensation. Use insulation with an outer vapor 

barrier. Refer to local codes for any insulation material 

requirements.

Содержание P6SP

Страница 1: ...deciding factor when installing this product and using common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper...

Страница 2: ...a Multi Supply 20 Figure 13 Wiring Diag 072 090 120 Series 21 Figure 14 Ladder Diag 072 090 120 Series 22 Blower Performance Tables 23 Table 4 P6SP Alt Accessory Blower Drives 23 Table 5 P6SP 072 C D...

Страница 3: ...place combustible materials including gasoline and any other flammable vapors and liquids in the vicinity of the unit WARNING PROPOSITION 65 WARNING This product contains fiberglass wool a product kno...

Страница 4: ...of gravity Refer to Physical Data info pages 13 18 for center of gravity locations All panels must be securely in place during rigging and hoisting Roof Curb Condensate Drain 3 Min Figure 2 Condensate...

Страница 5: ...or downflow applications never drill or punch holes in unit base Leakage may occur if unit bottom pan is punctured If any brand other than a NORDYNE Roof Curb is to be used the frame support must be c...

Страница 6: ...talled in accordance with all applicablelocalcodesandthestandardsoftheNational Fire Protection Association Standard for Installation of Air Conditioning Systems NFPA 90A Design the ductwork according...

Страница 7: ...ircuit containing the correct fuse or circuit breaker for the unit IMPORTANT NOTE An electrical disconnect must be installed readily accessible from and located within sight of the unit See unit data...

Страница 8: ...ide of the control access panel and in Figures 13 16 pages 21 22 4 Secure the subbase or thermostat to the wall using screws provided with the thermostat 5 Install the correct thermostat housing to su...

Страница 9: ...sor crankcase Failure to comply may result in damage and could cause premature failure of the system This warning should be followed at initial start up and any time the powerhasbeenremovedfor12hourso...

Страница 10: ...ower mode 1 On a call for fan operation the thermostat applies 24 Vac directly to the blower contactor 2 The circulating blower is energized immediately Heating mode 1 On a call for heat the thermosta...

Страница 11: ...mpartment The blower compartment should be cleaned monthly during the heating and cooling seasons to remove any dirt and lint that may have accumulated in the compartment or on the blower and motor Bu...

Страница 12: ...eed for Removal with Curb Knockout for Bottom Power Entry Control Wiring Entry Power Wiring Entry 115v G F C I Convenience Outlet Factory or Field installed option Wiring supplied in field Condenser C...

Страница 13: ...31 8 30 1 2 775 16 1 2 419 30 1 2 775 16 1 2 419 A Corner D Corner C Corner A Corner B B 30 762 16 1 2 419 30 762 16 1 2 419 7 178 7 1 4 184 Filter Access Horizontal Duct connections for optional acc...

Страница 14: ...t mounting location Rating Label 15 3 8 390 AIR AIR Optional Economizer Hoods bottom pan top View Figure 10 P6SP 072 Series Continued physical data continued Dimensions shown in inches mm 5 3 4 146 16...

Страница 15: ...Access Optional Hail Guard Hood front View 43 1 2 1403 30 762 4 102 4 102 7 1 4 184 16 1 2 419 7 178 30 762 16 1 2 419 Filter Access Horz Return Air Opening Condenser Coil Horizontal Discharge Air Ope...

Страница 16: ...n top View 5 3 4 146 16 1 2 419 30 1 2 775 Discharge Air Opening 7 178 7 178 Return Air Opening 16 1 2 419 30 1 2 775 Power Entry 8 3 4 222 62 1575 101 1 4 2572 condenser end Airflow Airflow Compresso...

Страница 17: ...te Drain Field Wiring Electric Element Access 2 51 4 102 Recommended Unit Disconnect Location 16 1 2 30 762 419 16 1 2 7 1 4 4 102 30 762 184 419 178 7 419 16 1 2 Filter Access Coil Condenser Heat Exc...

Страница 18: ...pping Weight Center of Gravity Inches mm Corner Weights Unit Height A B C D Horizontal Duct Applications Vertical Duct Applications Lbs Kg Lbs Kg A B Lbs Kg Lbs Kg Lbs Kg Lbs Kg P6SP 072 C D 845 384 9...

Страница 19: ...090Ca 208 230 V Factory Std 2 ea 13 1 83 1 2 3 1 5 4 4 4 2 35 2 39 39 50 50 090Da 460 V 2 ea 6 1 41 1 2 2 1 16 7 19 20 120Ca 208 230 V Factory Std 2 ea 16 0 110 2 3 1 5 4 4 4 2 41 0 45 45 60 60 120Da...

Страница 20: ...81 92 97 110 60 60 60 60 90 100 100 110 120Da 460 V 22 30 46 55 25 30 50 60 Medium High Static Drive Electrical Data 072C 208 230 V 920609 32 33 51 58 81 92 n a 50 45 60 60 90 100 n a 072D 460 V 9205...

Страница 21: ...2 L3 T1 T2 T3 BLWR CON COM 5 5 S2 CCH S2 FS S2 LP S2 HP YE BR BR BR BR L1 L2 L3 T1 T2 T3 L1 L2 L3 T1 T2 T3 COMP 2 T2 T3 T1 BK BK BK BK BR BR S2 COMP CON S1 COMP CON L3 L1 L1 L2 L2 L3 L3 ECONOMIZER PLU...

Страница 22: ...2 L3 GND 24V Common 24V Hot Compressor 1 T2 T3 T1 CC2 Compressor 2 T2 T1 T3 CC1 Aux Switch N C CC2 Aux Switch N C CC1 CCH1 CCH2 IBC OFC Y1 Factory Jumper CC2 CC1 LVT C 24V COM IBC Aux Switch N O Field...

Страница 23: ...listed below for the high static drive kits The factory standard drive installed in these units has been set to deliver 400 Cfm ton at an External Static Pressure ESP of 0 25 0 30 in Wg Tables 5 10 sh...

Страница 24: ...8 2322 2181 2040 1870 RPM 897 876 855 831 807 780 kW 0 96 0 88 0 80 0 71 0 62 0 54 0 6 CFM 2395 2255 2115 1960 1805 RPM 901 880 858 834 809 kW 0 87 0 79 0 71 0 63 0 55 0 7 CFM 2509 2362 2214 2042 1870...

Страница 25: ...1 1904 RPM 836 812 788 760 731 kW 0 88 0 77 0 67 0 60 0 54 0 6 CFM 2687 2518 2349 2177 2005 RPM 885 862 838 815 791 kW 0 98 0 88 0 79 0 69 0 59 0 7 CFM 2460 2276 2092 RPM 889 865 841 kW 0 90 0 80 0 70...

Страница 26: ...9 3239 3115 2991 2846 2700 2549 2398 2257 RPM 990 972 950 928 904 881 857 833 813 kW 1 52 1 41 1 30 1 20 1 09 0 99 0 89 0 80 0 72 0 7 CFM 3294 3184 3074 2942 2810 2652 2493 2316 RPM 1011 993 975 953 9...

Страница 27: ...2 2919 2776 2616 2455 2282 RPM 986 966 947 928 904 879 856 833 809 kW 1 57 1 46 1 34 1 23 1 12 1 01 0 92 0 83 0 74 0 7 CFM 3360 3251 3142 3012 2881 2722 2563 2388 2212 RPM 1010 990 971 951 931 907 882...

Страница 28: ...9 712 695 678 659 639 623 kW 1 51 1 39 1 27 1 17 1 08 0 99 0 91 0 81 0 5 CFM 3998 3871 3706 3540 3368 3196 3017 RPM 761 747 731 714 697 680 661 kW 1 51 1 42 1 30 1 18 1 09 0 99 0 90 0 6 CFM 4016 3903...

Страница 29: ...1 RPM 743 727 711 694 676 658 640 623 kW 1 52 1 41 1 30 1 19 1 09 0 99 0 89 0 81 0 5 CFM 3969 3816 3662 3490 3318 3127 RPM 746 729 712 695 677 660 kW 1 44 1 32 1 20 1 10 0 99 0 89 0 6 CFM 3851 3719 35...

Страница 30: ...over the range of operation Always reference the charts to determine the ideal amount of sub cooling for a given liquid pressure Units charged to other values will not perform at the rated unit effic...

Страница 31: ...ication Notes for use Add refrigerant when below curve Remove refrigerant when above curve 180 205 230 255 280 305 330 355 380 405 430 455 480 505 530 555 580 50 55 60 65 70 75 80 85 90 95 100 105 110...

Страница 32: ...______ F Temperature Rise ___________ F INSTALLATION ADDRESS CITY_________________________ STATE_________________ UNIT MODEL _________________________________________ UNIT SERIAL _____________________...

Отзывы: