![Nortek AB 175 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/nortek/ab-175/ab-175_installation-operation-and-parts_1705889005.webp)
Form
I-A C (2-17),
Page
5
Gap to be kept
to a minimum
6’- 0” (1.8m)
minimum
Bottom of air curtain
to be level with top
of door opening
Outside
Door
FIGURE 2
-
Dimensional
Clearances
For safety and convenience, provide clearances as shown in the following table.
Clearance to combustibles is defined as the minimum distance from the heater to a
surface or object that is necessary to ensure that a surface temperature of 90°F above
the surrounding ambient temperature is not exceeded. Minimum clearances are also
listed on the heater rating plate.
Minimum Clearances to Combustibles - ALL Models
Service Side
Opposite Service Side
Front
Top
Bottom
Flue
inches
18
6
3
18
36
6
mm
457
152
76
457
914
152
4.2
Combustible
Clearances
No
Feature
1
Main power cable
2
Gas supply line
3
Combustion air inlet
4
Limit control sensor
5
Vacuum line
6
Venter motor
1
3
2
4
5
4.3 Features
6
Содержание AB 175