8.6
Lighting
Sequence
8.7 Startup
8.8 Shutdown
After the venting has been installed in accordance to Section 6.2. Verify
that the vacuum setting is correct using the following procedure:
•
On the remote console (see photo on page 15), activate the
“Power”
switch to
“ON”
.
•
Turn the remote console
“Heat”
switch to
“ON”
. The air curtain exhaust
fan should now start. If it did not start, follow the “Trouble Shooting the Air
Distribution Fans” flow chart in
Section 9.0
to start fan(s).
•
Locate plastic vacuum line on top of the air curtain. Refer to Item No. 5 in
picture shown in
Section 4.3
.
•
Remove the cap from the one port on the tee-fitting (reference picture
shown below) and connect a calibrated manometer at this port.
Remove Cap
Vacuum Setting Range (i.w.c.)
AB 225
AB 175
Cold
.60 - .65
.30 - .35
Hot
.50 - .55
.20 - .25
NOTE:
If the air curtain will not start on the initial start up, the ignition
controller may require resetting. This occurs when ever the unit has
been on a prolonged stand-by period.
This unit is fitted with an automatic spark ignition. When proper airflow for combustion
is proven by the air proving switch and a pre-purge period has elapsed, the integral
igniter and gas control valve operates. The ignition spark ignites the burner and the
flame is detected by the flame sensor. If a burner flame is not detected, the ignition
controller will require manual resetting.
NOTE:
If the air curtain will not reset, use the flow chart in “Trouble Shooting the
Burner Controls”
Section 9.0
to reset the unit.
To startup the air curtain:
•
On the remote console (see photo on page 15), activate the
“Power”
switch to
“ON”
.
•
Turn the remote console
“Heat”
switch to
“ON”
. The air curtain exhaust
fan should now start.
To shutdown the air curtain:
•
On the remote console (see photo on page 15), turn the
“Power”
switch
to
“OFF”
.
•
Turn the remote console
“Heat”
switch to
“OFF”
.
NOTE:
If the air curtain is to be shutdown longer than a week, it is highly
recommended that the gas and electrical services are turned off to the unit.