All wiring and connections, including electrical grounding, MUST be made in accordance
with local, state and national codes and regulations and with the National Electrical
Code (ANSI/NFPA 70) or in Canada the Canadian Electric Code Part 1 CSA C.22.1. In
addition, the installer should be aware of and comply with any local ordinances or gas
company requirements.
Check the rating plate on the unit for the supply voltage and current requirements. A
separate line voltage supply with a fused disconnect switch should be run directly from
the main electrical panel to the heater. All external wiring must be within approved
conduit and have a minimum temperature rating of 60°C. Conduit from the disconnect
switch must be run so as not to interfere with the service panels of the unit.
CAUTION
If any of the original wire as suppled with the unit must be replaced, it
must be replaced with wiring material having a temperature rating of at
least 105°C, except for sensor lead wires which must be 150°C. Refer
to Hazard Levels, page 2.
AB SERIES
DWG # D304456WD REV. #6
TERMINAL BLOCK -- SWITCH BOX
TERMINAL BLOCK -- CONTROL BOX
L1
L2
N
1
2
3
4
5
TERMINAL BLOCK -- UNIT
1
2
3
4
5
HI
MED
L2
E
OPTIONAL FACTORY WIRING
FACTORY WIRING
FIELD WIRING
A TEMPERATURE RATING OF AT LEAST 105 DEGREES C.,
MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING
2. CAUTION: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE
1. THE FOLLOWING CONTROLS ARE SUPPLIED BY REZNOR FOR FIELD INSTALLATION:
3. LINE AND BLOWER MOTOR BRANCH CIRCUIT WIRE SHOULD BE OF A SIZE
TO PREVENT VOLTAGE DROP BEYOND FIVE PERCENT OF SUPPLY LINE VOLTAGE.
NOTES
OPERATING SEQUENCE
1. TURN ON POWER TO UNIT.
TIMES THE MAXIMUM TOTAL INPUT AMPS.
LINE FEEDS CONNECT TO THE LOCKABLE DISCONNECT OR DISTRIBUTION BLOCKS.
USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO 1.25
7. ALL MOTORS MARKED IOL HAVE INTERNAL LINE BREAK.
6. WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH
5. USE #18 GA. WIRE FOR 24 VOLT CONTROL WIRING ON UNIT.
4. SEE RATING PLATE LABEL FOR MCA, TO DETERMINE LINE FEED COPPER WIRE SIZE.
8. FUSIBLE DISCONNECT IS FIELD FURNISHED OR AVAILABLE FROM FACTORY AS AN OPTION.
2. UNIT IS CONTROLLED BY THE SWITCH BOX.
SWITCH BOX
WIRING CODE
BLACK - BK
BROWN - BR
RED - R
ORANGE - O
YELLOW - Y
GREEN - G
BLUE - BL
PURPLE - PR
WHITE - W
7.0 Electrical and
Wiring
7.2 Typical Unit
Wiring Diagram
7.1 Wiring
Wiring Diagram P/N:
D304456WDR6