Form
I-A C (2-17),
Page
17
9.0
Trouble
Shooting
Verify the gas & electric
services are on and
that the remote console
power & heat switches
are “ON”
Check:
1) Ignition controller
YES
Is there power
to the burner?
NO
Trouble Shooting the Air Distribution Fan(s)
YES
Check:
1) Operation of cycling
limit controls.
(If tripped - determine
fault & reset)
2) Control panel burner
on 230V supply
3) External circuit
breakers / fuses
Check:
1) Wiring harness & plugs
2) Operation of vacuum
switch
3) Replace fan
Does the
fan run?
NO
Check:
1) Vacuum switch tube
2) Air inlet & vent
for obstructions
3) Operation of vacuum
switch
4) Replace fan
Does the vacuum
switch pull in?
Check:
1) Ignition controller
2) Wiring harness
NO
YES
Is the burner
sparking?
YES
NO
Check:
1) Integrity of spark leads
2) Integrity of spark
electrode (assembly &
spark gap)
3) Ignition controller
Is the gas
valve open?
Check:
1) Ignition controller
2) Replace gas valve
Check:
1) Burner inlet pressure
2) Burner nozzle pressure
3) Gas valve & polarity
4) Ground
NO
YES
If the heater still fails to
operate normally,
please contact
your factory rep
YES