Table 4. MCA/MOP Data (Single Circuit)

Electrical Data

7

CP-H9HK (05-20) 1012566-B

SINGLE CIRCUIT WITH NO ELECTRIC HEAT

UNIT EQUIPPED WITH:

STANDARD 2-HP

2-SPEED MOTOR

STANDARD 2-HP

2-SPEED MOTOR

+ POWER EXHAUST

HIGH STATIC DRIVE

3-HP ECM 5-SPEED MOTOR

HIGH STATIC DRIVE

3-HP ECM 5-SPEED MOTOR

+ POWER EXHAUST

COOLING

TONNAGE

*

,

**

UNIT

VOLTAGE

***

TOTAL 

LINE

CURRENT

MCA

MOP

TOTAL

LINE

CURRENT

MCA

MOP

TOTAL

LINE

CURRENT

MCA

MOP

TOTAL

LINE

CURRENT

MCA

MOP

6

208–230

26.4

30.8

45

30.4

34.8

50

29.3

33.7

50

33.3

37.7

50

460

12.8

14.9

20

14.8

16.9

25

14.3

16.4

20

16.3

18.4

25

7.5

208–230

36.8

40.1

50

40.8

44.1

50

39.7

43.0

50

43.7

47.0

60

460

17.7

19.2

25

19.7

21.2

25

19.2

20.7

25

21.2

22.7

25

10

208–230

42.6

46.6

60

46.6

50.6

60

45.5

49.5

60

49.5

53.5

60

460

21.1

23.1

30

23.1

25.1

30

22.6

24.6

30

24.6

26.6

30

UNIT EQUIPPED WITH:

STANDARD 3-HP

2-SPEED MOTOR

STANDARD 3-HP

2-SPEED MOTOR

+ POWER EXHAUST

HIGH STATIC DRIVE

5-HP 2-SPEED MOTOR

HIGH STATIC DRIVE

5-HP 2-SPEED MOTOR

+ POWER EXHAUST

COOLING

TONNAGE

*

,

**

UNIT

VOLTAGE

***

TOTAL

LINE

CURRENT

MCA

MOP

TOTAL

LINE

CURRENT

MCA

MOP

TOTAL

LINE

CURRENT

MCA

MOP

TOTAL

LINE

CURRENT

MCA

MOP

12.5

208–230

53.4

58.2

70

57.4

62.2

80

57.6

62.4

80

61.6

66.4

80

460

27.3

29.7

35

29.3

31.7

40

29.5

31.9

40

31.5

33.9

40

 

SINGLE CIRCUIT WITH ELECTRIC HEAT: STANDARD DRIVE MOTOR AND/OR POWER EXHAUST

UNIT EQUIPPED WITH:

2-HP 2-SPEED MOTOR + HEATER KIT

2-HP 2-SPEED MOTOR + HEATER KIT + POWER EXHAUST

COOLING

TONNAGE

*

,

**

UNIT

VOLTAGE

***

MCA

MOP

MCA

MOP

9 KW

18 KW

30 KW

35 KW

9 KW 18 KW

30 KW

35 KW

9 KW

18 KW

30 KW

35 KW

9 KW 18 KW 30 KW

35 KW

6

208–240

31.0-34.6 52.9-59.9 82.5-94.1 98.3-112.1 45-45 60-60

90-100

100-125 36.0-39.6 57.9-64.9 87.5-99.1 103.3-117.1 50-50 60-70 90-100 110-125

480

18.5

30.8

46.9

56.0

20

35

50

60

21.0

33.3

49.4

58.5

25

35

50

60

7.5

208–240

40.1-40.1 52.9-59.9 82.5-94.1 98.3-112.1 50-50 60-60

90-100

100-125 44.1-44.1 57.9-64.9 87.5-99.1 103.3-117.1 50-50 60-70 90-100 110-125

480

19.2

30.8

46.9

56.0

25

35

50

60

21.2

33.3

49.4

58.5

25

35

50

60

10

208–240

46.6-46.6 52.9-59.9 82.5-94.1 98.3-112.1 60-60 60-60

90-100

100-125 50.6-50.6 57.9-64.9 87.5-99.1 103.3-117.1 60-60 60-70 90-100 110-125

480

23.1

30.8

46.9

56.0

30

35

50

60

25.1

33.3

49.4

58.5

30

35

50

60

UNIT EQUIPPED WITH:

3-HP 2-SPEED MOTOR + HEATER KIT

3-HP 2-SPEED MOTOR + HEATER KIT + POWER EXHAUST

COOLING

TONNAGE

*

,

**

UNIT

VOLTAGE

***

MCA

MOP

MCA

MOP

9 KW

18 KW

30 KW

35 KW

9 KW 18 KW

30 KW

35 KW

9 KW

18 KW

30 KW

35 KW

9 KW 18 KW 30 KW

35 KW

12.5

208–240

58.2-58.2 58.9-65.9 88.5-100.1 104.3-118.1 70-70 60-70

90-110

110-125 62.2-62.2 63.9-70.9 93.5-105.1 109.3-123.1 80-80 70-80 100-110 110-125

480

29.7

33.8

49.9

59.0

35

35

50

60

31.7

36.3

52.4

61.9

40

40

60

70

SINGLE CIRCUIT WITH ELECTRIC HEAT: HIGH STATIC DRIVE MOTOR AND/OR POWER EXHAUST

UNIT EQUIPPED WITH:

3-HP ECM MOTOR + HEATER KIT

3-HP ECM MOTOR + HEATER KIT + POWER EXHAUST

COOLING

TONNAGE

*

,

**

UNIT

VOLTAGE

***

MCA

MOP

MCA

MOP

9 KW

18 KW

30 KW

35 KW

9 KW 18 KW

30 KW

35 KW

9 KW

18 KW

30 KW

35 KW

9 KW 18 KW 30 KW

35 KW

6

208–240

34.6-38.3 56.5-63.5 86.1-97.8 101.9-115.8 50-50 60-70

90-100

110-125 39.6-43.3 61.5-68.5 91.1-102.8 106.9-120.8 50-50 70-70 100-110 110-125

480

20.4

32.6

48.8

57.9

25

35

50

60

22.9

35.1

51.3

60.4

25

40

60

70

7.5

208–240

43.0-43.0 56.5-63.5 86.1-97.8 101.9-115.8 50-50 60-70

90-100

110-125 47.0-47.0 61.5-68.5 91.1-102.8 106.9-120.8 60-60 70-70 100-110 110-125

480

20.7

32.6

48.8

57.9

25

35

50

60

22.9

35.1

51.3

60.4

25

40

60

70

10

208–240

49.5-49.5 56.5-63.5 86.1-97.8 101.9-115.8 60-60 60-70

90-100

110-125 53.5-53.5 61.5-68.5 91.1-102.8 106.9-120.8 60-60 70-70 100-110 110-125

480

24.6

32.6

48.8

57.9

30

35

50

60

26.6

35.1

51.3

60.4

30

40

60

70

UNIT EQUIPPED WITH:

5-HP 2-SPEED MOTOR + HEATER KIT

5-HP 2-SPEED MOTOR + HEATER KIT + POWER EXHAUST

COOLING

TONNAGE

*

,

**

UNIT

VOLTAGE

***

MCA

MOP

MCA

MOP

9 KW

18 KW

30 KW

35 KW

9 KW 18 KW

30 KW

35 KW

9 KW

18 KW

30 KW

35 KW

9 KW 18 KW 30 KW

35 KW

12.5

208–240

62.4-62.4 64.1-71.1 93.8-105.4 109.5-123.4 80-80 70-80

100-110 110-125 66.4-66.4 69.1-76.1 98.8-110.4 114.5-128.4 80-80 70-80 100-125 125-150

480

31.9

36.5

52.6

61.8

40

40

60

70

33.9

39.0

55.1

64.3

40

40

60

70

*

For C series units: Nominal unit input voltage = 208–230V/60-Hz/3PH, minimum allowed unit voltage = 187V, and maximum allowed voltage = 253V.

**

For D series units: nominal unit input voltage = 460V/60-Hz/3PH, minimum allowed unit voltage = 414V, and maximum allowed voltage = 506V.

***

To achieve the rated unit performance, unit voltage should be within 2% of nominal.

KEY: FLA = Full Load Amps, MCA = Minimum Circuit Ampacity, RLA = Rated Load Amps, MOP = Maximum Over-Current Protection, and LRA = Locked Rotor Amps.

Содержание 1011669

Страница 1: ...with these instructions and with all applicable national and local codes and standards Please read all instructions carefully before starting the installation Return these instructions to the customer...

Страница 2: ...ons are primarily intended to assist qualified individuals experienced in the properinstallationofthesecomponents Somelocalcodes may require licensed installation service personnel for this type of eq...

Страница 3: ...and DO NOT serve as a unit disconnect The circuit breakers DO NOT provide over current protection of the supply wiring Whether or not circuit breakers are used in the units protection and disconnect...

Страница 4: ...supply grille 1 Remove Compressor Access panel See Figure 2 foam wire guards for later use See 4 Install the DIN rail mounting bracket inside of the unit and tightly secure it with two screws See NOT...

Страница 5: ...m flange of the element mounting plate to the bottom pan and then one in the rear of the element assembly support bracket as shown in and 11 Route all wiring out the two wire passage holes and foam wi...

Страница 6: ...0Q 21 1011675 2 Figure 18 210 F 35 H9HK035Q 21 1011678 2 Figure 18 210 F 6 7 5 10 and 12 5 ton 460V 3PH P7TQ 072 090 120 150 D 9 H9HK009S 01 1011670 NONE Figure 15 155 F 18 H9HK018S 01 1011673 NONE Fi...

Страница 7: ...49 4 58 5 30 35 50 60 UNIT EQUIPPED WITH 3 HP 2 SPEED MOTOR HEATER KIT 3 HP 2 SPEED MOTOR HEATER KIT POWER EXHAUST COOLING TONNAGE UNIT VOLTAGE MCA MOP MCA MOP 9 KW 18 KW 30 KW 35 KW 9 KW 18 KW 30 KW...

Страница 8: ...7 40 31 7 40 31 7 40 31 7 40 14 9 15 27 1 30 43 3 45 52 3 60 HIGH STATIC DRIVE OPTIONAL 3 HP ECM MOTOR 6 208 240 33 7 50 33 7 50 33 7 50 33 7 50 23 5 27 1 30 30 45 4 52 3 50 60 75 0 86 6 80 90 90 7 1...

Страница 9: ...POWER SUPPLY L1 L2 L3 To Cooling Circuit Power Supply Disconnect Main Control Panel 3 Pole Terminal Block To Cooling Components and Control L1 L2 L3 L1 L2 L3 Electric Heat 3 Pole Terminal Block Elect...

Страница 10: ...BE REPLACED WITH WIRING MATERIAL OF THE 1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1...

Страница 11: ...T BE REPLACED WITH WIRING MATERIAL OF THE 1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS...

Страница 12: ...OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012105A Replaces 10121050 05 17 18 kW 1 Stage 20...

Страница 13: ...RING MATERIAL OF THE 1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012106A Replaces 10...

Страница 14: ...HE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012108A Replaces 10121080 05 17 30 35 kW 1 Stage 208...

Страница 15: ...THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012109A Replaces 10121090 05 17 30 35 kW 1 Stage 48...

Страница 16: ...HESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER Specifications and illustrations subject to change without notice or incurring obligations 2020 Nortek Global HVAC LLC O Fallon MO All rights reserved...

Отзывы: