background image

overcurrent protection of the unit supply wire must be 

provided at the branch circuit distribution panel and must 

be sized as shown in 

Table 3, (page 6)

 or on the unit 

rating label and according to the National Electric Code, 

Canadian Electrical Code and applicable local codes. 

NOTE: In most cases the overcurrent protection specified 

on the unit rating label is less than the 60 amp rating of 

the circuit breakers used in the units. This is because 

the function of the overcurrent protection required at the 

distribution panel (field supplied) and the unit mounted 

breakers is different.

Breaker Removal

Insert a screwdriver into the hole (in the white release tab) 

and pull down. 

NOTE: The white release tab is located at 

the base of the breaker under the line side (right) terminals.

HEAT KIT INSTALLATION

Rooftop installations with vertical ducts must be provided 

with a 90-degree elbow installed in the supply duct to 

comply with U. L. (Underwriters Laboratories) codes for 

use with electric heat so the elements are not directly 

over a supply grille.

1.  Remove Compressor Access panel. See Figure 2.

foam wire guards for later use. See 

 

.

4.  Install the DIN rail mounting bracket inside of the 

unit and tightly secure it with two screws. See 

 

NOTE: This step needs to be performed only if circuit 

breakers are included with your kit.

5.  Mount circuit breakers (if included with your kit) onto the 

Figure 2. Compressor Access Panel

Figure 3. Electric Heat Kit Access Panel

2.  Remove electric heat vestibule cover by pulling straight 

out, perpendicular to the unit. See 

 

.

3.  Remove electric heat access plate. Retain all screws and 

Figure 6. Single Circuit Breaker and Contactor

Figure 5. DIN Rail Location

Figure 4. Electric Heat Access Plate

DIN rail. 

NOTE: Secure circuit breaker(s) to bracket by 

hooking the rear top groove over the din rail and pushing 

in on the bottom until it snaps into place. Refer to 

Table 

3, (page 6)

 for quantity.

6.  Attach Black (T1), Yellow (T2), and Red (T3) power leads 

from the circuit breaker(s) to L1, L2, and L3 on the 3 pole 

terminal block.

7.  Mount element control contactor (1 or 2 depending on 

kit) to the control panel with two screws. Make sure L1/

L2/L3 wiring point to the left. See 

 

.

8.  Attach Black (T1), Yellow (T2), and Red (T3) of contactor 

4

CP-H9HK (05-20) 1012566-B

Содержание 1011669

Страница 1: ...with these instructions and with all applicable national and local codes and standards Please read all instructions carefully before starting the installation Return these instructions to the customer...

Страница 2: ...ons are primarily intended to assist qualified individuals experienced in the properinstallationofthesecomponents Somelocalcodes may require licensed installation service personnel for this type of eq...

Страница 3: ...and DO NOT serve as a unit disconnect The circuit breakers DO NOT provide over current protection of the supply wiring Whether or not circuit breakers are used in the units protection and disconnect...

Страница 4: ...supply grille 1 Remove Compressor Access panel See Figure 2 foam wire guards for later use See 4 Install the DIN rail mounting bracket inside of the unit and tightly secure it with two screws See NOT...

Страница 5: ...m flange of the element mounting plate to the bottom pan and then one in the rear of the element assembly support bracket as shown in and 11 Route all wiring out the two wire passage holes and foam wi...

Страница 6: ...0Q 21 1011675 2 Figure 18 210 F 35 H9HK035Q 21 1011678 2 Figure 18 210 F 6 7 5 10 and 12 5 ton 460V 3PH P7TQ 072 090 120 150 D 9 H9HK009S 01 1011670 NONE Figure 15 155 F 18 H9HK018S 01 1011673 NONE Fi...

Страница 7: ...49 4 58 5 30 35 50 60 UNIT EQUIPPED WITH 3 HP 2 SPEED MOTOR HEATER KIT 3 HP 2 SPEED MOTOR HEATER KIT POWER EXHAUST COOLING TONNAGE UNIT VOLTAGE MCA MOP MCA MOP 9 KW 18 KW 30 KW 35 KW 9 KW 18 KW 30 KW...

Страница 8: ...7 40 31 7 40 31 7 40 31 7 40 14 9 15 27 1 30 43 3 45 52 3 60 HIGH STATIC DRIVE OPTIONAL 3 HP ECM MOTOR 6 208 240 33 7 50 33 7 50 33 7 50 33 7 50 23 5 27 1 30 30 45 4 52 3 50 60 75 0 86 6 80 90 90 7 1...

Страница 9: ...POWER SUPPLY L1 L2 L3 To Cooling Circuit Power Supply Disconnect Main Control Panel 3 Pole Terminal Block To Cooling Components and Control L1 L2 L3 L1 L2 L3 Electric Heat 3 Pole Terminal Block Elect...

Страница 10: ...BE REPLACED WITH WIRING MATERIAL OF THE 1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1...

Страница 11: ...T BE REPLACED WITH WIRING MATERIAL OF THE 1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS...

Страница 12: ...OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012105A Replaces 10121050 05 17 18 kW 1 Stage 20...

Страница 13: ...RING MATERIAL OF THE 1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012106A Replaces 10...

Страница 14: ...HE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012108A Replaces 10121080 05 17 30 35 kW 1 Stage 208...

Страница 15: ...THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012109A Replaces 10121090 05 17 30 35 kW 1 Stage 48...

Страница 16: ...HESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER Specifications and illustrations subject to change without notice or incurring obligations 2020 Nortek Global HVAC LLC O Fallon MO All rights reserved...

Отзывы: