Table 5. MCA/MOP Data (Multiple Circuit)
8
CP-H9HK (05-20) 1012566-B
MULTIPLE CIRCUIT ELECTRICAL DATA
STANDARD 2-HP 2-SPEED MOTOR
COOLING
TONNAGE
*
,
**
UNIT
VOLTAGE
***
COOLING CIRCUIT
HEATING CIRCUIT
9 KW
18 KW
30 KW
35 KW
9 KW
18 KW
30 KW
35 KW
MCS MOP MCS MOP MCS MOP MCS MOP
MCS
MOP
MCS
MOP
MCS
MOP
MCS
MOP
6
208-240V
30.8
45.0
30.8
45.0
30.8
45.0
30.8
45.0
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480V
14.9
20.0
14.9
20.0
14.9
20.0
14.9
20.0
14.9
15.0
27.1
30.0
43.3
45.0
52.3
60.0
7.5
208-240V
40.1
50
40.1
50
40.1
50
40.1
50
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480V
19.2
25
19.2
25
19.2
25
19.2
25
14.9
15
27.1
30
43.3
45
52.3
60
10
208-240V
46.6
60
46.6
60
46.6
60
46.6
60
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480V
23.1
30
23.1
30
23.1
30
23.1
30
14.9
15
27.1
30
43.3
45
52.3
60
STANDARD 3-HP 2-SPEED MOTOR
12.5
208-240V
58.2
70
58.2
70
58.2
70
58.2
70
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480V
29.7
35
29.7
35
29.7
35
29.7
35
14.9
15
27.1
30
43.3
45
52.3
60
STANDARD 2-HP 2-SPEED MOTOR WITH POWER EXHAUST (OPTIONAL)
COOLING
TONNAGE
*
,
**
UNIT
VOLTAGE
***
COOLING CIRCUIT
HEATING CIRCUIT
9 KW
18 KW
30 KW
35 KW
9 KW
18 KW
30 KW
35 KW
MCS MOP MCS MOP MCS MOP MCS MOP
MCS
MOP
MCS
MOP
MCS
MOP
MCS
MOP
6
208–240
34.8
50
34.8
50
34.8
50
34.8
50
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480
16.9
25
16.9
25
16.9
25
16.9
25
14.9
15.0
27.1
30.0
43.3
45.0
52.3
60.0
7.5
208–240
44.1
50
44.1
50
44.1
50
44.1
50
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480
21.2
25
21.2
25
21.2
25
21.2
25
14.9
15
27.1
30
43.3
45
52.3
60
10
208–240
50.6
60
50.6
60
50.6
60
50.6
60
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480
25.1
30
25.1
30
25.1
30
25.1
30
14.9
15
27.1
30
43.3
45
52.3
60
STANDARD 3-HP 2-SPEED MOTOR WITH POWER EXHAUST (OPTIONAL)
12.5
208–240
62.2
80
62.2
80
62.2
80
62.2
80
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480
31.7
40
31.7
40
31.7
40
31.7
40
14.9
15
27.1
30
43.3
45
52.3
60
HIGH STATIC DRIVE (OPTIONAL): 3-HP ECM MOTOR
6
208–240
33.7
50
33.7
50
33.7
50
33.7
50
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480
16.4
20
16.4
20
16.4
20
16.4
20
14.9
15.0
27.1
30.0
43.3
45.0
52.3
60.0
7.5
208–240
43.0
50
43.0
50
43.0
50
43.0
50
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480
20.7
25
20.7
25
20.7
25
20.7
25
14.9
15
27.1
30
43.3
45
52.3
60
10
208–240
49.5
60
49.5
60
49.5
60
49.5
60
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480
24.6
30
24.6
30
24.6
30
24.6
30
14.9
15
27.1
30
43.3
45
52.3
60
HIGH STATIC DRIVE (OPTIONAL): 5-HP 2-SPEED MOTOR
12.5
208–240
62.4
80
62.4
80
62.4
80
62.4
80
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480
31.9
40
31.9
40
31.9
40
31.9
40
14.9
15
27.1
30
43.3
45
52.3
60
HIGH STATIC DRIVE (OPTIONAL): 3-HP ECM MOTOR WITH POWER EXHAUST (OPTIONAL)
6
208–240
37.7
50
37.7
50
37.7
50
37.7
50
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480
18.4
25
18.4
25
18.4
25
18.4
25
14.9
15.0
27.1
30.0
43.3
45.0
52.3
60.0
7.5
208–240
47.0
60
47.0
60
47.0
60
47.0
60
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480
22.7
25
22.7
25
22.7
25
22.7
25
14.9
15
27.1
30
43.3
45
52.3
60
10
208–240
53.5
60
53.5
60
53.5
60
53.5
60
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480
26.6
30
26.6
30
26.6
30
26.6
30
14.9
15
27.1
30
43.3
45
52.3
60
HIGH STATIC DRIVE (OPTIONAL): 5-HP 2-SPEED MOTOR WITH POWER EXHAUST (OPTIONAL)
12.5
208–240
66.4
80
66.4
80
66.4
80
66.4
80
23.5-27.1
30-30
45.4-52.3 50-60
75.0-86.6
80-90 90.7-104.6
100-110
480
33.9
40
33.9
40
33.9
40
33.9
40
14.9
15
27.1
30
43.3
45
52.3
60
*
For C series units: Nominal unit input voltage = 208–230V/60-Hz/3PH, minimum allowed unit voltage = 187V, and maximum allowed voltage = 253V.
**
For D series units: nominal unit input voltage = 460V/60-Hz/3PH, minimum allowed unit voltage = 414V, and maximum allowed voltage = 506V.
***
To achieve the rated unit performance, unit voltage should be within 2% of nominal.
KEY: FLA = Full Load Amps, MCA = Minimum Circuit Ampacity, RLA = Rated Load Amps, MOP = Maximum Over-Current Protection, and LRA = Locked Rotor Amps.