9 Tabular overview of the program procedures
Charge
74
©
Nortec Electronics 2018
9.3.9
Program 222: Charge NiCd battery SAFT
Name according to manual: Constant Current Charge for SAFT with C
1
22: NiCd battery SAFT
select Batteryprocessing:
P2: Charge
Enter:
Number of cells
Rated capacity
Step 1:
Charging with C
1
until a charging voltage of 1.57
V × number of cells is reached.
Step 2:
Topping charge C
10
for 4 hours.
In case no automatic cell tester is connected:
30 minutes before the end of the topping charge a signal asks for the measurement of the single cells
voltages and to control the electrolyte level
Otherwise:
30 minutes before the end of the topping charge you are requested to control the electrolyte level.
End of program
Time monitoring:
Charging maximum 75 minutes.
Voltage monitoring:
Monitoring minus ΔU > 30mV/cell during charging, error message:
minus delta U detected