8 Program selection
Battery data entry
©
Nortec Electronics 2018
41
8.4.3
Work with lead batteries
All battery types starting with 1x respond. In particular, these are:
Type 10:
Lead acid battery sealed MIL
Type 11:
Lead acid battery sealed commercial
Type 12:
Valve regulated lead acid aircraft battery
Type 16:
Lead acid battery vented commercial
Type 17:
Lead acid battery MIL P3-C Orion
Type 19:
Lead acid battery (free input)
Choose the type using the following keys
and confirm with pressing the key
afterwards select kind of treatment.
For example, select the charging of a military sealed lead battery:
Use this key
to get to the desired kind of treatment and confirm by pressing the key
On dispay you will see:
10: Pb battery sealed MIL
P410:
Please enter parameter:
RATED VOLTAGE: 00.00 V
Enter the nominal voltage of the battery. You find it on the identification plate of the battery.
NOTE:
Lead batteries usually consist of several cells of 2
V each.
Commercially common:
2
V
cells
6
V
batteries
12
V
batteries
24
V
batteries
The device only accepts 2.0
V and the multiple. All other entry will be rejected as defective.
Confirm the entered voltage by pressing
. The display shows: