Vent Pipe Installation
Chapter 4. – Installation
• Intake and exhaust should face the same
direction. Intake and exhaust should stay within
the same pressure zone.
• Insert the vent screen. 90° elbow vertical set-
ting (downward).
• Ensure at least 3ft (0.9m) or more distance
between the near edge of the air intake pipe or
exhaust pipe to the inside corner of a wall.
• Ensure at least 2ft (0.6m) or more distance
between intake pipe and exhaust pipe. The
distance is measured at inside of pipe to inner
dimension.
• Intake and exhaust should face the same
direction. Intake and exhaust should stay within
the same pressure zone.
• Insert the vent screen. 90° elbow vertical set-
ting (downward).
• Ensure at least 3ft (0.9m) or more distance
between edge of air intake pipe or exhaust pipe
and corner wall.
• Upper side is exhaust, lower side is intake. The
reverse orientation is not allowed.
• Ensure at least 1ft (0.3m) or more distance be-
tween intake pipe and exhaust pipe.
The distance is measured at the outlets of intake
port (terminal) and exhaust port (terminal).
• Intake and exhaust should face the same
direction. Intake and exhaust should stay within
the same pressure zone.
• Insert the vent screen. 90° elbow vertical set-
ting (downward).
• Ensure at least 3ft (0.9m) or more distance
between edge of air intake pipe or exhaust pipe
and corner wall.
• The pipe farther from the wall is intake, the side
near the wall is exhaust. The reverse connection
is not allowed.
• Ensure at least 1ft (0.3m) or more distance
between intake pipe and exhaust pipe. The
distance is measured at inside of pipe to inner
dimension.
Horizontal Vent Termination- PVC/CPVC Materials Only
* When 3' (0.9m) remote distance between Intake and Exhaust cannot be ensured.
* Can not use Hood termination (PVT-HL)
Vent Pipe Installation (DV-Direct Vent)