87
Warning
Fault
Message
Possible causes
Remedy
–––
E155
Ext. 5 V supply
External 5 V supply of the Nordmann Omega faulty. Voltage too
high or too low.
Note: The Condair Delta SPA Control Box or the Nordmann Ome-
ga, respectively continue to work normally.
Short circuit on LED.
Contact your Nordmann repre-
sentative.
Overload on LED connection.
Check LED connection.
E156
EEPROM read
Reading from EEPROM not possible.
Note: In order to reset the fault, the Condair Delta SPA Control
Box or the Nordmann Omega must be switched off and on again
(depending on which device the fault occurred).
EEPROM defective.
Contact your Nordmann repre-
sentative.
E157
EEPROM write
Writing to EEPROM not possible.
Note: In order to reset the fault, the Condair Delta SPA Control
Box or the Nordmann Omega must be switched off and on again
(depending on which device the fault occurred).
EEPROM defective.
Contact your Nordmann repre-
sentative.
–––
E158
Heat Element 1 control relay
Heating element control relay 1 does not work correctly.
Note: The operation of the Condair Delta SPA Control Box or
Nordmann Omega is stopped. After the fault has been eliminated,
the Nordmann Omega must be switched off and on again. If the
Nordmann Omega is controlled by a Condair Delta SPA Control
Box, the Condair Delta SPA Control Box must also be switched off
and on again after the Nordmann Omega has been restarted.
Heating element control relay 1
on control board blocked.
Contact your Nordmann repre-
sentative.
–––
E159
Heat Element 2 control relay
Heating element control relay 2 does not work correctly.
Note: The operation of the Condair Delta SPA Control Box or
Nordmann Omega is stopped. After the fault has been eliminated,
the Nordmann Omega must be switched off and on again. If the
Nordmann Omega is controlled by a Condair Delta SPA Control
Box, the Condair Delta SPA Control Box must also be switched off
and on again after the Nordmann Omega has been restarted.
Heating element control relay 2
on control board blocked.
Contact your Nordmann repre-
sentative.
–––
E160
Heat Element 3 control relay
Heating element control relay 3 does not work correctly.
Note: The operation of the Condair Delta SPA Control Box or
Nordmann Omega is stopped. After the fault has been eliminated,
the Nordmann Omega must be switched off and on again. If the
Nordmann Omega is controlled by a Condair Delta SPA Control
Box, the Condair Delta SPA Control Box must also be switched off
and on again after the Nordmann Omega has been restarted.
Heating element control relay 3
on control board blocked.
Contact your Nordmann repre-
sentative.
–––
E161
Heat Element 4 control relay
Heating element control relay 4 does not work correctly.
Note: The operation of the Condair Delta SPA Control Box or
Nordmann Omega is stopped. After the fault has been eliminated,
the Nordmann Omega must be switched off and on again. If the
Nordmann Omega is controlled by a Condair Delta SPA Control
Box, the Condair Delta SPA Control Box must also be switched off
and on again after the Nordmann Omega has been restarted.
Heating element control relay 4
on control board blocked.
Contact your Nordmann repre-
sentative.