![Nordica LNK15 EVO Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/nordica/lnk15-evo/lnk15-evo_user-manual_1701827011.webp)
ENGLISH
obliGations of the system operator
the operator is required to
:
- always operate the system in appropriate conditions;
- not make changes or allow others to make changes or tamper with the system;
- read the operating instructions before starting the system;
- have the operation of the whole system checked;
- have the system repaired.
The system must be commissioned by the installing company (specialising in the construction of heating systems) or by an authorised la
nordica spa service centre.
This must be documented in a commissioning report.
It is necessary to check that all system components have been installed correctly and that all control and safety devices are working properly
and are correctly set.
The installer must issue the certification of the entire system installed, with instructions for operation and maintenance.
When it is delivered to the operator, the operation and maintenance of the system and of the boiler, including any additional equipment, must
be explained in detail to him/her or to the person assigned to the management of the system.
In particular, the function of the safety devices and the measures to maintain safe operation must be explained.
chimney
before installing the system, be sure to have all the permissions required by european, national and local regulations.
The chimney and flue pipe must be designed in accordance with the technical specifications of the lnk-evo product.
When sizing and checking the flue, a draught regulator must be installed.
In order to ensure trouble-free operation when installing a new heating system, optimal chimney sizing in accordance with current regulations
is a prerequisite.
The connection to the chimney must be as short as possible.
before installing the system, it is necessary to measure the draught and calculate the flue.
The maximum vacuum in the boiler room must not exceed 4 Pa for combustion air supplied via pipes.
If the combustion air is introduced through an opening in the outer wall, a pressure difference of 3 Pa must not be exceeded.
all information required for the calculation of the flue can be found in the technical specifications of the respective boiler type.
calculated chimneys smaller than the flue gas inlet (150mm) of the boiler are not allowed.
DrauGht reGulator
To ensure the correct operation of lnk-evo wood boilers, it is necessary to use a draught regulator.