P2M054STD-Ver1.2
GB
Main Parameters
Parameter Meaning
cyS
Cycle setting
tEP
: by temperature; the cycle is done according to the
rEM
parameter
tiM
: Timed cycle, based pn the
Pd1,Pd2,Pd3
(Option parameter)
dbC
Defrost before cycle
Yes = defrost is carried out
No = the cycle starts immediately without defrosting
dbH
Defrost end of cycle/before storage
Yes = defrost is carried out
No = the storage phase starts immediately
cap
Storage mode after cycle
Yes = storage phase is carried out
No = the storage phase is disabled
rSP
Set point room pre-cooling phase
When the temperature measured by the chamber probe reaches this value, the
current phase is finished and the next one starts
PdP
Max duration time pre-cooling phase
This is the maximum duration of the pre-cooling phase if the temperature defined
in parameter rSP is not reached at the end of this time it switched to the next phase
(Only available on the ice cream cycle)
iS1
Set point for inserction probe for the first phase
When the temperature measured by the insert probes reaches this value, the
current phase is finished and next one starts
rS1
Chamber set point for the first phase
It prevents temperature from reaching a too low value. This value controls the
operation of the compressor
Pd1
If the cycle is timed for the first phase
It is considered if the insert probe is not present (OFF to 4h 00Min., res 10Min.) at
the end of this time it switches to next phase.
If the cycle is temperature for the first phase
This value is used only if there is an insert probe; this is the maximum duration of
the first phase if the temperature defined in parameter
iS1
is not reached.
iS2
Set point for insertion probe for the second phase
When the temperature measured by the insert probes reaches this value, the
current phase is finished and the next one started.
rS2
Chamber set point for the second phase
It prevents temperature from reaching a too low value.This value controls the
operation of the compressor.
Pd2
If the cycle is timed for the second phase
It is considered if the insert probe is not present (OFF to 4h 00Min., res 10Min.) at
the end of this time it switches to next phase.
If the cycle is temperature for the second phase
This value is used only if there is an insert probe; this is the maximum duration of
the second phase in the event the temperature in the parameter
iS2
is not reached.
HdS
Set point of the hold phase
54
Содержание 45110250
Страница 1: ...Bedienungsanweisung COOL LINE Schnellkühler Schockfroster SKF 5 Easy Art 45110250 2019 12 ...
Страница 3: ...Produktbeschreibung Bezeichnung des Geräts Schockkühler 5 Trays GN und Euronorm 3 ...
Страница 27: ...Sonderzubehör Versetzen des Türanschlags 27 ...
Страница 28: ...Sonderzubehör 28 ...
Страница 33: ...Instruction Manual COOL LINE Blast Chiller SKF 5 Easy Art 45110250 33 ...
Страница 35: ...P2M054STD Ver1 2 GB Product Overview Article Description Blast Chiller N 5 Trays GN and Euronorm 35 ...
Страница 59: ...P2M054STD Ver1 2 GB Optional Accessory How to reverse the door 59 ...
Страница 60: ...P2M054STD Ver1 2 GB Optional Accessory 60 ...
Страница 65: ...Istruzioni d uso Abbattitore SKF 5 Easy Art 45110250 65 ...
Страница 67: ...P2M054STD Ver1 2 IT Panoramica Prodotto Descrizione articolo Abbattitore N 5 Teglie GN e Euronorm 67 ...
Страница 92: ...P2M054STD Ver1 2 IT Accessorio opzionale Come invertire la porta 92 ...
Страница 93: ...P2M054STD Ver1 2 IT Accessorio opzionale 93 ...