Note  Replacement of components

should only be carried out by a

competent person.

Isolate electrical and gas supplies

before replacement of parts.  Check for

gas soundness after replacing gas

carrying components.  Access for

replacement of the main burner

assembly, ignition electrode, flame

electrode, fan, motor, drive belts, is via

the access doors in the fan section.

Inadvertent substitution or replacement

of similar components, particularly

those with plug-in bases, could cause

a hazard.

Main burner assembly

Disconnect main gas supply union and

pilot gas supply, HT cable and flame

rod connections.  Unbolt burner straps

from the burner supports and remove

assembly from heater.  If necessary,

replace damaged sections as required,

re-join flanges using Hermetite,

Plasticoll X10G joining compound.

Replace burner assembly in reverse

order to removal.  Check operation and 

combustion as detailed in the

Commissioning Instructions.

Ignition electrode

Isolate electrical supply, remove HT

cable, unscrew ignition electrode from

burner body, ensure electrode has

3mm spark gap, replace with new and

reconnect HT cable, and protective

boot.

Ignition transformer

Isolate electricity supply, unbolt ignition

transformer.  Disconnect cable from 

terminal block and remove and replace

ignition transformer.  Reconnect

cables.

Flame electrode

Isolate electrical supply, remove cable

from flame electrode, unscrew old rod

and replace with a new one, bending

the probe through 45

˚

so that the probe

runs parallel to the burner plates.  It

will be necessary to   straighten the old

probe prior to unscrewing from the

burner.

Ambi-Tec controller

Isolate electrical supply at heater.

Remove Ambi-Tec front cover,

discount wires from terminal rail

ensuring cable/terminal numbers are

recorded.  Remove 5WA multicode

cable from the base and unscrew base

plate from wall.  Refit new Ambi-Tec

controller, ensuring all wiring

connections are correct.  The Ambi-Tec

controller will require reprogramming

and this should be carried out by a

Nordair Niche Engineer.

Modulating gas valve control unit

Isolate electric supply, unbolt motor

clamp from valve spindle and  remove

motor from motor mounting bracket,

replace and re-connect.  Care should

be taken not to move the valve

spindle, as this will alter the low fire

setting and will require

re-commissioning.

Gas train components

Isolate gas and electricity supply, 

disconnect electrical connections to

valves and modulating valve motor unit.

Unscrew unions on gas train, replace

components where necessary using

approved thread sealing compound,

re-fit and tighten unions.  Gas train

should be leak tested and

recommissioned.

Drive belts

Access is via the twin access doors in

the fan section.  Loosen motor

adjusting screw, replace belts and

re-tension.

Active duct sensor

Isolate electrical supply, remove cover

from sensor, unscrew terminals,

remove cable, remove fixing screw and

withdraw.  Refit new duct sensor and

refit in reverse order.  Potentiometer

will require resetting, this should be

carried out by a Nordair Engineer.

Room sensor

Isolate electrical supply, unclip room 

sensor, unscrew terminal, and remove

cable.  Refit new room sensor and refit

in reverse order.

Air differential pressure switch

Isolate main electrical supply, remove

cover of pressure switch, terminal box.

Disconnect electrical wires, remove 

sensing tubes and unbolt pressure

switch from mounting bracket, replace

the switch, re-connect the sensing

tubes, re-connect the electrical supply.

Recommission the differential pressure

switch by setting to the pressure switch

to 75% of the measured differential 

pressure between pressure points P8

and 9.

Control panel components
Burner programmer

Unscrew body from terminal base and

replace.

Relays

Unplug body and replace.

Motor MPCB

Remove and replace, replace amp trip 

setting.

Control MCB

Remove and replace.

Overheat thermostat

Isolate electrical supply, remove the

cover, disconnect wiring, unscrew from

duct/casing and withdraw.  Fit 

replacement thermostat reconnect

wiring and reset to 85

˚

C for the DV

range and 75

˚

C for the DH range, then

replace cover.

Replacement instructions

Содержание DH2 150

Страница 1: ...DIRECT FIRED DV DH DIRECT GAS FIRED MAKE UP AIR UNITS Installation Commissioning Service Manual Ambi Tec Ambi Stat...

Страница 2: ...d be required on the access side of the heater and a minimum 500mm clearance required on the non access side and top of the heater For heaters mounted in the roof steel work the units can be supported...

Страница 3: ...Internal wiring The amount of interconnecting wiring will depend on the control system being used this will be indicated on the schematic wiring diagram with the minimum connections Ambitec controlle...

Страница 4: ...Louvre 4 OFF 20mm electrical connection points H BSP gas inlet connection B B C Discharge opening C Discharge 50 50 50 500 50 50 50 500 DH2 75 1 2 BSP Weather proofed hood fitted to external units on...

Страница 5: ...SP 1400 856 DH2 75 1 2 BSP Weather proofed hood fitted to external units only ACCESS SIDE VIEW VIEW ON DISCHARGE OUTLET VIEW ON FRESH AIR INLET A Electrical control panel B N Optional extra discharge...

Страница 6: ...set point say 19 C adjustable the heater discharge air temperature is controlled at a constant 40 C by means of a active duct sensor modulating the gas throughput control valve At 1 C above room set...

Страница 7: ...and main electrical supply Gas installation pipework has been tested for soundness Gas installation has been purged Note and record fan motor data badge details Note and record fan and motor pulley si...

Страница 8: ...le and with a pair of grips on the valve spindle minutely close to the valve in small stages until the 5 C temperature rise is obtained With great care tighten the U clamp onto the valve spindle ensur...

Страница 9: ...on pipework has been tested for soundness Gas installation has been purged Note and record fan motor data badge details Note and record fan and motor pulley sizes belt reference and pulley centres Fan...

Страница 10: ...t increase the burner pressure at high fire then the gas control valve requires resetting Connect a separate manometer to pressure tapping point P5 and P9 measure the pressure The differential gas pre...

Страница 11: ...out condition Remove the air sensing tube from the bottom connection of the air pressure switch The heater will lockout Replace and reset Adjust overheat controller set point down until heater shuts o...

Страница 12: ...LATE DRIVE FREE PROFILE DAMPER SLIDE RAILS GREASE PROFILE DAMPER LIMIT SWITCH OPERATION PROFILE DAMPER DRIVE LINKAGE PROFILE DAMPER DRIVE MOTOR DRIVE BELT CONDITION BURNER GAS PORTS RE DRILL BURNER MI...

Страница 13: ...PLATE DRIVE FREE PROFILE DAMPER SLIDE RAILS GREASE PROFILE DAMPER LIMIT SWITCH OPERATION PROFILE DAMPER DRIVE LINKAGE PROFILE DAMPER DRIVE MOTOR DRIVE BELT CONDITION BURNER GAS PORTS RE DRILL BURNER M...

Страница 14: ...ELT CENTRES ALIGNMENT TENSION PROFILE OPENING VELOCITY BURNER SIZE CURRENT L1 L2 L3 OVERLOAD SIZE GAS LINE SUCTION LOW FIRE HIGH FIRE DIFF GOVERNOR INLET PRESS GOVERNOR OUTLET PRESS PILOT PRESSURE AIR...

Страница 15: ...TS BELT CENTRES ALIGNMENT TENSION PROFILE OPENING VELOCITY BURNER SIZE CURRENT L1 L2 L3 OVERLOAD SIZE GAS LINE SUCTION LOW FIRE HIGH FIRE DIFF GOVERNOR INLET PRESS GOVERNOR OUTLET PRESS PILOT PRESSURE...

Страница 16: ...Layout of electrical equipment DV heater Layout of electrical equipment DH heater...

Страница 17: ...rmer V5 Motorised Ball Valve M1 Modulating Control Valve Motor V6 Burner Isolating Valve P4 Air Pressure Switch V7 Pilot Gas Isolating valve T1 Room Sensor V8 Pilot Governor T2 Duct Sensor V9 V10 Pilo...

Страница 18: ...ssure test point P1 and P3 to pressurise the assembly between the two safety shut off valves Connect pressure gauge to pressure test point P4 10 Open V1 any rise in pressure indicates the downstream s...

Страница 19: ...10 x 50 LG HEX Head Set Screw 5 M5 x 12 HEX Head Set Screw 6 M10 Nut and Washer 7 Support Bracket Gasket N0010 8 M5 x 40 HEX Head Set Screw 9 M5 nut and Washer 10 Stainless Steel Mixing Plate N0006 11...

Страница 20: ...he black section normally takes 1 min 28 seconds for the MMI 810 1 Note References to terminal numbers in this section relate to those in the Satronic burner controller sub base and do not correspond...

Страница 21: ...rminal 5 or terminal C If solenoid coils fitted with rectifier the negative side must be connected to terminal 5 or C Flame sensing probe earthing Reposition or replace flame sensing probe Lockout dur...

Страница 22: ...me failure due to loss of gas supply Investigate the cause of gas supply failure Flame failure due to an unstable flame Check the flame signal during the switching from high to low to hire fire Adjust...

Страница 23: ...d Hazel Grove STOCKPORT Cheshire SK7 4LD Tel 0161 482 7900 Fax 0161 482 7901 Description Part No Spark Probe N1014 Flame Probe IEG 18 6 N1007 Satronic MMI810 N1018 4 Pole Miniature Relays N1244 N1260...

Страница 24: ...programming and this should be carried out by a Nordair Niche Engineer Modulating gas valve control unit Isolate electric supply unbolt motor clamp from valve spindle and remove motor from motor mount...

Страница 25: ......

Страница 26: ...n Nortek Global HVAC reserves the right to change product speci cation without due notice NORTEK GLOBAL HVAC UK LTD Fens Pool Avenue Brierley Hill West Midlands DY5 1QA United Kingdom Tel 01384 489 25...

Отзывы: