Nordair Niche DH2 150 Скачать руководство пользователя страница 2

Related documents

The installation of the Nordair direct gas

fired air heater must be in   accordance

with the relevant  requirements of the

current Gas Safety (Installation and Use)

Regulations, building Regulations and

the IEE Wiring Regulations.
It should also be in accordance with any

relevant requirements of the local suppli-

er of gas, Local Authority and the rele-

vant recommendations of the following

documents:

British standards

EN525:1997
Requirements for non-domestic gas fired

forced convection air heaters for space

heating.
BS6230
Specification for installation of gas fired

forced convection air heaters for 

commercial and industrial space heating

of rated input exceeding 60kW (2nd

family gases).

Institution of gas engineers

IGE/UP/1
Soundness testing and purging of 

industrial and commercial gas

installations.
IGE/UP/2
Gas installation pipework, boosters and

compressors on industrial and

commercial premises.

Installation of DV/DH direct gas

fired air heaters

Note  Only a competent person shall be

allowed to install a DH heater.
DV/DH gas fired air heaters are 

manufactured in two configurations, DV

as a vertical unit and DH as a horizontal

unit, both types are suitable for internal

and external installation only.

DV Vertical indoor configuration

The heater should be positioned onto a

prepared flat level concrete base, or a

support steel work frame, with a

minimum 500mm clearance on the non-

access sides, and 1000 clearance on

the access sides.
The unit should be lifted into position

from it’s base using a suitably sized fork

lift truck with the fresh air inlet facing the

outside wall.
The fresh air inlet weather louvre, cowl

etc should be sized at a maximum inlet 

velocity of 2.5m3/sec to prevent water 

carryover into the heater, with the duct

work tapering to suit the heater fresh air

inlet connection.
For heaters with extended ductwork.

The ductwork should be sized to ensure

that the external static pressure (ESP)

does not exceed the figure stated on the

data badge.

DH Horizontal indoor configuration

The heater is supplied as a single 

fan/burner section.  It is usual for 

horizontal units to be mounted above

floor level, due to the amount of floor

space they would take up, and are

normally positioned onto the roofs of

internal offices/mezzanine areas or into

the building steelwork.
For heaters being installed onto the roof

of offices etc, the roof must be adequate

to take the weight of the heater, and be 

adjacent to an outside wall, to allow

fresh air to be ducted to the heater.  A

1000mm clearance would be required

on the access side of the heater, and a

minimum 500mm clearance required on

the non-access side and top of the

heater.
For heaters mounted in the roof steel

work, the units can be supported via 6

M12 drop rods through the support

channels situated on the base of the

unit.
The fresh air to the heater should be 

ducted through the roof, with a fresh air

inlet sized to achieve inlet velocities of

2.5m/sec.  Supply ductwork should be

sized to suit the flange connection on

the distribution head, or for extended

ductwork runs, sized to ensure that the

external  static resistance does not

exceed that stated on the Data Badge.
The fan/burner section should be lifted

into position with a suitably sized fork lift

truck, under the base of the heater or

via a crane using straps and spreader

bars

.

DV - Vertical outdoor configuration 

The heater is identical to the indoor 

configuration except for a control 

Installation instructions

cubicle fitted over the electrical 

components, and an inlet cowl fitted to

the fresh air inlet. 

The heater is supplied as a single

section, overall sizes and weights as

indicated on the arrangement drawing.

The heater should be positioned onto

a prepared flat level concrete base or 

support steelwork frame, with a 50mm

clearance from the building wall, and a

clearance on the access and control

panel side as indicated in the 

arrangement drawing.

The heater should be lifted into

position with the fresh air inlet cowl

adjacent to the building wall, using a

suitably sized fork lift truck, with the

forks positioned under the base of the

water. or via a crane with lifting straps

slung under the base of the unit and

spreader bars between the straps at

the top of the heater to prevent the

straps from exerting any undue strain

onto the heater frame.

The external ductwork from the heater

into the building must be weatherproof

and form a water tight seal to the top

of the flange of the heater. All

ductwork should be sized to ensure

that the  external static resistance

(ESP) does not exceed the figure

stated on the data badge.

DH - Horizontal Outdoor

Configuration.

The heater is identical to the indoor 

configuration except for a control

cubicle fitted over the electrical

components, and an inlet cowl fitted to

the fresh air inlet. The heater is

supplied as a single section, overall

sizes and weights as indicated on the

arrangement drawing.

The heater should be positioned onto

a flat level concrete base, or support 

steelwork frame, to give a 500mm 

clearance to the underside of the

heater from floor level, 500mm

clearance on the non access side and

a clearance on the access side as

indicated in the arrangement drawing.

The heater should be lifted into

position, using a suitable sized fork lift

Содержание DH2 150

Страница 1: ...DIRECT FIRED DV DH DIRECT GAS FIRED MAKE UP AIR UNITS Installation Commissioning Service Manual Ambi Tec Ambi Stat...

Страница 2: ...d be required on the access side of the heater and a minimum 500mm clearance required on the non access side and top of the heater For heaters mounted in the roof steel work the units can be supported...

Страница 3: ...Internal wiring The amount of interconnecting wiring will depend on the control system being used this will be indicated on the schematic wiring diagram with the minimum connections Ambitec controlle...

Страница 4: ...Louvre 4 OFF 20mm electrical connection points H BSP gas inlet connection B B C Discharge opening C Discharge 50 50 50 500 50 50 50 500 DH2 75 1 2 BSP Weather proofed hood fitted to external units on...

Страница 5: ...SP 1400 856 DH2 75 1 2 BSP Weather proofed hood fitted to external units only ACCESS SIDE VIEW VIEW ON DISCHARGE OUTLET VIEW ON FRESH AIR INLET A Electrical control panel B N Optional extra discharge...

Страница 6: ...set point say 19 C adjustable the heater discharge air temperature is controlled at a constant 40 C by means of a active duct sensor modulating the gas throughput control valve At 1 C above room set...

Страница 7: ...and main electrical supply Gas installation pipework has been tested for soundness Gas installation has been purged Note and record fan motor data badge details Note and record fan and motor pulley si...

Страница 8: ...le and with a pair of grips on the valve spindle minutely close to the valve in small stages until the 5 C temperature rise is obtained With great care tighten the U clamp onto the valve spindle ensur...

Страница 9: ...on pipework has been tested for soundness Gas installation has been purged Note and record fan motor data badge details Note and record fan and motor pulley sizes belt reference and pulley centres Fan...

Страница 10: ...t increase the burner pressure at high fire then the gas control valve requires resetting Connect a separate manometer to pressure tapping point P5 and P9 measure the pressure The differential gas pre...

Страница 11: ...out condition Remove the air sensing tube from the bottom connection of the air pressure switch The heater will lockout Replace and reset Adjust overheat controller set point down until heater shuts o...

Страница 12: ...LATE DRIVE FREE PROFILE DAMPER SLIDE RAILS GREASE PROFILE DAMPER LIMIT SWITCH OPERATION PROFILE DAMPER DRIVE LINKAGE PROFILE DAMPER DRIVE MOTOR DRIVE BELT CONDITION BURNER GAS PORTS RE DRILL BURNER MI...

Страница 13: ...PLATE DRIVE FREE PROFILE DAMPER SLIDE RAILS GREASE PROFILE DAMPER LIMIT SWITCH OPERATION PROFILE DAMPER DRIVE LINKAGE PROFILE DAMPER DRIVE MOTOR DRIVE BELT CONDITION BURNER GAS PORTS RE DRILL BURNER M...

Страница 14: ...ELT CENTRES ALIGNMENT TENSION PROFILE OPENING VELOCITY BURNER SIZE CURRENT L1 L2 L3 OVERLOAD SIZE GAS LINE SUCTION LOW FIRE HIGH FIRE DIFF GOVERNOR INLET PRESS GOVERNOR OUTLET PRESS PILOT PRESSURE AIR...

Страница 15: ...TS BELT CENTRES ALIGNMENT TENSION PROFILE OPENING VELOCITY BURNER SIZE CURRENT L1 L2 L3 OVERLOAD SIZE GAS LINE SUCTION LOW FIRE HIGH FIRE DIFF GOVERNOR INLET PRESS GOVERNOR OUTLET PRESS PILOT PRESSURE...

Страница 16: ...Layout of electrical equipment DV heater Layout of electrical equipment DH heater...

Страница 17: ...rmer V5 Motorised Ball Valve M1 Modulating Control Valve Motor V6 Burner Isolating Valve P4 Air Pressure Switch V7 Pilot Gas Isolating valve T1 Room Sensor V8 Pilot Governor T2 Duct Sensor V9 V10 Pilo...

Страница 18: ...ssure test point P1 and P3 to pressurise the assembly between the two safety shut off valves Connect pressure gauge to pressure test point P4 10 Open V1 any rise in pressure indicates the downstream s...

Страница 19: ...10 x 50 LG HEX Head Set Screw 5 M5 x 12 HEX Head Set Screw 6 M10 Nut and Washer 7 Support Bracket Gasket N0010 8 M5 x 40 HEX Head Set Screw 9 M5 nut and Washer 10 Stainless Steel Mixing Plate N0006 11...

Страница 20: ...he black section normally takes 1 min 28 seconds for the MMI 810 1 Note References to terminal numbers in this section relate to those in the Satronic burner controller sub base and do not correspond...

Страница 21: ...rminal 5 or terminal C If solenoid coils fitted with rectifier the negative side must be connected to terminal 5 or C Flame sensing probe earthing Reposition or replace flame sensing probe Lockout dur...

Страница 22: ...me failure due to loss of gas supply Investigate the cause of gas supply failure Flame failure due to an unstable flame Check the flame signal during the switching from high to low to hire fire Adjust...

Страница 23: ...d Hazel Grove STOCKPORT Cheshire SK7 4LD Tel 0161 482 7900 Fax 0161 482 7901 Description Part No Spark Probe N1014 Flame Probe IEG 18 6 N1007 Satronic MMI810 N1018 4 Pole Miniature Relays N1244 N1260...

Страница 24: ...programming and this should be carried out by a Nordair Niche Engineer Modulating gas valve control unit Isolate electric supply unbolt motor clamp from valve spindle and remove motor from motor mount...

Страница 25: ......

Страница 26: ...n Nortek Global HVAC reserves the right to change product speci cation without due notice NORTEK GLOBAL HVAC UK LTD Fens Pool Avenue Brierley Hill West Midlands DY5 1QA United Kingdom Tel 01384 489 25...

Отзывы: