6 Operating status messages
BU 0240 en-US-4920
79
Pos: 655 /Anleitungen/El ektr onik/FU und Starter/6. M eldung en zum Betriebszustand/Mel dungen @ 3\m od_1361803071259_14638.docx @ 59852 @ 2 @ 1
6.3 Messages
Pos: 656 /Anleitungen/El ektr onik/FU und Starter/6. M eldung en zum Betriebszustand/Störm eldung en (Tabell enüberschrift) @ 3\m od_1361803456862_14638.docx @ 59894 @ 5 @ 1
Error messages
Display in the
Simple Box/Control Box Fault
Text in the Parameter Box
Cause
• Remedy
Group
Details in
P700 [-01] /
P701
Pos: 657 /Anleitungen/El ektr onik/FU und Starter/6. M eldung en zum Betriebszustand/Störm eldung en (Auflistung)/F ehl er E001 [SK 180E/SK 2xxE/SK 5xxE/SK2xxE-FD S/SK 500P] @ 2\m od_1347452921592_14638.docx @ 46428 @ @ 1
E001
1.0
Overtemp.
inverter
"Inverter overtemperature"
(inverter heat sink)
Temperature monitoring of the inverter
Measuring results lie outside the permissible temperature
range, that is, the error is triggered when falling short of the
permissible lower temperature limit or when exceeding the
permissible upper temperature limit.
• Depending on cause: Reduce or increase ambient
temperature
• Check device fan/cabinet ventilation
• Check the device for dirt
1.1
Overtemp. VFD internal
"Internal VFD overtemperature"
(internal area of the variable
frequency drive)
Pos: 658 /Anleitungen/El ektr onik/FU und Starter/6. M eldung en zum Betriebszustand/Störm eldung en (Auflistung)/F ehl er E002 [SK 180E/SK 2xxE/SK 5xxE/SK2xxE-FD S] @ 2\m od_1347453302152_14638.docx @ 46452 @ @ 1
E002
2.0
Overtemp. Motor PTC
"Overtemperature motor PTC"
Motor temperature sensor (PTC thermistor) has triggered
• Reduce motor load
• Increase motor speed
• Use external motor fan
2.1
Overtemp. I²t motor
"Overtemperature I²t motor"
Only if I
2
t motor (P535) is
programmed.
I
2
t motor has triggered (calculated overtemperature of
motor)
• Reduce motor load
• Increase motor speed
2.2
Overtemp. ext. brak. res.
"Overtemperature of external
braking resistor"
Overtemperature via digital
input (P420 […])={13}
Temperature monitor (e.g. braking resistor) has activated
• Digital input is low
• Check connection, temperature sensor
Pos: 659 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uch kompakt --------- @ 13\m od_1476369695906_0.docx @ 2265496 @ @ 1
Содержание NORDAC FLEX SK 205E Series
Страница 1: ...BU 0240 en US NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters...
Страница 4: ...NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters 4 BU 0240 en US 4920...
Страница 29: ...2 Mounting and installation BU 0240 en US 4920 29 Installation Size 1 3 Size 4...
Страница 97: ...Key word index BU 0240 en US 4920 97...
Страница 98: ...NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters 98 BU 0240 en US 4920...
Страница 99: ...Key word index BU 0240 en US 4920 99...
Страница 100: ...6072403 4920...