4 Commissioning
BU 0240 en-US-4920
55
For the correct operation of the drive unit, it is necessary to input the motor data from the nameplate
as precisely as possible. In particular, an automatic stator resistance measurement using parameter
P220
is recommended.
Pos: 225 /Anleitungen/El ektr onik/FU und Starter/4. Inbetriebnahm e/SK 1xxE, SK 2xxE, -FD S/W erksei nstellungen/W erksei nstellungen_02_IE2_3 @ 30\m od_1552397134005_14638.docx @ 2506307 @ @ 1
Motor data for IE2 / IE3 motors are provided via the
NORDCON
software. The required data record
can be selected and imported into the variable frequency drive with the aid of the "Import motor
parameter" function (also refer to the manual for the
NORDCON
software
Pos: 226 /Anleitungen/El ektr onik/FU und Starter/1. Allgemei nes/Sicherheits- und Install ationshinw eise und W arn- Gefahrenhinw eise/neu/War n- und Gefahrenhinw eise/Informati on - Doppel bel egung DIN 2 und DIN 3 [SK 2xxE] @ 19\mod_1511860681545_14638.docx @ 2373600 @ @ 1
Information
DIN 2 and DIN 3 double allocation
Digital inputs DIN2 and DIN3 are used for 2 different functions:
1. for digital functions that can be parameterized (e.g. “enable left”),
2. for evaluation of an incremental encoder.
Both functions are coupled by an OR link.
Evaluation of an incremental encoder is always activated. This means that when an incremental encoder is
connected, make sure that the digital functions are switched off (parameter (P420 [-02] and [-03]) or with DIP
switch (please see chapter 4.2.2.2 "DIP switches (S1)" on page 58)).
Pos: 227 /Anleitungen/El ektr onik/FU und Starter/1. Allgemei nes/Sicherheits- und Install ationshinw eise und W arn- Gefahrenhinw eise/neu/War n- und Gefahrenhinw eise/Informati on - Vorrang DIP - Schalter [SK 2xxE] @ 19\m od_1511862534906_14638.docx @ 2373682 @ @ 1
Information
DIP switch priority
Please note that DIP switch settings on the variable frequency drive (
S1
) have priority over parameter settings.
The settings of integrated potentiometers
P1
and
P2
must also be taken into consideration.
Pos: 229 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uch kompakt --------- @ 13\m od_1476369695906_0.docx @ 2265496 @ @ 1
Содержание NORDAC FLEX SK 205E Series
Страница 1: ...BU 0240 en US NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters...
Страница 4: ...NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters 4 BU 0240 en US 4920...
Страница 29: ...2 Mounting and installation BU 0240 en US 4920 29 Installation Size 1 3 Size 4...
Страница 97: ...Key word index BU 0240 en US 4920 97...
Страница 98: ...NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters 98 BU 0240 en US 4920...
Страница 99: ...Key word index BU 0240 en US 4920 99...
Страница 100: ...6072403 4920...