2.4.1 Operation in potentially explosive environments - ATEX zone 22 3D
Pos: 175.9 /Anleitungen/El ektr onik/FU und Starter/2. M ontage und Installation/ATEX und EAC EX ( SK 1xxE, SK 200E)/Betrieb i n explosi onsgefähr deter Umg ebung - AT EX Zone 22 3D _02 [SK 1xxE / SK 2xxE] @ 22\mod_1528895961505_14638.docx @ 2426795 @ @ 1
All of the conditions which must be observed for operation of the device in an explosion hazard
environment (ATEX) are summarized below.
Pos: 175.10 /Anl eitungen/Elektronik/FU und Starter/2. Montage und Installati on/AT EX und EAC EX (SK 1xxE, SK 200E)/M odi fizier ung des Gerätes zur Ei nhaltung der Kategorie 3D - ATEX_01 [SK 1xxE / SK 2xxE] @ 58\m od_1605709415641_14638.docx @ 2693384 @ 4 @ 1
2.4.1.1 Modification of the device for compliance with category 3D
Only a specially modified device is permissible for operation in ATEX zone 22. This adaptation is only
made at the NORD factory. In order to use the device in ATEX zone 22, the diagnostic caps are
replaced with anodized oil inspection glasses, among other things.
( 1 ) Year of manufacture
( 2 ) Labelling of the device (ATEX)
IP55:
II 3D Ex tc IIIB T125°C Dc X
IP66:
II 3D Ex tc IIIC T125°C Dc X
Allocation:
• Protection with "housing"
• Procedure "A" zone "22" category 3D
• IP55/IP66 rating (according to the device)
IP66 is required for conductive dust
• Maximum surface temperature 125°C
• Ambient temperature -20°C to +40°C
Information
Possible damage caused by mechanical overload
Devices in series SK 2xxE and the permitted options are only designed for a degree of mechanical
stress that corresponds to a low impact energy of 4J.
Higher loads will lead to damage to or in the device.
Pos: 175.11 /Anl eitungen/Elektronik/FU und Starter/2. Montage und Installati on/AT EX und EAC EX (SK 1xxE, SK 200E)/M odi fizier ung des Gerätes zur Ei nhaltung der Kategorie 3D - ATEX_02 [SK 2xxE] @ 19\m od_1505901677263_14638.docx @ 2365560 @ @ 1
The components needed for the modification are contained in an appropriately modified variable
frequency drive connection unit (SK TI4-…-EX).
Pos: 175.12 /Allgemei n/Allgemei ngültige M odul e/---------Seitenum bruch kom pakt --------- @ 13\m od_1476369695906_0.docx @ 2265496 @ @ 1
Содержание NORDAC FLEX SK 205E Series
Страница 1: ...BU 0240 en US NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters...
Страница 4: ...NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters 4 BU 0240 en US 4920...
Страница 29: ...2 Mounting and installation BU 0240 en US 4920 29 Installation Size 1 3 Size 4...
Страница 97: ...Key word index BU 0240 en US 4920 97...
Страница 98: ...NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters 98 BU 0240 en US 4920...
Страница 99: ...Key word index BU 0240 en US 4920 99...
Страница 100: ...6072403 4920...