NORDAC FLEX (SK 200E ... SK 235E) – Brief instructions for Frequency Inverters
36
BU 0240 en-US-4920
Information
Reaction time of digital inputs
The reaction time of a digital signal is approx. 4-5 ms and consists of the following:
Scan time
1 ms
Signal stability check
3 ms
Internal processing
< 1 ms
For digital inputs DIN2 and DIN3 there is a parallel channel which relays the signal pulses between 250 Hz and
205 kHz directly to the processor, and therefore makes it possible for a rotary encoder to be evaluated.
Pos: 161 /Anleitungen/El ektr onik/FU und Starter/1. Allgemei nes/Sicherheits- und Install ationshinw eise und W arn- Gefahrenhinw eise/neu/War n- und Gefahrenhinw eise/Informati on - Kabelführung @ 29\m od_1552045826996_14638.docx @ 2502097 @ @ 1
Information
Cable routing
All control cables (including PTC thermistors) must be routed separately from power and motor cables
to prevent interference in the device.
If the cables are routed in parallel, keep a minimum distance of 20 cm from cables which carry a
voltage of > 60 V. The minimum distance may be reduced by shielding live cables or by using
grounded metal separator within the cable ducts.
Alternatively: Use of a hybrid cable with shielded control lines.
Pos: 162 /Allgem ein/Allgem eingültig e Module/---------Seitenumbr uch kompakt --------- @ 13\m od_1476369695906_0.docx @ 2265496 @ @ 1
Содержание NORDAC FLEX SK 205E Series
Страница 1: ...BU 0240 en US NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters...
Страница 4: ...NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters 4 BU 0240 en US 4920...
Страница 29: ...2 Mounting and installation BU 0240 en US 4920 29 Installation Size 1 3 Size 4...
Страница 97: ...Key word index BU 0240 en US 4920 97...
Страница 98: ...NORDAC FLEX SK 200E SK 235E Brief instructions for Frequency Inverters 98 BU 0240 en US 4920...
Страница 99: ...Key word index BU 0240 en US 4920 99...
Страница 100: ...6072403 4920...