30
6.3.2
Setting Up Hydraulic Valves
There are two key settings for each valve direction (for example, the left up
direction). These settings are valve DeadZone, "
DZ
", and valve GAIN,
"
KP
".
The DeadZone ("
DZ
") setting represents the size of electrical signal required
at the solenoid valve to cause a boom speed of one inch per second.
The GAIN ("
KP
") setting is inversely related to the maximum speed of the
boom. That is, the faster the boom the lower the GAIN setting.
The left channel is described in
Table 5
. For the other channels the basic
structure and behavior is the same.
Table 5 – Left Channel SETUP Menus
Navigating past the end of the menu will return the panel to the Setup…”More” Menu
Left On
Informs you that the left valve channel is ON. To change the status to OFF,
use the "
+/-
" switch (
Section 6.3.5
).
↑
DZ- 100
Informs you that the left up DeadZone setting is 100. To adjust the reading
use the "
+/-
" switch.
↑
KP- 53
Informs you that the left up GAIN setting is 53. To adjust the reading use
the "
+/-
" switch.
↓
DZ- 100
Informs you that the left down DeadZone setting is 100. To adjust the
reading use the "
+/-
" switch.
↓
KP- 42
Informs you that the left down GAIN setting is 42. To adjust the reading
use the "
+/-
" switch.
Navigating past the end of the menu will return the panel to the Setup…”More” Menu
These settings will be determined during the Automatic System Setup
(
Section 6.1
) and "
ReTune?
" (
Section 6.2
) sequences automatically.
However, it is possible to check and adjust these settings manually as
described below.