background image

digital converter. The factory-adjusted 
calibration values are used to convert the 
result to an accurate mA or V reading. This 
unprocessed reading can be seen in the 
monitor menu, item Mea.
If the digital lowpass filter is enabled, the 
reading is processed with it. Likewise if the 
Hold function is active, the reading is locked.
The reading is scaled using up to ten user-
entered scaling points Mea/Sca to a scaled 
(engineering) reading. If the tare function is 
active, the current tare value is subtracted. 
The current value is copied to the tare value 
memory when a switch programmed as a 

tare switch is activated. The tare value is 
stored in an EEPROM memory and is 
retained even if the power supply is cut off.
The last element in the chain is Dead zone. 
It allows rounding very small readings to 
zero, to get a empty weigh to indicate zero 
reading despite of a small tare error.
The reading processed this way is 
observable in the monitor menu item Sca, 
and it is also stored to the channel table to 
be used on the display and analog and serial
outputs and alarms. The card in slot A stores
the reading to channel 1 and card in slot B to
channel 2.

Configuration menu

In/Setup/Range

Defines the physical input signal type.  
Contains predefined ranges 0-20mA, 4-
20mA, 0-5V, and 0-10V, and free scaling 
ranges mA, V, and Pot (=potentiometer).

Predefined ranges

When using one of the predefined ranges 0-
20mA, 4-20mA, 0-5V, or 0-10V, the scaling 
to engineering units is done by giving the 
scaled endpoints in menu items Lo and Hi. 
When the input signal is at the low end of the
range, the scaled (displayed) reading 
corresponds to Lo setting.

Free scaling

When using free scaling ranges mA, V, or 
Pot, the In/Setup/Pts setting defines how 
many scaling points are desired. It can be 
adjusted from 0 to 10.

If 0 points is selected, the reading is not 
scaled at all, but milliamps or volts are 
displayed as are. A potentiometer will give 
unscaled readings 0 to 100.
Two point scaling is achieved by setting Pts 
to 2. Settings Mea1, Sca1, Mea2, and Sca2 
will appear in the menu. Mea1 and Sca1 
form a pair: when the physical input signal 
corresponds to Mea1, the scaled 
(engineering) reading will be Sca1. The 
same applies for the other pair, and linear 
interpolation and extrapolation is used 
elsewhere.
An example how to scale 4-20mA signal to 
be displayed 0-100::
Pts=2
Mea1 = 4 (mA)
Sca1 = 0 (scaled)
Mea2 = 20 (mA)
Sca2 = 100 (scaled)
A non-linear behaviour is obtained by using 
more than two points. The points can be 

18

Master

Slot A

Slot B

Slot C

Setup

Filter

*+^

>

^
v

^
v

Range

Lo

Hi

MeaMin

Dec

Lopass

Disable

Dead

Hold

More

Tare

Pts

Mea1

Sca1

Mea2

Sca2

Act

Value

Visible when Range 
is 0-20mA, 4-20mA, 
0-5V, or 0-10V.

Visible, when 
Range is mA, V, or 
Pot.

^
v

>

In

>

Содержание 1000F-2012

Страница 1: ...2012 2800 2012 910E 920E 2012 1000F 2012 1100F 2012 1800F 2012 For process inputs User manual 1 12 2014 Firmware V1 5...

Страница 2: ...is possible to calculate a simple mathematical operation among the channels About this manual The next page shows a quick look at the connectors Every series small large panel field has a chapter of i...

Страница 3: ...24V 9 8 7 230VAC PE L N 910E 920E 2012 large panel meter Conf Slot A Slot B Slot C Supply voltage 2 3 4 1 PE 1000F 1100F 1800F 2012 large field meter See installation chapter on page 11 Cards 6 5 4 3...

Страница 4: ...ible when the meter is not installed in a panel Pull the front bezel on the middle To open from the rear end unscrew the four screws The base card with other cards can be withdrawn after opening the c...

Страница 5: ...rs of the card types Configuration The panel meter can be configured with many ways By using the front panel display and buttons Using the buttons is described in chapter User interface Via the RS 232...

Страница 6: ...nclosure Power supply In the 24VDC model the power supply is connected in the base card terminals 7 and 9 The polarity does not matter The connector is green In the 230VAC model the Live is connected...

Страница 7: ...232 or RS 485 bus Available only if the device is equipped with a serial communications card Use the free Mekuwin software Via the POL connector on the input card in slot A Available only if the devi...

Страница 8: ...57 100 100 W4 291 408 498 H4 100 153 153 The opening dimensions are given for a tolerance of 2 1 mm Connections First detach the lid of the connector room on the backside of the unit It can be recogn...

Страница 9: ...ack panel display and buttons Using the buttons is described in chapter User interface Via the RS 232 or RS 485 bus Available only if the device is equipped with a serial communications card Use the f...

Страница 10: ...side of the rightmost digit Now the display assembly may be turned away on its hinges Connections There is two PG11 cable glands on the lower wall of the enclosure allowing the cables to be brought i...

Страница 11: ...a Faston crimping tool is needed A pre fuse is not necessary but if one is used it should be at least 500mAT The power and signal wires must be fastened using cable ties or equivalent so that if one...

Страница 12: ...RS 485 bus Available only if the device is equipped with a serial communications card Use the free Mekuwin software Via the POL connector on the input card in slot A Available only if the device is N...

Страница 13: ...d Scan2 Scan5 Like Scan but slower Indicator LEDs A1 A4 indicate the state of the alarms on the optional relay card A1 and A2 follow the alarms on slot C A3 and A4 follow the alarms on slot B If the C...

Страница 14: ...g the button shows the value of the setting and allows editing it Most data types are edited simply with v buttons and exited with Floating point numbers are edited using the buttons v Select the digi...

Страница 15: ...ons are described above in section Normal state and the indicator LEDs Gen Ch The channel to be displayed in the Single mode The channels are 1 slot A reading 2 slot B reading 7 math channel Gen Brigh...

Страница 16: ...m2 Div Division From1 From2 Dividing by zero will give an undefined result Min Lesser of the two From1 or From2 Max greater of the two Sqrt Square root from the channel selected with From1 A negative...

Страница 17: ...5 V excitation The lower end is connected in 3 The wiper is connected in terminal 4 If using two 2012 IN cards please note that they share the common ground terminals 3 are internally together An exte...

Страница 18: ...0 20mA 4 20mA 0 5V and 0 10V and free scaling ranges mA V and Pot potentiometer Predefined ranges When using one of the predefined ranges 0 20mA 4 20mA 0 5V or 0 10V the scaling to engineering units i...

Страница 19: ...works as a bypass switch ExtSw An external contact connected in slot A works as a bypass switch Both Both of the above switches work When the selected switch is activated the lowpass filter is switch...

Страница 20: ...anged manually This way the operation of the scaling analog outputs alarms etc may be tested with no need to feed in different physical signals The normal operation is restored with a Free command Sca...

Страница 21: ...If the channel is indicating fault the input signal is below MeaMin the analog output is steered to exceed the range by 20 or its electrical maximum 22mA or 11V Configuration menu Out Range Output si...

Страница 22: ...ceed the range between Out1 Out2 by 20 the output will be Out1 1 2 Out2 Out1 however it can t go above 22 mA or 11 V Monitor menu Out The analog output in mA or V The analog signal will be electricall...

Страница 23: ...6 is commonly called D1 A or B Correspondingly the negative line at terminal 5 is called D0 B or A The common wire is connected in terminal 4 The shield of the cable should be earthed at one point on...

Страница 24: ...otation marks MEA CH 1 Returns channel 1 reading The channels are 1 slot A input 2 slot B input 7 math channel The response may consist of characters 0 9 minus sign and a decimal point If the reading...

Страница 25: ...enu There are two or three identical submenus corresponding to two or three relays Type Off Alarm disabled Lo Alarm will activate when the reading goes below Level and deactivate when goes above Level...

Страница 26: ...alarm is reset with an external contact connected in slot A Both The alarm may be reset by both ways The alarm can not be reset before the condition causing the alarm has been removed NC Reverse opera...

Страница 27: ...that is more than 120 VDC or 50 VAC with respect to ground mA input Resistance Approx 80 ohm Range 0 24 mA or wider Calibr accuracy 8 A Non linearity 3 A Thermal drift 100 ppm C V input Resistance 1...

Страница 28: ...200 ms max Alarm relays 2000 REL2 3 Relays 2000REL2 2 pcs 2000REL3 3 pcs Alarms 1 per relay Contacts 250 VAC 2 A resistive load Snubber An external one must be used when driving heavily inductive loa...

Страница 29: ...ply voltage 230VAC model 85 260 VAC or VDC Cat II 24VDC model 20 32 VDC Power Max 17 W Protection class 1 protective earth Environment Temperature 35 50 C IP class IP65 Large field meter 1100F 2012 Su...

Отзывы: