Supply voltage
The power supply is connected in a three-pole connector, that has terminals
numbered 7, 8, and 9. The supply is brought to terminals 7 and 9. The polarity does
not matter. The 24VDC model has green connector block, while the 230VAC model
has a grey one.
The 230VAC model is built with a reinforced insulation, so a protective earth connection is not
needed.
The meter has internal pre-fuse. If an external is used, it should be at least 2AT for 24VDC
model and 500mAT for 230VAC model.
Other cards
See the chapters of the card types.
Configuration
The panel meter can be configured with many ways:
•
By using the front panel display and buttons. Using the buttons is described in chapter User
interface.
•
Via the RS-232 or RS-485 bus. Available only, if the device is equipped with a serial
communications card. Use the free Mekuwin software.
•
Via the POL connector on the input card in slot A. Available only, if the device is NOT
equipped with a serial communications card. Suitable programming cables include POL-
RS232 (for RS-232 port of a PC) and DCS772 (for USB port). Additionally an adapter POL-
3PIN is needed. Use the free Mekuwin software. Caution: Do not operate the 230VAC model
with no enclosure to avoid an electrick shock!
5
9
8
7
+L
-N