![Nokeval 1000F-2012 Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/nokeval/1000f-2012/1000f-2012_user-manual_1699177024.webp)
not known – however there must not be
other devices on the bus when using this.
Monitor menu
Count
Will be increased by one every time a valid
serial bus command is processed. Will roll
over to 0 after 255.
SCL protocol
A more detailed document of the Nokeval
SCL protocol is available on Nokeval WWW
pages.
This device accepts the following SCL
commands:
TYPE ?
Returns the type and firmware version: ”2012
V1.5” without the quotation marks.
MEA CH 1 ?
Returns channel 1 reading. The channels
are:
•
1 = slot A input
•
2 = slot B input
•
7 = math channel
The response may consist of characters 0…
9, minus sign and a decimal point.
If the reading is invalid (e.g. the input signal
is below MeaMin), consequent dashes are
returned "------".
MEA SCAN 1 3
Returns the readings from channels 1 to 2
separated by a space. E.g. “101.000
0.00000 79800.”.
MN xxxxx
Configuration commands used by Mekuwin
software.
CARDID slot type
Card type programming. Only for factory use.
Slot: A=1, B=2, C=3.
Card types: 2012-IN=33, 2000-OUT=16,
2000-RS=17, 2000-REL2=48, 2000-
REL3=49.
CARDID slot ?
Card type query.
24