Back panel
1KVA
2KVA
3KVA
No.
Meaning
1
EPO input for emergency shutdown. When the circuit is closed, the UPS immediately stops powering
all output outlets, emits a continuous whistle, the word ALARM starts flashing and Fault LED Fault
turns red. Error code 07 appears.
To exit the generated state, turn the device off.
2
USB port for PC connection. The supplied UPSilon2000 software must be installed on the PC (Windows
environment). The USB port is used in read-only mode.
3
Serial port RS232 for PC connection. This port must only be used for advanced UPS settings. Please
read
Advanced Settings via RS232.
4
Cooling fan. Never obstruct this fan, the device could overheat because of limited air circulation.
5
External battery bank outlet. Available for 17NXGCON11001/17NXGCON12001 models only. Single
code 17NXBAON11001 (17NXBAON12001) allows you to add extra 4/8 (6/12) 7Ah batteries and to
double/triple the autonomy. Up to 2 17NXBAON11001 (17NXBAON12001) can be added to extend
maximum autonomy 5 times that of the one provided by the UPS alone.
6
Expansion slot for additional card (SNMP). Use 17NXGCSN00001 code.
7
Power outlet for connection to 220V/50Hz mains.
8
AC Input Breaker.
9
Output Breaker. Only available for model 17NXGCON12001.
10/11 Output outlets. 2 programmable output outlets are only provided for model 17NXGCON12001.