Appendix [Technical Features]:
Model
17NXGCON38001
17NXGCON11001
17NXGCON12001
EAN
8059616333608
8059616333615
8059616333622
Name
UPS Online Pro 1000
UPS Online Pro 2000
UPS Online Pro 3000
Power Rating(W) Vin=210-265
900
1800
2700
Power Rating (VA)
1000
2000
3000
Input
Voltage
170-276V
Frequency
50Hz±5%
Output
Voltage
200/208/220/230/240±1%
Frequency
±1Hz or ±3Hz (Selectable)
Harmonic
Distortion
<3% @ 100% Linear Load
<7% @ 100% NON Linear Load
Waveform
Pure SineWave
Crest Factor
3:1
Transfer
Time
AC->DC
0 ms (True Online Topology)
Inverter -> Bypass
4 ms
Overload
Line Mode
(Vin=210-265)
<105%
106% - 120% for 30s then bypass
121% - 150% for 10s then bypass
>150% immediately bypass
Buzzer
Battery
<105%
106% - 120% for 30s then shuts down
121% - 150% for 10s then shuts down
>150% immediately shuts down
Buzzer
Bypass
<105%
106% - 120% for 250s then shuts down
121% - 130% for 125s then shuts down
131% - 135% for 50s then shuts down
136% - 145% for 20s then shuts down
146% - 188% for seconds then shuts down
>188% immediately shuts down
Buzzer
Battery
Voltage
24VDC
48VDC
72VDC
Quantity
2
4
6
Type
12V@7Ah , Sealed Maintenance Free Lead Acid VRLA Type
Backup Time min
(50%, 70%, 100%)
6, 3, 1
6, 3, 1
6, 3, 1
Charge Current
1,5A
1A
1A
Charging Time
4 hours to (90%)
Efficiency
Line Mode
Up to 90%
Up to 91%
Up to 92%
ECO Mode
Up to 96%
Up to 96%
Up to 96%
Battery Mode
Up to 85%
Up to 85%
Up to 86%
LCD Display
4 LED [Utility Normal, Backup, Fault, Battery Fault]
LCD [ECO, Normal, Battery, Overload, Alarm, Service, Bypass,
Programmable Outlet 1/2, Self-Test, Load/Battery/Vin/Vout/Fin/Fout
level, Error, Status]
Diagnostics
Power ON, Front Panel (Select), SW, 24hrs (routine check)
Protection
In Normal Mode/Battery Short Circuit (LOAD) Electronic Circuit or output
Circuit breaker
In bypass Mode input Circuit breaker
Spike Suppression meets EN61000-4-5
Battery Over-drain Two stages: Controlled Battery Low Warning & Cut
Off
Battery Overcharge
Over temperature [Normal mode -> Bypass, Battery mode -> UPS shuts
down]
Overload AC Buzzer continuously alarms
Function
Normal / ECO / CF60Hz / CF50Hz, Cold Start
ALARM
Battery Mode, Low Battery, Overload, Fault
Input Connections
1xIEC (10A, IEC 320-C14)
1xIEC(16A, IEC 320-C20)