17
MECHANICAL INSTALLATION
POWERDRIVE MD2R Installation guide
4948 - 2017.11 / d
en
2.7 - Weight
The values indicated in the table below are maximum net
weights.
Rating
Maximum weight (kg)
60T and 75T
350
100T to 150T
400
180T to 270T
900
340T to 570T
1500
600T to 1100T
2800
1400T to 1700T
Please Consult Leroy-Somer
270TH to 500TH
1500
600TH to 900 TH
2500
1200TH and 1500 TH
Please Consult Leroy-Somer
2.8 - Drive losses
Rating
Maximum thermal dissipation
(kW)
60T
2.5
75T
3.2
100T
3.8
120T
4.6
150T
5.5
180T
7
220T
8.6
270T
10.4
340T
12.8
400T
14.2
470T
17.8
570T
19.8
600T
23.1
750T
26.9
900T
32.3
1100T
36.2
1400T
48.5
1700T
54.2
270TH
11.4
340TH
13.8
400TH
17.3
500TH
20.7
600TH
26.6
750TH
31.7
900TH
38.1
1200TH
48.6
1500TH
55.2
2.9 - Drive ventilation flow rates and
noise levels
Rating
Forced
ventilation
flow rates
(m
3
/hr)
Noise level
with IP21
(dBA)
60T and 75T
600
78
100T to 150T
1200
78
180T to 270T
1800
80
340T to 570T
2500
80
600T to 1100T
5000
83
1400T to 1700T
7500
85
270TH to 500TH
2500
80
600TH to 900TH
5000
83
1200TH to 1500TH
7500
85
Air can exit on all sides of the roof. The cabinet can be installed
with one side only against a wall. Under no circumstance must
the difference between the internal temperature of the cabinet
and the ambient temperature outside the cabinet exceed 5°C.
In atmospheres where condensation may form, install a
heating system (to be switch off when the drive is operating).
It is advisable ton control the heating system automatically.
Air outlets
Air inlets