Digitax HD M75X Series Installation and Technical Guide
Issue Number: 5
5.2.2 DC paralleling with cables
DC supply cables up to 6 mm
2
(AWG 10) can be connected directly to the DC terminals with a suitably insulated M4 ring crimp. The DC terminal
cover breakout tab (
1
) only needs to be removed when a DC drive supply is made with cable connections. DC terminal cover breakout tabs do not
need to be removed when connecting multi axis drives using pre-made busbars supplied in the multi axis kits.
Figure 5-3 DC supply connections and cable routing
Larger external DC supply cables for multi axis installations (6 mm
2
to 16 mm
2
) can be accommodated using an external DC bus cable connection kit;
Installation and system accessory kits available with Digitax HD M75X series
Figure 5-4 External DC bus cable connection kit - Installation step 1
•
Attach the base assembly of the External DC bus cable connection kit to the drive (
1
).
•
Secure the DC busbar terminals with the M4 screws (
2
) supplied wit the drive.
1
DC cable grommets must be fitted when DC terminal cover breakout tabs are removed. Suitable grommets are available from the supplier
of the drive. Refer to section 2.8.1
Installation and system accessory kits available with Digitax HD M75X series
WARNING
1
2