62
Digitax HD M75X Series Installation and Technical Guide
Issue Number: 5
Table 4-15 External EMC filter ratings
For external EMC filter dimensions and terminal data refer to section 3.14
The installer of the drive is responsible for ensuring compliance with the EMC regulations that apply in the country in which the drive is to be used.
4.10.2 Grounding hardware
The drive is supplied with a cable screen bracket to facilitate EMC compliance. The bracket provides a convenient method for direct grounding of
cable shields without the use of “pig-tails”. Cable shields can be bared and clamped to the cable screen bracket using metal clips or cable ties. Note
that, where applicable, the shield must in all cases be continued through the cable screen bracket to the intended terminal on the drive, in accordance
with the connection details for the specific signal.
•
See Figure 4-10 for details on installing the cable screen bracket.
Figure 4-9 Attaching the cable screen bracket to the motor, feedback and control wiring (frame sizes 1 and 2)
•
Expose outer cable shields (
1
).
•
The cable screen bracket (
2
) must be tie wrapped to the motor, feedback and control wiring (
3
).
Part number
Number of
phases
Maximum continuous
current
Maximum voltage
rating
Power
losses at
rated
current
IP
rating
Weight
Operational
leakage current
Worst
case
leakage
current
@40
C
(104
F)
@50
C
(122
F)
IEC
UL
A
A
V
V
W
kg
lb
mA
mA
4200-3503
1
30
27.3
250
250
6.1
20
0.7
1.5
5.4
10.8
4200-5033
1
55
50.1
250
250
9.9
20
1.2
2.6
11
22
4200-6034
1
65.7
60
250
250
5.5
20
1.8
4.0
3.4
6.8
4200-8744
3
7.7
7
480
480
3.8
20
0.5
1.1
33
178.2
4200-6002
3
11
10
480
480
10
20
1.2
2.64
16
90
4200-6001
3
17
15.5
250
250
13
20
1.2
2.64
8
50
4200-1644
3
17.5
16
480
480
6.1
20
0.8
1.76
33
178.2
4200-5833
3
32.9
30
480
480
11.8
20
1.2
2.64
33
178.2
4200-3233
3
46
42
480
480
15.7
20
1.4
3.1
33
178.2
4200-5534
3
60.2
55
480
480
25.9
20
2.0
4.4
33
178.2
4200-7534
3
82.2
75
480
480
32.2
20
2.7
6.0
33
178.2
4200-0035
3
109.5
100
480
480
34.5
20
4.3
9.5
33
178.2
High ground leakage current
When an EMC filter is used, a permanent fixed ground connection must be provided which does not pass through a connector or flexible
power cord. This includes the internal EMC filter.
WARNING
NOTE
2
1
3