background image

– ENGLISH

4.2.3 Operations for connection

To make the electrical connections (“

Figure

 

7

”):

1. 

remove the terminals from their housings

2. 

connect the various devices to the relevant terminals 

according to the diagram shown in “

Figure

 

7

3. 

put the terminals back into their housings.

4. 

connect the power supply cable to terminal (

A

) and secure it 

with the cable clamp (

B

) (“

Figure

 

8

”).

If the system includes a single gearmotor only, 

connect it to terminal M2 and leave terminal M1 

free.

B

A

8

4.3  CONNECTING OTHER DEVICES TO THE 

CONTROL UNIT

If the user needs to power external devices, such as a proximity 

reader for transponder cards or the light of the key selector switch, 

power can be tapped as shown in the figure.

The power supply voltage is 24V

c

 -30% ÷ +50% with a maximum 

available current of 200mA.

STOP

SBS

(-) (+)

9

The voltage available at the “SbS” and “STOP” 

terminals remains even when the “Stand-by” 

function is enabled on the board.

4.4  ADDRESSING OF DEVICES CONNECTED 

WITH THE BLUEBUS SYSTEM

To allow the control unit to recognise the devices connected 

through the “BlueBUS” system, these devices must be addressed.

This operation can be carried out by correctly positioning the 

electrical jumper present in each device (also refer to the instruction 

manual of each device). Shown below is an addressing diagram for 

photocells, based on their type.

FOTO 1

FOTO

FOTO II

FOTO 1 II

FOTO 2

FOTO 2 II

10

Table 3

PHOTOCELL ADDRESSES

Photocell

Position of the 

jumpers

FOTO (PHOTO)

External photocell h = 50 activated during 

the closing phase (stops and reverses the 

gate’s movement)
FOTO II (PHOTO II)

External photocell h = 100 activated during 

the closing phase (stops and reverses the 

gate’s movement)
FOTO 1 (PHOTO 1)

Internal photocell h = 50 cm with activation 

both during closing (stops and reverses the 

movement) and during opening (stops and 

restarts when the photocell disengages)
FOTO 1 II (PHOTO 1 II)

Internal photocell h = 100 cm with activation 

both during closing (stops and reverses the 

movement) and during opening (stops and 

restarts when the photocell disengages)
FOTO 2 (PHOTO 2)

Internal photocell triggered during the 

opening phase (stops and reverses the 

gate’s movement)
FOTO 2 II (PHOTO 2 II)

Internal photocell triggered during the 

opening phase (stops and reverses the 

gate’s movement)
FOTO 3 (PHOTO 3)

CONFIGURATION NOT ALLOWED

At the end of the installation procedure, or after 

photocells or other devices have been removed, it is 

necessary to complete the learning procedure (see 

the “

Learning of connected devices

” paragraph).

4.5  INITIAL START-UP AND ELECTRICAL 

CONNECTIONS TEST

After powering the control unit, carry out the following checks 

(“

Figure

 

11

”):

1. 

after a few seconds, check that the 

“Bluebus”

 (

A

) LED 

flashes regularly with one flash per second

2. 

check that the LEDs of the photocells, both TX (transmission) 

and  RX  (reception),  flash.  The  type  of  flash  emitted  in  this 

phase is not significant

3. 

check that the warning light connected to the 

“Flash”

 

output is turned off.

If any one of these tests fails, disconnect the power 

supply to the control unit and check the various 

electrical connections made previously.

Содержание MC824HHS

Страница 1: ...Nice MC824HHS Control unit EN Instructions and warnings for installation and use...

Страница 2: ...care by avoiding crushing impacts falls or contact with liquids of any kind Do not place the product near sources of heat nor expose it to open flames All these actions can damage the product and caus...

Страница 3: ...type radio receiver paragraph and an IBT4N type connector which through the IBT4N interface can be used to connect BusT4 devices such as the Oview programmer see the Connecting the IBT4N interface pa...

Страница 4: ...ENTIFICATION AND OVERALL DIMENSIONS The overall dimensions and label A that allow for identifying the product are shown in Figure 2 232 mm 310 mm 122 mm A 2 3 4 TYPICAL INSTALLATION Figure 3 shows an...

Страница 5: ...ectronic circuits 3 5 INSTALLING THE CONTROL UNIT a Secure the control unit to an unmovable vertical flat surface adequately protected against possible impacts The lower part of the control unit must...

Страница 6: ...ositioned in sight of the automation If located in a concealed position it must be equipped with a system that prevents inadvertent or unauthorised reconnection of power to avoid potential hazards 4 2...

Страница 7: ...open contacts NC normally closed contacts or devices with 8 2 k fixed resistor output such as sensitive edges can be connected to this input Each device connected to this input will be individually r...

Страница 8: ...FOTO PHOTO External photocell h 50 activated during the closing phase stops and reverses the gate s movement FOTO II PHOTO II External photocell h 100 activated during the closing phase stops and reve...

Страница 9: ...mode to be assigned to the motor see Table 4 Close Open SbS Stop Bluebus 1 2 3 4 5 6 7 8 9 10 11 12 A 13 m The motor selector must be set before activating the mechanical stop learning function m Any...

Страница 10: ...trolled by M2 press f or h to stop the learning phase At this point reverse the connections of motors M1 and M2 on the terminals on the control unit and those of the respective encoders Then repeat th...

Страница 11: ...button is released LED L7 will start flashing 9 LED L7 flashes position 1 of M1 to command and move motor 1 to position 1 Figure 14 press and hold the f or h button Once the position is reached relea...

Страница 12: ...ether the leaves can be opened and closed with a force below 390 N 3 lock the motors as described in the respective instruction manual 4 using the control devices transmitter control button key select...

Страница 13: ...ction short flash OFF long flash ON 5 wait 10 seconds maximum time to exit the programming mode l To set other functions to ON or OFF while the procedure is running repeat points 2 and 3 during the ph...

Страница 14: ...10 seconds to press the buttons consecutively during the programming procedure after which time the procedure terminates automatically and memorises the changes made up to then To perform Level 2 pro...

Страница 15: ...of the movement namely the opening of the gate leaves instead the Close command does not cause any effect If the sent command remains for more than 2 seconds a Stop command is executed L6 STEP BY STEP...

Страница 16: ...nsmitter or key selector etc If everything functions properly the gate will move normally otherwise proceed with point 2 2 within 3 seconds press the control again and hold it down 3 after roughly 2 s...

Страница 17: ...e cause and increase the motor force if necessary 4 short red flashes 1 second pause 4 short red flashes Intervention of the STOP input At the start of the manoeuvre or during the movement itself the...

Страница 18: ...blown verify the cause and replace it with one having the same characteristics Green LED always on Serious anomaly There is a serious problem try disconnecting the power supply to the control unit an...

Страница 19: ...ton to shift flashing of the LED to L8 Anomaly list parameter 4 keep the g button pressed down it must be kept pressed throughout phases 5 and 6 5 wait roughly 3 seconds after which LED L1 correspondi...

Страница 20: ...mation Unlock or only from Oview the following commands Unlock and close and Unlock and open 12 Lock automation Triggers the stoppage of the manoeuvre and locks the automation the control unit will no...

Страница 21: ...CT MAINTENANCE Being an electronic part the control unit does not require any special maintenance Nonetheless the system should be regularly checked to ensure that it works efficiently at least every...

Страница 22: ...command SbS input for normally open contacts the closing of the contact triggers the Step by Step command OPEN input for normally open contacts the closing of the contact triggers the OPEN command CLO...

Страница 23: ...according to the requirements envisaged for partly completed machinery Annex II part 1 section B Directive 2006 42 EC of the EUROPEAN PARLIAMENT AND COUNCIL of 17 May 2006 related to machinery and am...

Страница 24: ...24 ENGLISH NOTES...

Страница 25: ...ystem or the programming and adjustment parameters of the control unit your installer is exclusively responsible for these operations Failure or power outage while waiting for your installer to interv...

Страница 26: ...26 ENGLISH NOTES...

Страница 27: ...ENGLISH 27 NOTES...

Страница 28: ...www niceforyou com Nice SpA Via Callalta 1 31046 Oderzo TV Italy info niceforyou com IDV0779A00EN_27 11 2020...

Отзывы: