ELECTRICAL CONNECTIONS

Terminals

Function

Description

Cable type

Flash

Warning light

Output for warning light mounting a 12 V (maximum 21 W) lamp. The 

output can be programmed (refer to the “

Level 1 programming (ON-

OFF)

” paragraph).

2 x 0.5 mm

2

ELS

Electric lock

Output for 12 V

a

 (maximum 15 VA) electric lock. The output can be 

programmed (refer to the “

Level 1 programming (ON-OFF)

” paragraph). 2 x 1.0 mm

2

OGI

OGI

“Open Gate Indicator” output for 24 V maximum 4 W signalling lamp. The 

output can be programmed (refer to the “

Level 1 programming (ON-

OFF)

” paragraph).

1 x 0.5 mm

2

ENC

Encoder 1

Motor 1 encoder input. No pole markings to observed

2 x 1.0 mm

2

ENC

Encoder 2

Motor 2 encoder input. No pole markings to observed

2 x 1.0 mm

2

Antenna

Radio receiver antenna connection

1 x RG58-type shielded 

cable

Bluebus

BlueBus

Input for compatible devices (MOFB, MOFOB, MOB and MOTB). The 

devices must be connected in parallel through two conductors carrying 

both the power supply and the communication signals. It is not necessary 

to observe the pole markings. During the learning function, each device 

connected to the control unit will be individually recognised thanks to a 

univocal code. Whenever a device is added or eliminated, the control unit 

must run the learning procedure (see “

Learning of connected devices

” 

paragraph).

2 x 0.5 mm

2

Stop

Stop

CONFIGURATION 1:

Input for devices that through their intervention trigger the immediate 

stoppage of the current manoeuvre followed by a brief reversal. NO 

(normally open) contacts, NC (normally closed) contacts or devices with 

8.2 kΩ fixed resistor output, such as sensitive edges, can be connected 

to this input. Each device connected to this input will be individually 

recognised by the control unit during the learning phase (see “

Learning 

of connected devices

” paragraph). During this phase, if the control unit 

detects any variation with respect to the learned status, it triggers a STOP. 

One or more devices, even different from one another, can be connected 

to this input: any number of NO inputs in parallel; any number of NC inputs 

in series; 2 devices with 8.2 kΩ fixed resistor output in parallel. If there 

are more than 2 devices, they must all be connected in cascade mode 

with a single 8.2 kΩ terminating resistor; 2 NO and NC devices in parallel, 

putting an 8.2 kΩ resistor in series with the NC contact (this also allows for 

combining 3 devices: NO, NC and 8.2 kΩ).

CONFIGURATION 2:

Closes motor 2.

1 x 0.5 mm

2

SbS

Step-by-step

CONFIGURATION 1:

Input for a NO (normally open) button, for sending commands in step-by-

step mode.

CONFIGURATION 2:

Opens motor 2.

1 x 0.5 mm

2

Open

Open

CONFIGURATION 1:

Input for command devices that trigger the opening manoeuvre only, when 

they intervene. NO (normally open) contacts can be connected to this 

input.

CONFIGURATION 2:

Closes motor 1.

1 x 0.5 mm

2

Close

Close

CONFIGURATION 1:

Input for command devices that trigger the closing manoeuvre only, when 

they intervene. NO (normally open) contacts can be connected to this 

input.

CONFIGURATION 2:

Opens motor 1.

1 x 0.5 mm

2

To  select  the  type  of  motor  configuration  (CONFIGURATION  1  or  CONFIGURATION  2),  refer  to  paragraph  “

Selector for choosing the type of configuration of the control unit inputs

”.

Содержание MC824HHS

Страница 1: ...Nice MC824HHS Control unit EN Instructions and warnings for installation and use...

Страница 2: ...care by avoiding crushing impacts falls or contact with liquids of any kind Do not place the product near sources of heat nor expose it to open flames All these actions can damage the product and caus...

Страница 3: ...type radio receiver paragraph and an IBT4N type connector which through the IBT4N interface can be used to connect BusT4 devices such as the Oview programmer see the Connecting the IBT4N interface pa...

Страница 4: ...ENTIFICATION AND OVERALL DIMENSIONS The overall dimensions and label A that allow for identifying the product are shown in Figure 2 232 mm 310 mm 122 mm A 2 3 4 TYPICAL INSTALLATION Figure 3 shows an...

Страница 5: ...ectronic circuits 3 5 INSTALLING THE CONTROL UNIT a Secure the control unit to an unmovable vertical flat surface adequately protected against possible impacts The lower part of the control unit must...

Страница 6: ...ositioned in sight of the automation If located in a concealed position it must be equipped with a system that prevents inadvertent or unauthorised reconnection of power to avoid potential hazards 4 2...

Страница 7: ...open contacts NC normally closed contacts or devices with 8 2 k fixed resistor output such as sensitive edges can be connected to this input Each device connected to this input will be individually r...

Страница 8: ...FOTO PHOTO External photocell h 50 activated during the closing phase stops and reverses the gate s movement FOTO II PHOTO II External photocell h 100 activated during the closing phase stops and reve...

Страница 9: ...mode to be assigned to the motor see Table 4 Close Open SbS Stop Bluebus 1 2 3 4 5 6 7 8 9 10 11 12 A 13 m The motor selector must be set before activating the mechanical stop learning function m Any...

Страница 10: ...trolled by M2 press f or h to stop the learning phase At this point reverse the connections of motors M1 and M2 on the terminals on the control unit and those of the respective encoders Then repeat th...

Страница 11: ...button is released LED L7 will start flashing 9 LED L7 flashes position 1 of M1 to command and move motor 1 to position 1 Figure 14 press and hold the f or h button Once the position is reached relea...

Страница 12: ...ether the leaves can be opened and closed with a force below 390 N 3 lock the motors as described in the respective instruction manual 4 using the control devices transmitter control button key select...

Страница 13: ...ction short flash OFF long flash ON 5 wait 10 seconds maximum time to exit the programming mode l To set other functions to ON or OFF while the procedure is running repeat points 2 and 3 during the ph...

Страница 14: ...10 seconds to press the buttons consecutively during the programming procedure after which time the procedure terminates automatically and memorises the changes made up to then To perform Level 2 pro...

Страница 15: ...of the movement namely the opening of the gate leaves instead the Close command does not cause any effect If the sent command remains for more than 2 seconds a Stop command is executed L6 STEP BY STEP...

Страница 16: ...nsmitter or key selector etc If everything functions properly the gate will move normally otherwise proceed with point 2 2 within 3 seconds press the control again and hold it down 3 after roughly 2 s...

Страница 17: ...e cause and increase the motor force if necessary 4 short red flashes 1 second pause 4 short red flashes Intervention of the STOP input At the start of the manoeuvre or during the movement itself the...

Страница 18: ...blown verify the cause and replace it with one having the same characteristics Green LED always on Serious anomaly There is a serious problem try disconnecting the power supply to the control unit an...

Страница 19: ...ton to shift flashing of the LED to L8 Anomaly list parameter 4 keep the g button pressed down it must be kept pressed throughout phases 5 and 6 5 wait roughly 3 seconds after which LED L1 correspondi...

Страница 20: ...mation Unlock or only from Oview the following commands Unlock and close and Unlock and open 12 Lock automation Triggers the stoppage of the manoeuvre and locks the automation the control unit will no...

Страница 21: ...CT MAINTENANCE Being an electronic part the control unit does not require any special maintenance Nonetheless the system should be regularly checked to ensure that it works efficiently at least every...

Страница 22: ...command SbS input for normally open contacts the closing of the contact triggers the Step by Step command OPEN input for normally open contacts the closing of the contact triggers the OPEN command CLO...

Страница 23: ...according to the requirements envisaged for partly completed machinery Annex II part 1 section B Directive 2006 42 EC of the EUROPEAN PARLIAMENT AND COUNCIL of 17 May 2006 related to machinery and am...

Страница 24: ...24 ENGLISH NOTES...

Страница 25: ...ystem or the programming and adjustment parameters of the control unit your installer is exclusively responsible for these operations Failure or power outage while waiting for your installer to interv...

Страница 26: ...26 ENGLISH NOTES...

Страница 27: ...ENGLISH 27 NOTES...

Страница 28: ...www niceforyou com Nice SpA Via Callalta 1 31046 Oderzo TV Italy info niceforyou com IDV0779A00EN_27 11 2020...

Отзывы: