Adjusting the limit switches - General information

If  a  motor  cable  is  connected  without  the  Mini  Fit  connector  (J5),  the  safety 

circuit (Thermo) must be connected to terminal X7 (J29). The electronic limit 

switch (Encoder) is then connected to terminal X7 (J34,J35).

With the D-PRO Automatic, using mechanical limit switches enables you to 

connect an additional limit switch (J33/X6) to the drive for lifting, after which you 

can select between two different OPEN positions (e.g. summer/winter positions) 

with a position switch (optional) on the cover of the D-PRO Automatic's housing. 

With electronic limit switches, the second OPEN position is adjusted when the 

limit switch itself is being programmed.
The limit switch adjustments must be done in hold-to-run mode! 
If using Nice cables, the terminals in question are pre-assembled.
Adjusting the limit switches establishes the top and bottom stop positions of 

the door.
The drive must be connected to the power supply during this procedure.

CONTROLS AND CONNECTIONS

The buttons on the cover of the housing are used to raise and lower the door, 

either locking or in hold-to-run mode. 
If  operated  in  locking  mode,  the  door  can  be  stopped  at  any  time  with  the 

STOP button.
You can also hookup and external control, such as a three-button keypad.
A pull-switch mounted inside or outside (pull-cord operated switch under the 

ceiling) controls the door in OPEN-STOP-CLOSE mode.

Connecting the OPEN, STOP, CLOSE transmitters 

For external control, a three-button keypad can be connected to the D-PRO 

Automatic's  terminal  block  X4.  The  OPEN  and  CLOSE  buttons  must  be 

configured as closing contacts.
Since the STOP button is connected to the safety circuit, it must be connected 

as an opening contact. 
If you connect a STOP button to terminal block X4, you must remove the jumper 

on terminal J15 and connect the STOP (opening contact) to it!

Connection of operating elements

OPEN, STOP, CLOSE and IMPULSE

STOP

OPEN

Imp

CLOSE

X4

J15

J16

J17

J18

Connection of 3 x button with 4-wire cable

STOP

OPEN

Imp

CLOSE

X4

J15

J16

J17

J18

Connection of a key switch

STOP

OPEN

Imp

CLOSE

X4

J15

J16

J17

J18

7

Hooking up an optoelectronic sensitive edge

Optoelectronic  sensitive  edges  are  constructed  so  that,  when  the  sensitive 

edge is actuated, a ray of light is interrupted along its entire length. In order to 

control the safety edge along its entire length, a receiver is installed at one end.

Pneumatic / 8.2 kOhm

8.2k l opto

8.2k l opto

Optical

X5

X5

8

Jumper J1 set to Opto = ready for use with optical edge

If the sensitive edge is fixed to the ground, the inversion function is neutralised 
by connecting a pre-limit switch (additional limit, pre-limit) to terminal J27 on 
terminal block X7 (mechanical limit switch only). 

The pre-limit switch must be set to around 5 cm off the ground.

X6

white - GND/0V

-  SIG  +   12V

green - output
brown - 12VDC

9

Hooking up an 8.2 kΩ safety edge

The D-PRO Automatic can be connected directly to an electric or pneumatic 
safety edge.

X6

-  SIG  +   12V

8,2 kΩ

Caution!

 If using a pneumatic sensitive edge in combination 

with the NDA010 junction box, you must also connect the 

negative of the spiral cable to terminal X6.

10

The control logic for such units is already integrated into the controller. In order 
to monitor the edge's entire electrical circuit, the edge must be connected to 
a resistance (8.2 kOhm).

The sensitive edge connects to terminal J32 (S and +) of terminal block X6                                                                     

Pneumatic / 8.2 kOhm

8.2k l opto

8.2k l opto

Optical

X5

X5

11

Jumper J1 set to 8.2 k = ready for use of pneumatic/electric pneumatic edge, 
8.2 kOhm. 

If using an impact actuated safety edge, parameter P105 must be set to 1!

Hooking up photocells

You can connect the D-PRO Automatic directly to a photocell (terminal block 
X5) to ensure safe transit. If the IR beam of the photocell is interrupted while the 
door is closing, the door stops and returns to its top position. 

CAUTION:

 If a one-way photocell with only three connection points is used, 

the switching contact and positive side of the photocell's electronics must be 
connected to terminal J30/1 with the positive potential.

If you connect a photocell, you must remove the jumper on J31, terminal block 
X5!

Содержание D-Pro Automatic R01 Series

Страница 1: ...inal operating instructions in German these operating instructions cover series R01 devices see nameplate Control unit Industrial D Pro Automatic IS0040F00MM_20 12 2016 www niceforyou com Nice S p A V...

Страница 2: ......

Страница 3: ...ing the installation the propulsion system s packaging must be disposed of in accordance with local regulations CAUTION Keep these instructions carefully as a reference for scrapping and servicing the...

Страница 4: ...03 The mounting of the housing will depend on the conditions in the installation location It may be installed in one of 3 ways a directly onto the wall using the bolts on the housing A b using the pro...

Страница 5: ...ch In this case the SCHUKO connector may be removed during the installation If using a 200V DC brake L2 N must be connected to N on terminal X1 Functions and parameters The D Pro Automatic control uni...

Страница 6: ...ULSE STOP OPEN Imp CLOSE X4 J15 J16 J17 J18 Connection of 3 x button with 4 wire cable STOP OPEN Imp CLOSE X4 J15 J16 J17 J18 Connection of a key switch STOP OPEN Imp CLOSE X4 J15 J16 J17 J18 7 Hookin...

Страница 7: ...2 If a drive with electronic limit switches is hooked up further bridges will be required in positions J26 J27 of terminal X7 All these bridges and jumpers are installed in the factory Hooking up the...

Страница 8: ...he D PRO Automatic parameters and error list addendum accompanying this manual ADJUSTING THE DIGITAL LIMIT SWITCHES Adjusting the end positions To this end set dipswitch 4 to ON ON 1 SAB 2 3 4 The upp...

Страница 9: ...1 sec The value changes by 10 units sec Hold the button down for 3 sec The value changes by 100 units sec Automatic Closing If the automatic close function is enabled the door closes after the time se...

Страница 10: ...8 English EN Schematic overview D PRO Automatic 2 2kW...

Страница 11: ...ke Starter condenser board connector Motor terminals PE terminals Select lower sensitive edge Controller board Sensitive edge terminal clamps Mains terminals Transit photocell terminal clamps Key swit...

Страница 12: ...10 English EN Front board D PRO Automatic 2 2kW Dipswitch CLOSE button OPEN button Controller board cable D PRO housing front view front board with display...

Страница 13: ...PRO AUTOMATIC 2 2kW D PRO AUTOMATIC 5 5kW Power supply 3 x 400V AC 50Hz protected by 6 10A fuse 3 x 400V AC 50Hz protected by 10A fuse Motor power up to 2 2kW up to 5 5kW Motor connection 3 NO contac...

Страница 14: ......

Страница 15: ......

Страница 16: ...11 20 5 2 2 5 5 10 6 50 400 3 10 50 400 3 2 2 5 5 3 3 2 2 400 5 5 400 AT 6 3 4 4 50 20 50 20 0 8 24...

Страница 17: ...10 2 2 CLOSE CLOSE...

Страница 18: ...9 2 2 OXI 200 PE 2 1 N O N O N O N C TYKO Mini Fit...

Страница 19: ...8 2 2...

Страница 20: ...7 DIP OFF ON 1 0 ON 4 1 ON 4 1 ON 1 0 ON 1 ON 4 1 4 OFF ON 4 1 10 100 3 41 OPEN EE 1 P70 0 P5 1 P5 2 P5 1 P29 CLOSE CLOSE...

Страница 21: ...X7 MiniFit AMP 3 X7 MiniFit AMP 4 X7 MiniFit AMP 2 X7 MiniFit AMP 5 X7 MiniFit AMP 6 X7 MiniFit AMP 1 CLOSED 3 E OPEN 1 E 4 SE 2 SE 4 SE 2 SE 7 P2 8 P2 5 P1 6 P1 6 5 16 dip 4 ON SAB OFF 4 4 ON OFF 4...

Страница 22: ...led OXI 106 14 J10 X2 J15 X4 J31 X5 J33 X6 6 5 X8 2 1 X9 X7 J27 J26 MLT ML 230 MLT ML 7 X3 X1 L1 9 X3 X1 N ML ML T N L1 L2 L3 X1 X3 15 X1 230 MLT ML 6 105 2 7 2 6 5 4 3 2 1 2 8 2 7 1 6 1 5 4 3 2 1 P2...

Страница 23: ...PEN OPEN STOP X4 X4 J15 X4 J15 J16 J17 J18 3X X4 J15 J16 J17 J18 X4 J15 J16 J17 J18 7 kOhm 8 2k l opto 8 2k l opto X 5 X 5 8 Opto J1 J27 X7 5 X6 GND 0V SIG output 12VDC 9 8 2 X6 SIG NDA010 X6 10 8 2 X...

Страница 24: ...2 0 25 2 3 10 4 5 1 X1 L3 N L2 L1 PE 3 PE N L3 L2 L1 16 CEE CEE EP N L3 L2 L1 X1 16 3 PE X1 N L2 L1 4 PE L2 L1 SCHUKO 200 SCHUKO X1 N L2 N 50 CEE 2 P 75 75 L3 N 2 PE V U W B D A L2 L1 V W U C L3 N L2...

Страница 25: ...2 01 02 03 2 4 NDA530 20 04 1 4 2...

Страница 26: ...1 R01 1 1 2 3 4 5 6 7 8 2 2 9 2 2 10 2 2 11 11 D PRO 400 230 13241 1...

Страница 27: ......

Страница 28: ...utomatic IS0040F00MM_20 12 2016 www niceforyou com Nice S p A Via Pezza Alta 13 31046 Oderzo TV Italy info niceforyou com Original operating instructions in German these operating instructions cover s...

Отзывы: